Airflow Measurement & Balancing for HVAC Engineers
Airflow Measurement & Balancing for HVAC Engineers
Testing, Adjusting, and Balancing (TAB) verifies HVAC system delivers design airflows to all spaces. Proper measurement techniques and documentation ensure comfort, energy efficiency, and code compliance.
Duct Traverse Methods
Pitot Tube Traverse
Velocity pressure measurement:
$$v = 4005 \times \sqrt{\frac{P_v}{\rho}}$$
For standard air ($\rho = 0.075$ lb/ft³):
$$v = 4005 \times \sqrt{P_v}$$
Where:
- $v$ = velocity (FPM)
- $P_v$ = velocity pressure (“w.g.)
Traverse procedure:
- Drill test holes per ASHRAE/SMACNA (equal area method)
- Measure velocity pressure at each point
- Calculate average velocity
- Multiply by duct area for CFM
Number of measurement points:
- Round duct: 20+ points (5 × 4 grid minimum)
- Rectangular duct: Based on aspect ratio (6-64 points)
Accuracy: ±5% with proper technique
Flow Hoods (Capture Hoods)
Principle: Captures all air from diffuser/grille
Advantages:
- Fast (30 seconds per measurement)
- No duct access required
- Easy for existing buildings
Disadvantages:
- ±15% accuracy (lower than pitot)
- Sensitive to mounting position
- Expensive ($2,000-$5,000)
Applications: VAV terminal verification, diffuser balancing
Balancing Procedure
Preliminary checks:
- Verify all dampers open
- Check belt tensions, sheave settings
- Measure motor amps (should be < nameplate)
Proportional balancing:
- Measure all terminal flows
- Calculate ratios to design
- Adjust furthest/highest pressure drop branch first
- Re-measure and iterate
Final measurements:
- Document actual CFM, static pressure
- Record damper positions
- Photograph balancing damper settings
Hydronic Balancing
Flow measurement methods:
- Calibrated balancing valves: Read flow directly
- Pressure drop method: $\Delta P$ across coil/valve correlates to flow
- Temperature method: $\Delta T$ and heat transfer rate infer flow
Balance tolerance: ±10% of design flow
Documentation Requirements
TAB report must include:
- Design vs. actual CFM for all terminals
- Fan motor amps, voltage, speed
- System static pressures
- Outdoor air measurements
- Damper positions
- Deficiency list
Standards:
- ASHRAE Standard 111: Practices for Measurement, Testing, Adjusting, and Balancing
- AABC National Standards
- NEBB Procedural Standards
Common TAB Issues
- Low airflow: Dirty filters, closed dampers, incorrect sheaves
- Noisy terminals: Excessive velocity (>2,000 FPM)
- Unbalanced zones: Duct leakage, undersized branch dampers
- Low system airflow: Undersized ductwork, excessive fittings
Practical Applications
- New construction: Full TAB per contract documents
- Renovation: Verify affected zones only
- Troubleshooting: Selective measurements to diagnose complaints
- Commissioning: TAB is critical component of Cx process
Related Technical Guides:
References:
- ASHRAE Standard 111: Practices for Measurement, Testing, Adjusting, and Balancing of Building HVAC Systems
- SMACNA HVAC Systems Testing, Adjusting and Balancing, 3rd Edition