HVAC Systems Encyclopedia

A comprehensive encyclopedia of heating, ventilation, and air conditioning systems

Healthcare HVAC Design for Operating Rooms & Critical Care

Healthcare HVAC Design for Operating Rooms & Critical Care

Healthcare HVAC systems protect patients, staff, and visitors from airborne pathogens while maintaining strict temperature and humidity control. This guide covers design requirements for operating rooms, isolation spaces, and critical care areas per ASHRAE Standard 170 and FGI Guidelines.

Regulatory Framework

Primary standards:

  • ASHRAE 170: Ventilation of Health Care Facilities
  • FGI Guidelines: Facility Guidelines Institute design standards
  • Joint Commission: Accreditation requirements
  • State/local codes: Often more stringent

Key metrics:

  • Air changes per hour (ACH)
  • Pressure relationships
  • Temperature and humidity ranges
  • Filtration efficiency (MERV ratings)

Operating Room (OR) HVAC Design

Ventilation Requirements

ASHRAE 170 minimums:

  • Total ACH: 20 minimum (15 outdoor air + 5 recirculated)
  • Outdoor air: 4 ACH minimum
  • Pressure: Positive (+0.01" w.g. minimum relative to corridor)
  • Temperature: 68-73°F (adjustable by surgical team)
  • Relative humidity: 20-60%

Enhanced requirements (common practice):

  • Total ACH: 20-25
  • Laminar flow ceiling: 25-35 ACH over sterile field
  • HEPA filtration: 99.97% @ 0.3 μm

Airflow Pattern

graph TD
    A[Supply Air<br/>Ceiling Diffusers<br/>Center of Room] --> B[Laminar Flow<br/>Over Sterile Field]
    B --> C[Surgical Table]
    C --> D[Low Returns<br/>Perimeter<br/>6\" Above Floor]
    D --> E[Exhaust/Recirculation]
    
    F[Positive Pressure] --> G[Prevents Contamination<br/>from Adjacent Spaces]

Design principles:

  • Supply from ceiling center (unidirectional flow over table)
  • Low return/exhaust grilles at perimeter (remove contaminated air)
  • No supply diffusers directly over doors
  • Maintain laminar flow from ceiling to 4-6 ft above floor

Filtration

Three-stage filtration (typical):

  1. Pre-filter: MERV 8 (protect downstream filters)
  2. Intermediate filter: MERV 14 minimum
  3. Final filter: HEPA (99.97% @ 0.3 μm) or MERV 17

Filter location: Final filters in ceiling plenum or terminal units

Maintenance access: Critical - plan filter change procedure

Temperature and Humidity Control

Temperature control:

  • Adjustable setpoint: 68-73°F
  • ±2°F stability
  • Individual room control (surgeon preference varies)

Reasons for cooling:

  • Surgical lights generate heat (500-2,000 Btu/hr)
  • Staff in gowns under lights
  • Equipment heat load

Humidity control:

  • Range: 20-60% RH
  • Target: 30-50% RH (reduces static, bacterial growth)
  • Dehumidification: Cooling coil + reheat
  • Humidification: Steam (most hygienic)

Worked Example 1: OR Ventilation Sizing

Given:

  • Operating room: 20 ft × 20 ft × 10 ft ceiling
  • Design: 25 total ACH, 5 outdoor air ACH
  • Temperature: 70°F
  • Humidity: 40% RH
  • Outdoor air: 95°F, 70% RH

Find: Supply airflow, outdoor air CFM, cooling load

Solution:

Room volume: $$V = 20 \times 20 \times 10 = 4,000 \text{ ft}^3$$

Total supply airflow: $$CFM_{supply} = \frac{25 \times 4,000}{60} = 1,667 \text{ CFM}$$

Outdoor air: $$CFM_{OA} = \frac{5 \times 4,000}{60} = 333 \text{ CFM}$$

Return air: $$CFM_{RA} = 1,667 - 333 = 1,334 \text{ CFM}$$

Mixed air temperature (before cooling): $$T_{MA} = \frac{333 \times 95 + 1,334 \times 70}{1,667} = 75°F$$

Sensible cooling (to 55°F supply air): $$Q_s = 1.08 \times 1,667 \times (75 - 55) = 36,006 \text{ Btu/hr}$$

Latent cooling (OA from 70% to 40% RH): From psychrometric chart:

  • OA: W = 0.0251 lb/lb
  • Supply: W = 0.0062 lb/lb at 55°F, 90% RH

$$Q_l = 4840 \times 333 \times (0.0251 - 0.0062) = 30,486 \text{ Btu/hr}$$

Total cooling load: $$Q_t = 36,006 + 30,486 = 66,492 \text{ Btu/hr} = 5.5 \text{ tons}$$

Plus internal loads (lights, equipment, people) ~10,000 Btu/hr

Total design: ~6.4 tons cooling

Answer:

  • Supply airflow: 1,667 CFM
  • Outdoor air: 333 CFM
  • Cooling load: ~6.4 tons

Airborne Infection Isolation (AII) Rooms

Negative Pressure Isolation

Purpose: Contain infectious aerosols (tuberculosis, COVID-19, measles)

ASHRAE 170 requirements:

  • Pressure: Negative (-0.01" w.g. minimum relative to corridor)
  • Total ACH: 12 minimum
  • Outdoor air: 2 ACH minimum
  • Filtration: MERV 14 on supply, HEPA on exhaust (optional but recommended)
  • Air transfer: From corridor → room → bathroom → exhaust

Design approach:

$$CFM_{exhaust} = CFM_{supply} + CFM_{offset}$$

Where $CFM_{offset}$ = 75-150 CFM (creates negative pressure)

Pressure monitoring: Required per code

  • Continuous pressure sensor
  • Visual indicator at door
  • Alarm if pressure differential fails

Protective Environment (PE) Rooms

Purpose: Protect immunocompromised patients (bone marrow transplant, chemotherapy)

ASHRAE 170 requirements:

  • Pressure: Positive (+0.01" w.g. minimum relative to anteroom)
  • Total ACH: 12 minimum
  • Filtration: HEPA on supply (99.97% @ 0.3 μm)
  • Air transfer: Room → anteroom → corridor

Anteroom (airlock):

  • Neutral or positive pressure
  • Prevents contamination during entry/exit
  • 10 ACH minimum

Control Strategies

graph TD
    A[Isolation Room Control] --> B{Room Type?}
    B -->|AII Negative| C[Monitor Pressure]
    B -->|PE Positive| D[Monitor Pressure]
    
    C --> C1[Exhaust > Supply]
    C --> C2[Modulate Exhaust Damper]
    C --> C3[Maintain -0.01 to -0.03 \"w.g.]
    
    D --> D1[Supply > Exhaust]
    D --> D2[Modulate Supply Damper]
    D --> D3[Maintain +0.01 to +0.03 \"w.g.]
    
    C3 --> E[Alarm if Pressure Lost]
    D3 --> E

Pressure control methods:

  1. Airflow offset: Fixed supply/exhaust differential

    • Simple, reliable
    • Requires good duct design
  2. Active pressure control: Modulating dampers

    • Precise pressure maintenance
    • Compensates for door openings, filter loading
  3. Dedicated exhaust fan with VFD

    • Best for critical applications
    • Highest reliability

Emergency Department (ED) Design

Waiting areas:

  • 100% outdoor air (no recirculation)
  • 12 ACH minimum
  • Exhaust to outdoors
  • Negative pressure relative to adjacent spaces

Triage/exam rooms:

  • Convertible to negative pressure isolation
  • 12 ACH, negative capability
  • Individual room exhaust

Mechanical System Configuration

Dedicated Outdoor Air System (DOAS)

Advantages for healthcare:

  • Decouples ventilation from sensible cooling
  • Precise humidity control
  • Energy recovery possible (with precautions)
  • Reduced recirculation risk

Configuration:

  • DOAS provides 100% OA to all spaces
  • Fan coil units or radiant panels for sensible cooling
  • Separate exhaust system

All-Air Systems

Single-duct VAV: Not recommended for ORs (airflow variation)

Constant volume: Preferred for critical spaces

  • Predictable airflow
  • Reliable pressure control
  • Simple troubleshooting

Dual-duct: Allows individual room temperature control

Infection Control Risk Assessment (ICRA)

Required during construction/renovation:

  1. Assess risk: Patient populations, construction type
  2. Barriers: Prevent dust migration
  3. Negative pressure: Construction areas
  4. HEPA filtration: Temporary units
  5. Monitoring: Particle counts, pressure

Practical Design Considerations

  1. Redundancy: Dual air handlers for critical areas
  2. Emergency power: All life-safety HVAC on generator
  3. Humidification: Steam preferred (hygienic, no aerosols)
  4. Drainage: Condensate must not back up into ductwork
  5. Acoustics: NC 35 maximum in patient rooms
  6. Maintenance access: Plan filter changes without room shutdown

Related Technical Guides:

References:

  • ASHRAE Standard 170: Ventilation of Health Care Facilities
  • FGI Guidelines for Design and Construction of Hospitals
  • CDC Guidelines for Environmental Infection Control in Health-Care Facilities
  • Joint Commission Environment of Care Standards