Dedicated Outdoor Air Systems (DOAS)
Fundamental Concept
Dedicated Outdoor Air Systems (DOAS) represent a paradigm shift in HVAC design by decoupling ventilation air treatment from space sensible cooling. Unlike conventional systems where outdoor air mixes with return air before conditioning, DOAS handles 100% outdoor air in a separate dedicated unit, delivering pretreated ventilation air directly to spaces or to terminal units.
The core principle: one system handles latent loads and ventilation (DOAS), while separate systems address sensible cooling loads (radiant panels, chilled beams, fan coils, or variable refrigerant flow systems).
ASHRAE 62.1 Compliance
ASHRAE Standard 62.1 requires minimum ventilation rates based on occupancy and floor area. DOAS simplifies compliance by:
- Delivering consistent ventilation airflow regardless of space load conditions
- Eliminating variable outdoor air fraction issues inherent in VAV systems
- Enabling direct measurement and verification of outdoor air delivery
- Maintaining ventilation effectiveness (Ez) more reliably
Ventilation requirement calculation per ASHRAE 62.1:
Vbz = RpPz + RaAz
Where:
- Vbz = breathing zone outdoor airflow (cfm)
- Rp = people outdoor air rate (cfm/person)
- Ra = area outdoor air rate (cfm/ft²)
- Pz = zone population
- Az = zone floor area (ft²)
For a typical office space (Rp = 5 cfm/person, Ra = 0.06 cfm/ft²):
- 3,000 ft² space with 15 people
- Vbz = (5 × 15) + (0.06 × 3,000) = 75 + 180 = 255 cfm
System Configurations
Parallel Configuration
In parallel DOAS, ventilation air delivers directly to spaces, independent of terminal units.
graph LR
A[Outdoor Air] --> B[DOAS Unit]
B --> C[Energy Recovery]
C --> D[Cooling Coil]
D --> E[Heating Coil]
E --> F[Supply Fan]
F --> G[Zone 1 Diffuser]
F --> H[Zone 2 Diffuser]
F --> I[Zone 3 Diffuser]
J[Sensible System] --> K[Fan Coil Zone 1]
J --> L[Fan Coil Zone 2]
J --> M[Fan Coil Zone 3]
style B fill:#e1f5ff
style J fill:#ffe1e1
Advantages:
- True decoupling of ventilation and sensible loads
- Terminal units handle only sensible loads (smaller equipment)
- Simplified terminal unit controls
- Enhanced humidity control at DOAS unit
Disadvantages:
- Requires separate ductwork distribution for DOAS
- Higher initial installation cost
- More ceiling space for dual distribution systems
Series Configuration
In series DOAS, ventilation air delivers to terminal unit inlets, mixing with recirculated air.
graph LR
A[Outdoor Air] --> B[DOAS Unit]
B --> C[Preconditioned OA]
C --> D[Fan Coil 1 Inlet]
C --> E[Fan Coil 2 Inlet]
C --> F[Fan Coil 3 Inlet]
G[Return Air] --> D
G --> E
G --> F
D --> H[Mixed Air Cooling]
E --> I[Mixed Air Cooling]
F --> J[Mixed Air Cooling]
H --> K[Zone 1]
I --> L[Zone 2]
J --> M[Zone 3]
style B fill:#e1f5ff
Advantages:
- Single ductwork distribution system
- Lower installation cost
- Less ceiling space required
- Simplified architecture
Disadvantages:
- Terminal units must handle combined ventilation and sensible loads (larger equipment)
- Less precise humidity control at zone level
- Potential for mixing losses
Dehumidification Strategies
Conventional Cooling Coil Approach
DOAS cooling coils operate at lower apparatus dew point (ADP) temperatures than conventional systems to achieve deeper dehumidification.
Latent cooling capacity:
QL = 4,840 × cfm × Δω
Where:
- QL = latent cooling capacity (Btu/hr)
- cfm = airflow rate
- Δω = humidity ratio difference (lbw/lbda)
- 4,840 = conversion constant (60 min/hr × 0.075 lbda/ft³ × 1,076 Btu/lbw)
Example calculation:
- Outdoor air: 95°F DB, 75°F WB (ω = 0.0146 lbw/lbda)
- Target supply: 55°F DB, 95% RH (ω = 0.0095 lbw/lbda)
- Airflow: 2,000 cfm
QL = 4,840 × 2,000 × (0.0146 - 0.0095)
QL = 4,840 × 2,000 × 0.0051
QL = 49,368 Btu/hr (4.1 tons latent)
Sensible cooling capacity:
QS = 1.08 × cfm × ΔT
QS = 1.08 × 2,000 × (95 - 55)
QS = 86,400 Btu/hr (7.2 tons sensible)
Total cooling: 135,768 Btu/hr (11.3 tons)
Sensible Heat Ratio (SHR):
SHR = QS / (QS + QL) = 86,400 / 135,768 = 0.64
This low SHR (typically 0.55-0.70 for DOAS) contrasts with conventional systems (SHR 0.75-0.85), demonstrating DOAS focus on latent removal.
Desiccant Dehumidification
For extreme humidity conditions or when very low dew points are required, desiccant wheels provide chemical dehumidification without overcooling.
graph TD
A[Hot Humid OA<br/>95°F, 75°F WB] --> B[Desiccant Wheel]
B --> C[Hot Dry Air<br/>130°F, 50°F WB]
C --> D[Sensible Cooling Coil]
D --> E[Supply Air<br/>65°F, 50°F DP]
F[Exhaust Air] --> G[Heating Coil<br/>Regeneration]
G --> H[Hot Regeneration<br/>180-200°F]
H --> I[Desiccant Wheel<br/>Reactivation]
I --> J[Humid Exhaust]
style B fill:#ffd700
style I fill:#ffd700
Desiccant wheel performance:
- Moisture removal: 40-60 grains/lb (0.006-0.009 lbw/lbda)
- Regeneration temperature: 180-220°F
- Energy recovery potential: 50-70% sensible effectiveness
- Pressure drop: 0.4-0.8 in. w.g.
Energy Recovery Integration
Energy recovery dramatically reduces DOAS operating costs by preconditiong outdoor air with exhaust air energy.
Total effectiveness:
ηt = (h1 - h2) / (h1 - h4)
Where:
- h1 = entering outdoor air enthalpy
- h2 = leaving outdoor air enthalpy (after recovery)
- h4 = entering exhaust air enthalpy
Example with enthalpy wheel (75% total effectiveness):
Summer condition:
- Outdoor air: 95°F, 75°F WB (h = 38.3 Btu/lb)
- Exhaust air: 75°F, 50% RH (h = 28.1 Btu/lb)
- After recovery: h2 = 38.3 - 0.75(38.3 - 28.1) = 30.6 Btu/lb
This represents precooling from 95°F to approximately 78°F before mechanical cooling.
Annual energy savings:
Savings = 4.5 × cfm × Δh × hours
For 2,000 cfm, 7.7 Btu/lb enthalpy reduction, 3,000 cooling hours:
Savings = 4.5 × 2,000 × 7.7 × 3,000 = 207,900,000 Btu/year
At $0.12/kWh (0.8 COP): $9,100 annual savings
Neutral vs. Cold Supply Air
Neutral Supply Strategy (55-65°F)
Delivers air near space temperature to minimize sensible impact on zones:
- Reduces terminal unit reheat requirements
- Allows smaller terminal units (sensible-only sizing)
- Optimal for radiant cooling systems
- Typical supply: 60-65°F in cooling mode
Cold Supply Strategy (48-55°F)
Delivers cold air to provide both latent and partial sensible cooling:
- Reduces terminal unit cooling capacity requirements
- May eliminate some terminal units in low-load spaces
- Requires reheat for ventilation-dominated zones
- Typical supply: 50-55°F
Trade-off analysis: Neutral supply maximizes decoupling benefits but requires full-capacity sensible systems. Cold supply provides sensible cooling assistance but increases reheat penalties and defeats pure decoupling advantages.
Load Calculation Methodology
DOAS Sizing Components
1. Ventilation airflow (ASHRAE 62.1):
- Calculate per space type and occupancy
- Sum all zones served by DOAS unit
- Add distribution losses if applicable
2. Latent load:
QL = 4,840 × cfm × (ωOA - ωsupply)
3. Sensible load:
QS = 1.08 × cfm × (TOA - Tsupply)
4. Dehumidification capacity check:
Verify coil ADP and contact factor can achieve target humidity:
Tsupply = Tcoil,ADP + CF × (Tmixed - Tcoil,ADP)
Where CF = coil contact factor (typically 0.85-0.95)
Design Day Example
Project: 20,000 ft² office building, 100 occupants Location: Atlanta, GA (Summer design: 94°F DB, 74°F WB)
Step 1: Ventilation requirement
V = (5 cfm/person × 100) + (0.06 cfm/ft² × 20,000)
V = 500 + 1,200 = 1,700 cfm
Step 2: Target supply conditions
- Supply: 55°F, 90% RH (ω = 0.0085 lbw/lbda)
- Outdoor: 94°F, 74°F WB (ω = 0.0142 lbw/lbda)
Step 3: Cooling loads
Latent:
QL = 4,840 × 1,700 × (0.0142 - 0.0085) = 46,903 Btu/hr
Sensible:
QS = 1.08 × 1,700 × (94 - 55) = 71,604 Btu/hr
Total: 118,507 Btu/hr (9.9 tons)
With 70% effective energy recovery:
Net cooling = 118,507 × (1 - 0.70) = 35,552 Btu/hr (3.0 tons)
DOAS equipment selection: 3-ton DX unit with enthalpy wheel
Control Strategies
Supply air temperature reset:
- Monitor zone humidity levels
- Reset supply temperature between 50-65°F based on dehumidification demand
- Prevents overcooling when latent loads are low
Demand-based ventilation:
- Modulate outdoor air based on CO₂ sensors (if occupancy varies)
- Maintain minimum code-required ventilation
- Reduces energy during unoccupied or low-occupancy periods
Bypass control:
- During mild conditions, bypass cooling coil
- Use energy recovery only for preconditioning
- Economizer operation when outdoor conditions favorable
Benefits Summary
| Benefit Category | Quantified Impact |
|---|---|
| IAQ consistency | 100% outdoor air delivery, no VAV turndown issues |
| Humidity control | Space RH maintained 40-60% vs. 35-70% conventional |
| Energy savings | 20-40% reduction in HVAC energy vs. constant volume |
| Equipment downsizing | Terminal units 30-50% smaller (sensible-only) |
| Maintenance | Centralized OA treatment, simplified zone equipment |
| Comfort | Elimination of cold drafts, improved distribution |
DOAS architecture provides superior ventilation performance, precise humidity control, and significant energy savings through intelligent decoupling of ventilation from sensible cooling loads. Proper design requires careful analysis of climate conditions, load profiles, and integration with sensible cooling systems to maximize benefits.
File: /Users/evgenygantman/Documents/github/gantmane/hvac/content/ventilation-indoor-air-quality/ventilation-systems/dedicated-outdoor-air-systems/_index.md