HVAC Systems Encyclopedia

A comprehensive encyclopedia of heating, ventilation, and air conditioning systems

Airflow Measurement & Balancing for HVAC Engineers

Airflow Measurement & Balancing for HVAC Engineers

Testing, Adjusting, and Balancing (TAB) verifies HVAC system delivers design airflows to all spaces. Proper measurement techniques and documentation ensure comfort, energy efficiency, and code compliance.

Duct Traverse Methods

Pitot Tube Traverse

Velocity pressure measurement:

$$v = 4005 \times \sqrt{\frac{P_v}{\rho}}$$

For standard air ($\rho = 0.075$ lb/ft³):

$$v = 4005 \times \sqrt{P_v}$$

Where:

  • $v$ = velocity (FPM)
  • $P_v$ = velocity pressure (“w.g.)

Traverse procedure:

  1. Drill test holes per ASHRAE/SMACNA (equal area method)
  2. Measure velocity pressure at each point
  3. Calculate average velocity
  4. Multiply by duct area for CFM

Number of measurement points:

  • Round duct: 20+ points (5 × 4 grid minimum)
  • Rectangular duct: Based on aspect ratio (6-64 points)

Accuracy: ±5% with proper technique

Flow Hoods (Capture Hoods)

Principle: Captures all air from diffuser/grille

Advantages:

  • Fast (30 seconds per measurement)
  • No duct access required
  • Easy for existing buildings

Disadvantages:

  • ±15% accuracy (lower than pitot)
  • Sensitive to mounting position
  • Expensive ($2,000-$5,000)

Applications: VAV terminal verification, diffuser balancing

Balancing Procedure

  1. Preliminary checks:

    • Verify all dampers open
    • Check belt tensions, sheave settings
    • Measure motor amps (should be < nameplate)
  2. Proportional balancing:

    • Measure all terminal flows
    • Calculate ratios to design
    • Adjust furthest/highest pressure drop branch first
    • Re-measure and iterate
  3. Final measurements:

    • Document actual CFM, static pressure
    • Record damper positions
    • Photograph balancing damper settings

Hydronic Balancing

Flow measurement methods:

  • Calibrated balancing valves: Read flow directly
  • Pressure drop method: $\Delta P$ across coil/valve correlates to flow
  • Temperature method: $\Delta T$ and heat transfer rate infer flow

Balance tolerance: ±10% of design flow

Documentation Requirements

TAB report must include:

  • Design vs. actual CFM for all terminals
  • Fan motor amps, voltage, speed
  • System static pressures
  • Outdoor air measurements
  • Damper positions
  • Deficiency list

Standards:

  • ASHRAE Standard 111: Practices for Measurement, Testing, Adjusting, and Balancing
  • AABC National Standards
  • NEBB Procedural Standards

Common TAB Issues

  • Low airflow: Dirty filters, closed dampers, incorrect sheaves
  • Noisy terminals: Excessive velocity (>2,000 FPM)
  • Unbalanced zones: Duct leakage, undersized branch dampers
  • Low system airflow: Undersized ductwork, excessive fittings

Practical Applications

  1. New construction: Full TAB per contract documents
  2. Renovation: Verify affected zones only
  3. Troubleshooting: Selective measurements to diagnose complaints
  4. Commissioning: TAB is critical component of Cx process

Related Technical Guides:

References:

  • ASHRAE Standard 111: Practices for Measurement, Testing, Adjusting, and Balancing of Building HVAC Systems
  • SMACNA HVAC Systems Testing, Adjusting and Balancing, 3rd Edition