Ventilation Systems: Design and Performance
Fundamental Principles
Ventilation systems provide outdoor air to occupied spaces to dilute and remove contaminants while maintaining acceptable indoor air quality. The primary functions include:
- Contaminant Dilution: Reducing concentrations of occupant-generated pollutants (CO₂, bioeffluents, VOCs)
- Moisture Control: Managing latent loads from occupants and processes
- Odor Management: Maintaining acceptable sensory conditions
- Pressurization Control: Preventing infiltration and managing airflow patterns between zones
The dilution principle follows mass balance:
$$C = \frac{G}{Q} + C_o \left(1 - e^{-Qt/V}\right)$$
Where:
- $C$ = indoor contaminant concentration (ppm or mg/m³)
- $G$ = contaminant generation rate (mass/time)
- $Q$ = outdoor air flow rate (volume/time)
- $C_o$ = outdoor contaminant concentration
- $V$ = space volume
- $t$ = time
At steady-state equilibrium:
$$C_{ss} = \frac{G}{Q} + C_o$$
This relationship demonstrates that doubling outdoor airflow reduces the steady-state concentration increment by half.
Ventilation Rate Determination
ASHRAE Standard 62.1 establishes minimum ventilation rates using the Ventilation Rate Procedure (VRP):
$$V_{oz} = R_p \times P_z + R_a \times A_z$$
Where:
- $V_{oz}$ = outdoor air requirement for zone (cfm)
- $R_p$ = people outdoor air rate (cfm/person)
- $P_z$ = zone population
- $R_a$ = area outdoor air rate (cfm/ft²)
- $A_z$ = zone floor area (ft²)
For multiple-zone systems, the system outdoor air intake must account for the fraction of outdoor air in the supply:
$$V_{ot} = \frac{\sum_{all\ zones} V_{oz}}{E_v}$$
Where $E_v$ is the system ventilation efficiency, ranging from 0.6 to 1.0 depending on system configuration.
Ventilation System Categories
Mechanical Ventilation Systems
Constant Volume Systems Supply fixed airflow rates regardless of load variations. Outdoor air is typically controlled by dampers maintaining minimum position or CO₂ concentration.
Variable Air Volume (VAV) Systems Modulate supply airflow based on thermal load. Outdoor air control must compensate for varying supply rates:
$$%OA_{min} = \frac{V_{ot}}{V_{supply}}$$
As supply airflow decreases during part-load, the outdoor air damper opens to maintain required ventilation rate.
Dedicated Outdoor Air Systems (DOAS) Decouple ventilation from thermal conditioning. The DOAS handles 100% outdoor air, pre-conditioning it before delivery. Parallel terminal units manage sensible loads independently.
Natural Ventilation
Utilizes driving forces from wind and temperature differences (stack effect). Effective opening area required:
$$A_{eff} = \frac{Q}{\sqrt{2 \times \frac{\Delta P}{\rho}}}$$
Where $\Delta P$ represents wind or buoyancy-driven pressure difference.
Ventilation System Comparison
| System Type | Outdoor Air Control | Energy Recovery Potential | Application |
|---|---|---|---|
| Single-Zone CAV | Fixed damper position | Limited | Small buildings, constant occupancy |
| VAV with Reset | Airflow tracking or CO₂ | Moderate via economizer | Office buildings, variable loads |
| DOAS + Parallel | 100% dedicated | High via ERV/HRV | All climates, high ventilation needs |
| Natural Ventilation | Opening modulation | None (free cooling) | Mild climates, low sensible loads |
| Demand-Controlled | CO₂ or occupancy sensors | Variable | Assembly spaces, variable density |
Air Change Rate Method
An alternative approach expresses ventilation as air changes per hour (ACH):
$$ACH = \frac{Q \times 60}{V}$$
Converting to outdoor air rate:
$$Q = \frac{ACH \times V}{60}$$
Typical requirements:
- Residential: 0.35 ACH minimum (ASHRAE 62.2)
- Offices: 4-6 ACH total, 15-20% outdoor air
- Laboratories: 6-12 ACH minimum, often 100% outdoor air
- Healthcare isolation rooms: 12 ACH with negative pressure
Ventilation Effectiveness
Not all ventilation air equally reaches the breathing zone. Ventilation effectiveness ($E_v$) accounts for short-circuiting and stratification:
$$E_v = \frac{C_e - C_s}{C_r - C_s}$$
Where:
- $C_e$ = exhaust contaminant concentration
- $C_r$ = breathing zone concentration
- $C_s$ = supply air concentration
Perfect mixing yields $E_v$ = 1.0. Displacement ventilation can achieve $E_v$ > 1.0, while poor distribution results in $E_v$ < 1.0.
Energy Considerations
Ventilation represents a significant energy load:
$$Q_{sensible} = 1.08 \times Q \times (T_o - T_s)$$
$$Q_{latent} = 4840 \times Q \times (W_o - W_s)$$
Where $Q$ is in cfm, temperatures in °F, and humidity ratios in lb_w/lb_da.
Annual ventilation energy in climates with heating and cooling seasons often exceeds 30% of total HVAC energy consumption. Energy recovery systems can reduce this by 50-80% depending on climate.
Pressurization Strategy
Building pressure relationships control contaminant migration:
- Positive Pressure: Supply > exhaust, prevents infiltration
- Negative Pressure: Exhaust > supply, contains contaminants
- Neutral Pressure: Balanced flows, minimal driving force
Pressure differential typically ranges from 0.02 to 0.05 in. w.c. between zones requiring separation.
System Integration
Modern ventilation systems integrate with:
- Building automation: Scheduling, reset strategies, demand control
- Energy management: Economizer cycles, heat recovery optimization
- Indoor air quality monitoring: CO₂, VOC, particulate sensors
- Life safety: Smoke control, emergency ventilation modes
flowchart TD
A[Outdoor Air Intake] --> B[Filtration]
B --> C{Energy Recovery?}
C -->|Yes| D[ERV/HRV]
C -->|No| E[Mixing Plenum]
D --> E
E --> F[Heating/Cooling Coils]
F --> G[Supply Fan]
G --> H[Distribution Ductwork]
H --> I[Terminal Devices]
I --> J[Occupied Zones]
J --> K[Return Air Path]
K --> L{Economizer Mode?}
L -->|Yes| E
L -->|No| M[Exhaust/Relief]
style A fill:#e1f5ff
style J fill:#fff4e1
style D fill:#e8f5e9
Design Best Practices
- Size outdoor air intakes for peak ventilation requirements with adequate free area (face velocity < 500 fpm)
- Locate intakes minimum 25 ft from exhaust outlets, loading docks, and other contamination sources
- Provide adequate mixing between outdoor and return air (minimum 5 ft mixing section)
- Install airflow measurement at outdoor air intakes for commissioning and verification
- Design for turndown in VAV systems maintaining minimum ventilation at all supply rates
- Consider bypass for energy recovery during mild conditions when outdoor air is suitable for free cooling
- Implement demand control only where occupancy varies significantly and unpredictably
These principles establish the foundation for effective ventilation system design that balances indoor air quality requirements with energy efficiency across all operating conditions.
Sections
Ventilation Principles and Fundamentals
Core principles of dilution ventilation, contaminant removal equations, air change methods, and ASHRAE 62.1 ventilation rate procedures for indoor air quality.
Natural Ventilation Design
Physics-based design guidance for natural ventilation systems including stack effect calculations, wind-driven airflow, opening sizing methodology, and hybrid system integration strategies.
Mechanical Ventilation Systems Engineering
Comprehensive engineering analysis of supply, exhaust, and balanced mechanical ventilation systems with fan power calculations, ASHRAE 62.1 requirements, and system performance optimization.
Energy Recovery Ventilation Systems
Technical analysis of ERV and HRV systems including effectiveness calculations, NTU method, enthalpy wheels, fixed plate exchangers, and climate-specific selection criteria per ASHRAE 90.1.
Demand Controlled Ventilation
Demand controlled ventilation (DCV) modulates outdoor air delivery based on actual occupancy or indoor air quality conditions rather than design occupancy. This strategy reduces energy consumption by eliminating unnecessary ventilation during periods of low or variable occupancy.
Fundamental Principles
DCV operates on the premise that ventilation requirements are directly proportional to occupant density and metabolic activity. By continuously monitoring space conditions, the system adjusts outdoor air intake to maintain acceptable indoor air quality while minimizing conditioning energy.
Dedicated Outdoor Air Systems (DOAS)
Comprehensive analysis of dedicated outdoor air systems including decoupled ventilation strategies, dehumidification approaches, parallel and series configurations, and energy recovery integration for optimized indoor air quality and energy performance.
Kitchen Ventilation
Components
- Type I Exhaust Hoods
- Type Ii Exhaust Hoods
- Grease Laden Vapor
- Capture Velocity
- Hood Design Factors
- Canopy Hoods
- Proximity Hoods
- Backshelf Hoods
- Pass Over Hoods
- Eyebrow Hoods
- Exhaust Flow Rate Calculation
- Makeup Air Requirements
- Tempered Makeup Air
- Direct Fired Makeup Air
- Heated Makeup Air
- Transfer Air
- Grease Duct Requirements
- Fire Suppression Integration
- Ul Listed Equipment
- Nfpa 96 Compliance
- Access Panels Cleaning
- Variable Speed Exhaust
- Demand Ventilation Kitchen
- Optics Based Controls
- Temperature Based Controls
Laboratory Ventilation
Components
- Fume Hood Types
- Constant Volume Fume Hoods
- Variable Air Volume Fume Hoods
- Bypass Fume Hoods
- Auxiliary Air Fume Hoods
- Ductless Fume Hoods
- Face Velocity Requirements
- Sash Position Monitoring
- Containment Testing
- Smoke Testing Annual
- Face Velocity Measurement
- Manifold Exhaust Systems
- Scrubber Systems
- Perchloric Acid Hoods
- Radioisotope Hoods
- Biosafety Cabinets
- Class I Bsc
- Class Ii Type A1 Bsc
- Class Ii Type A2 Bsc
- Class Ii Type B1 Bsc
- Class Ii Type B2 Bsc
- Class Iii Bsc
- Clean Benches
- Laminar Flow Benches
- Makeup Air Laboratory
- Lab Pressurization
- Once Through Air Systems
Hybrid Mixed-Mode Ventilation Systems
Technical analysis of hybrid ventilation combining natural and mechanical systems, control strategies, switching criteria, and design optimization methods.