Indoor Air Quality Management

Indoor Air Quality Management

Indoor air quality management represents a critical building environmental control discipline directly impacting occupant health, cognitive performance, and productivity. Modern IAQ practice integrates ventilation engineering, contaminant source control, air cleaning technologies, and continuous monitoring to maintain acceptable air within occupied spaces.

Fundamental IAQ Parameters

Contaminant Mass Balance

The steady-state contaminant concentration in a well-mixed zone follows the fundamental mass balance equation:

$$C_{ss} = \frac{S + Q_{oa} C_{oa}}{Q_{oa} + kV}$$

Where:

  • $C_{ss}$ = steady-state indoor concentration (µg/m³)
  • $S$ = contaminant generation rate (µg/h)
  • $Q_{oa}$ = outdoor air ventilation rate (m³/h)
  • $C_{oa}$ = outdoor air concentration (µg/m³)
  • $k$ = first-order decay/removal rate (h⁻¹)
  • $V$ = space volume (m³)

This equation demonstrates three primary control strategies: source reduction (decrease $S$), dilution ventilation (increase $Q_{oa}$), and active removal (increase $k$ through filtration or sorption).

Carbon Dioxide as Ventilation Indicator

CO₂ serves as a surrogate for occupant bioeffluent dilution. The steady-state CO₂ concentration above outdoor levels:

$$C_{CO_2} - C_{CO_2,oa} = \frac{N \cdot G}{Q_{oa}}$$

Where:

  • $N$ = number of occupants
  • $G$ = CO₂ generation rate per person (L/h·person)
  • Typical $G$ values: 18 L/h (sedentary), 38 L/h (moderate activity), 75 L/h (heavy work)

For target indoor CO₂ of 1000 ppm with 400 ppm outdoor concentration, required outdoor air per person:

$$\frac{Q_{oa}}{N} = \frac{G}{(C_{CO_2} - C_{CO_2,oa}) \times 10^6} \times \frac{10^6 \text{ L}}{m^3}$$

Substituting $G = 18$ L/h·person and 600 ppm differential yields approximately 30 m³/h·person (8.5 L/s·person) minimum ventilation.

graph TD
    A[IAQ Control Strategies] --> B[Source Control]
    A --> C[Dilution Ventilation]
    A --> D[Air Cleaning]

    B --> B1[Material Selection]
    B --> B2[Process Modification]
    B --> B3[Local Exhaust]

    C --> C1[Outdoor Air]
    C --> C2[Air Distribution]
    C --> C3[Ventilation Effectiveness]

    D --> D1[Particulate Filtration]
    D --> D2[Gaseous Adsorption]
    D --> D3[UV/PCO Treatment]

    style A fill:#f9f,stroke:#333,stroke-width:3px
    style B fill:#bfb,stroke:#333,stroke-width:2px
    style C fill:#bbf,stroke:#333,stroke-width:2px
    style D fill:#fbb,stroke:#333,stroke-width:2px

ASHRAE 62.1 Compliance Paths

Ventilation Rate Procedure

The Ventilation Rate Procedure (VRP) prescribes minimum outdoor air based on occupancy and floor area. The breathing zone outdoor airflow:

$$V_{bz} = R_p \cdot P_z + R_a \cdot A_z$$

Where:

  • $V_{bz}$ = breathing zone outdoor airflow (L/s or cfm)
  • $R_p$ = outdoor air rate per person (L/s·person or cfm/person)
  • $P_z$ = zone population (people)
  • $R_a$ = outdoor air rate per unit area (L/s·m² or cfm/ft²)
  • $A_z$ = zone floor area (m² or ft²)

For multiple zones with central outdoor air system, system outdoor air intake:

$$V_{ot} = \sum_{all zones} \frac{V_{oz}}{E_z} + V_{ou}$$

Where:

  • $V_{ot}$ = outdoor air intake flow (L/s)
  • $V_{oz}$ = zone outdoor air (L/s)
  • $E_z$ = zone air distribution effectiveness (typically 0.8-1.2)
  • $V_{ou}$ = unconditioned space outdoor air (L/s)
Space Type$R_p$ (L/s·person)$R_a$ (L/s·m²)Typical Application
Office Space2.50.3General office, conference rooms
Classrooms5.00.3Educational spaces, ages 9+
Retail3.80.3Sales floors, merchandising
Gymnasium100.3Sports facilities, exercise spaces
Conference/Meeting2.50.3Meeting rooms <13 m² per person
Food Preparation3.80.9Commercial kitchens
Laboratories5.00.9General laboratory spaces

IAQ Procedure

The IAQ Procedure requires demonstrating that contaminant concentrations remain below maximum acceptable levels. For each contaminant $i$:

$$C_i \leq C_{max,i}$$

The required outdoor air rate accounting for source strength, outdoor concentration, and removal mechanisms:

$$Q_{oa} = \frac{S_i - kV(C_{max,i} - C_{oa,i})}{C_{max,i} - C_{oa,i}}$$

The IAQ Procedure permits reduced outdoor air when source control, air cleaning, or other methods achieve acceptable contaminant levels. Verification requires measurement or validated modeling demonstrating compliance.

IAQ Performance Metrics

Ventilation Effectiveness

Air change effectiveness characterizes how efficiently ventilation air reaches occupied zones:

$$\epsilon_a = \frac{C_e - C_s}{C_r - C_s}$$

Where:

  • $\epsilon_a$ = air change effectiveness
  • $C_e$ = exhaust air concentration
  • $C_s$ = supply air concentration
  • $C_r$ = room average concentration

Values: $\epsilon_a > 1.0$ indicates better-than-perfect mixing, $\epsilon_a = 1.0$ represents perfect mixing, $\epsilon_a < 1.0$ indicates short-circuiting.

Contaminant removal effectiveness evaluates pollutant clearance:

$$\epsilon_c = \frac{C_r - C_s}{C_{breathing} - C_s}$$

Where $C_{breathing}$ represents contaminant concentration at breathing zone.

Particle Penetration and Deposition

Indoor particulate concentration depends on outdoor sources, penetration efficiency, deposition, and filtration:

$$\frac{dC_p}{dt} = P \cdot \lambda_v (C_{p,oa} - C_p) + \frac{S_p}{V} - \lambda_d C_p - \eta_f \lambda_r C_p$$

At steady state ($dC_p/dt = 0$):

$$C_p = \frac{P \lambda_v C_{p,oa} + S_p/V}{\lambda_v + \lambda_d + \eta_f \lambda_r}$$

Where:

  • $P$ = building penetration factor (0.4-1.0)
  • $\lambda_v$ = ventilation rate (h⁻¹)
  • $\lambda_d$ = deposition rate (h⁻¹, typically 0.1-0.6 for PM₂.₅)
  • $\eta_f$ = filtration efficiency
  • $\lambda_r$ = recirculation rate (h⁻¹)
  • $S_p$ = indoor particle generation rate (µg/h)
flowchart LR
    A[Outdoor Air<br/>Sources] --> B{Building<br/>Envelope}
    B -->|Penetration P| C[Indoor Air]
    D[Internal<br/>Sources] --> C
    C --> E{Deposition}
    C --> F{Filtration}
    C --> G{Ventilation}
    E --> H[Surfaces]
    F --> I[Filter Media]
    G --> J[Exhaust]

    style C fill:#e1f5ff,stroke:#333,stroke-width:2px
    style B fill:#ffe1e1,stroke:#333,stroke-width:2px
    style F fill:#e1ffe1,stroke:#333,stroke-width:2px

Health Effects and Exposure Assessment

Dose-Response Relationships

Inhalation exposure dose integrates concentration and breathing rate over time:

$$D = \int_0^t C(t) \cdot BR(t) \cdot dt$$

For constant concentration and breathing rate:

$$D = C \cdot BR \cdot t$$

Where:

  • $D$ = inhaled dose (µg or mg)
  • $C$ = contaminant concentration (µg/m³)
  • $BR$ = breathing rate (m³/h, typically 0.5-0.7 m³/h sedentary, 1.5-2.5 m³/h active)
  • $t$ = exposure duration (h)

Deposited dose in respiratory tract depends on particle size, breathing pattern, and deposition efficiency:

$$D_{dep} = D \cdot \eta_{dep}(d_p, Q_b)$$

Where $\eta_{dep}$ varies from 10-30% for 0.1-1.0 µm particles to 70-90% for >5 µm particles.

Comparison: Traditional vs. Performance-Based IAQ

AspectVentilation Rate ProcedureIAQ Procedure
ApproachPrescriptive dilutionPerformance-based verification
Design ComplexityLow - table lookupHigh - detailed analysis
FlexibilityLimited - fixed ratesHigh - innovative solutions
Outdoor AirMinimum specified ratesOptimized to maintain C < C_max
Source ControlAssumed standard materialsExplicitly quantified and credited
Air CleaningNot credited for OA reductionCan reduce OA requirements
VerificationAirflow measurementContaminant concentration measurement
Energy ImpactFixed ventilation energyPotential significant reduction
ApplicationStandard buildingsUnique buildings, tight envelopes
RiskLower - established approachHigher - requires validation

Monitoring and Control Strategies

Multi-Parameter IAQ Monitoring

Comprehensive IAQ assessment requires simultaneous measurement of multiple parameters. Critical measurements include:

Temperature and Humidity: Thermal comfort per ASHRAE 55 (20-26°C, 30-60% RH) and mold prevention (surface RH <80%).

CO₂ Concentration: Ventilation adequacy indicator. Target <1000 ppm for good IAQ, <800 ppm for enhanced cognitive performance. Demand-controlled ventilation modulates outdoor air based on real-time CO₂:

$$Q_{oa}(t) = Q_{oa,min} + K \cdot (C_{CO_2}(t) - C_{setpoint})$$

Particulate Matter: PM₂.₅ and PM₁₀ mass concentrations. WHO guideline: 15 µg/m³ (24-h mean) for PM₂.₅. Particle counts differentiate size fractions.

Volatile Organic Compounds: Total VOC screening via PID or metal oxide sensors. Individual VOC speciation requires GC-MS for formaldehyde, benzene, toluene quantification.

Pressure Relationships: Maintain positive pressure (+2.5 to +12.5 Pa) in clean spaces relative to surrounding areas to prevent contaminant infiltration.

Control Hierarchy

  1. Elimination: Remove contaminant sources through material substitution or process redesign
  2. Substitution: Replace high-emission materials with low-VOC alternatives
  3. Engineering Controls: Local exhaust ventilation at point of generation
  4. Administrative Controls: Occupancy scheduling, maintenance procedures
  5. Dilution Ventilation: General outdoor air supply as final defense
  6. Personal Protection: Last resort for extreme exposures

Integration with Building Systems

IAQ management requires coordination across building systems. HVAC systems provide primary control through outdoor air delivery, filtration, and contaminant dilution. Building envelope design controls infiltration, moisture entry, and outdoor pollutant penetration. Space pressurization prevents cross-contamination between zones with differential pressure control. Humidity management through cooling coil condensate removal and supplemental dehumidification prevents microbial amplification. Air distribution design ensures adequate air change effectiveness and prevents stagnant zones.

The optimal IAQ strategy balances health outcomes, energy consumption, capital costs, and operational complexity. Advanced buildings integrate real-time IAQ sensors with building automation systems for responsive control, achieving superior air quality while minimizing energy waste through precision ventilation delivery matched to actual occupancy and contamination levels.

References to Standards

  • ASHRAE 62.1: Ventilation for Acceptable Indoor Air Quality
  • ASHRAE 55: Thermal Environmental Conditions for Human Occupancy
  • ASHRAE 52.2: Method of Testing General Ventilation Air-Cleaning Devices for Removal Efficiency by Particle Size
  • ASHRAE 145.1: Laboratory Test Method for Assessing the Performance of Gas-Phase Air-Cleaning Systems
  • ISO 16000: Indoor Air (parts 1-40 covering measurement methods)
  • WHO Air Quality Guidelines: Indoor air quality pollutant concentration limits

Conclusion

Indoor air quality management integrates physics-based ventilation design, contaminant source control, and continuous monitoring to maintain healthy indoor environments. The evolution from prescriptive ventilation rates to performance-based IAQ procedures enables optimized solutions balancing health protection with energy efficiency. Successful implementation requires understanding fundamental mass transfer principles, applying appropriate measurement technologies, and coordinating multiple building systems to achieve comprehensive contaminant control.

Sections

Indoor Air Pollutant Sources and Control

Comprehensive analysis of indoor air pollutant sources including building materials, occupants, equipment, and outdoor air infiltration with source control strategies.

Particulate Matter Control

Comprehensive technical analysis of particulate matter control in HVAC systems including filtration mechanisms, MERV and HEPA filter ratings, pressure drop calculations, clean air delivery rate, and ASHRAE 52.2 test methods.

Gaseous Contaminant Control Systems

Technical analysis of activated carbon adsorption, potassium permanganate oxidation, photocatalytic systems, and VOC removal strategies for HVAC applications with adsorption isotherms and breakthrough analysis.

Biosecurity Filtration Systems

Engineering analysis of HEPA filtration, UVGI inactivation kinetics, airborne pathogen control strategies, and negative pressure isolation for healthcare and biosafety applications.

CO₂ Monitoring and Demand-Controlled Ventilation

Technical principles of CO₂-based demand-controlled ventilation including sensor technology, control strategies, energy savings, and ASHRAE design requirements.

Biological Contaminant Control in HVAC Systems

Comprehensive guide to controlling airborne biological contaminants including bacteria, viruses, mold, and pollen through filtration, UVGI, and ventilation strategies per ASHRAE 62.1.

Moisture Control

Moisture control represents a critical function of HVAC systems, directly affecting occupant comfort, building envelope integrity, and indoor air quality. Proper moisture management prevents material degradation, controls biological growth, and maintains conditions within acceptable psychrometric ranges.

Fundamentals of Moisture Control

Psychrometric Relationships

Moisture exists in air as water vapor, quantified through multiple psychrometric properties:

Relative Humidity (RH): The ratio of actual water vapor pressure to saturation vapor pressure at a given temperature, expressed as a percentage. RH varies inversely with temperature when absolute moisture content remains constant.

Ventilation Effectiveness

Comprehensive technical analysis of ventilation effectiveness including zone air distribution effectiveness (Ez), air change effectiveness, age of air theory, displacement vs mixing ventilation comparison, and measurement methods per ASHRAE 62.1.

Source Control Strategies for Indoor Air Quality

Engineering hierarchy for contaminant source control including elimination, substitution, isolation, and local exhaust based on ASHRAE 62.1 and industrial hygiene principles.

Humidity Control for Indoor Air Quality

Technical guide to humidity control in HVAC systems covering psychrometrics, health effects, moisture sources, control strategies, and ASHRAE standards.

VOC Control in HVAC Systems

Physics-based strategies for volatile organic compound removal including ventilation dilution, activated carbon adsorption, photocatalytic oxidation, and source control.