System Integration Tests
System integration tests verify coordinated operation across HVAC equipment, building automation controls, electrical power systems, and life safety components. Integration testing distinguishes itself from individual equipment tests by evaluating system-level responses, control interactions, and performance under dynamic building conditions per ASHRAE Guideline 0 commissioning protocols.
Integration Test Hierarchy
Integration testing follows a structured sequence from component-level verification through full building system coordination:
graph TD
A[Equipment Standalone Tests] --> B[Controller Integration]
B --> C[System-Level Integration]
C --> D[Multi-System Coordination]
D --> E[Building-Wide Integration]
B --> B1[HVAC-BAS Communication]
B --> B2[Sensor-Actuator Response]
C --> C1[Plant-Distribution]
C --> C2[AHU-Terminal Units]
C --> C3[Zone Coordination]
D --> D1[HVAC-Electrical]
D --> D2[HVAC-Fire Safety]
D --> D3[HVAC-Security]
E --> E1[Occupied Mode]
E --> E2[Unoccupied Mode]
E --> E3[Emergency Mode]
Economizer Functionality Test
Economizer integration testing verifies outdoor air damper modulation coordinates properly with mechanical cooling stages, minimum ventilation requirements, and space temperature control.
Test Sequence Protocol
sequenceDiagram
participant BAS as Building Automation
participant OAT as Outdoor Air Temp Sensor
participant Damper as OA/RA/EA Dampers
participant Cooling as Cooling Coil
participant Space as Space Temperature
BAS->>OAT: Read Temperature
OAT-->>BAS: 50°F (Economizer Available)
BAS->>Space: Read Temperature
Space-->>BAS: 74°F (Cooling Required)
BAS->>Damper: Open OA to 100%
BAS->>Damper: Close RA to Minimum
Damper-->>BAS: Position Confirmed
BAS->>Space: Monitor Temperature
Note over BAS,Cooling: If economizer insufficient
Space-->>BAS: 73°F (Still Above Setpoint)
BAS->>Cooling: Stage 1 Cooling
Cooling-->>Space: Mechanical Cooling Added
Space-->>BAS: 72°F (At Setpoint)
Economizer Test Procedure:
- Set outdoor air temperature simulation to 45°F, space to occupied cooling mode
- Command space temperature setpoint to 68°F
- Verify outdoor air damper modulates to 100% open position
- Confirm return air damper closes to minimum position (never fully closed)
- Monitor mixed air temperature equals outdoor air temperature ±2°F
- Incrementally increase outdoor air temperature: 50°F, 55°F, 60°F, 65°F, 70°F
- Record damper positions at each step
- Verify mechanical cooling stages only after economizer reaches maximum capacity
- Test high limit shutoff: increase OA temperature to 75°F, confirm economizer lockout
- Verify return to minimum outdoor air position during economizer lockout
Acceptance Criteria:
- Damper position correlates with outdoor air temperature per control sequence
- No simultaneous economizer cooling and first stage mechanical cooling
- Minimum outdoor air maintained at all operating conditions
- Mixed air temperature controlled to prevent coil freeze-up
Demand Controlled Ventilation Test
DCV integration verifies CO₂ sensors modulate outdoor air dampers while maintaining minimum code-required ventilation and coordinating with economizer operation.
Test Implementation
- Establish baseline: occupied mode with design occupancy load
- Record CO₂ levels at design conditions (typically 800-1000 ppm)
- Reduce occupancy or simulate reduced CO₂ generation
- Verify outdoor air damper modulates toward minimum position
- Confirm minimum outdoor air never violated (per ASHRAE 62.1 calculations)
- Increase occupancy or inject CO₂ to simulate high occupancy
- Verify outdoor air damper opens to increase ventilation
- Test interaction: enable economizer mode during DCV operation
- Confirm economizer overrides DCV when free cooling available
Critical Coordination:
- DCV minimum position must equal ASHRAE 62.1 minimum outdoor air requirement
- Economizer operation takes precedence over DCV damper positioning
- Multiple zones require ventilation efficiency calculations per ASHRAE 62.1-2019 Appendix A
Building Pressurization Test
Pressurization testing validates the coordinated control of supply air, return air, and relief air systems to maintain design building pressure relationships.
Pressure Control Integration
graph LR
A[Supply Air Fans] --> B[Building Pressure]
C[Return/Exhaust Fans] --> B
D[Relief Dampers] --> B
E[Outdoor Air Dampers] --> B
B --> F[Pressure Sensor]
F --> G[BAS Controller]
G --> H{Pressure High?}
H -->|Yes| I[Increase Exhaust/Relief]
H -->|No| J{Pressure Low?}
J -->|Yes| K[Decrease Exhaust/Relief]
J -->|No| L[Maintain Position]
Test Procedure:
- Verify all air systems operating in occupied mode
- Measure building pressure at representative locations (typically 5-10 points)
- Record baseline pressure differential: typically +0.02 to +0.05 in. w.c. positive
- Close exterior doors, disable relief dampers (one modification at a time)
- Monitor pressure response, verify relief damper modulates to control pressure
- Simulate high exhaust condition: enable all exhaust fans simultaneously
- Verify building pressure remains within acceptable range
- Test pressure response during economizer operation
- Confirm pressure control maintains setpoint during outdoor air modulation
Acceptance Criteria:
- Building maintains positive pressure relative to outdoors (prevents infiltration)
- Pressure remains within ±0.03 in. w.c. of setpoint during normal operation
- Pressure transients during system starts limited to ±0.05 in. w.c.
- Critical areas (stairwells, elevator shafts) maintain design pressure relationships
Smoke Control Integration Test
Smoke control testing validates integration between fire alarm systems, HVAC controls, and smoke management equipment. These tests require coordination with fire marshal authority and should follow NFPA 92 protocols.
Smoke Control Sequence
sequenceDiagram
participant FA as Fire Alarm Panel
participant BAS as Building Automation
participant HVAC as HVAC Equipment
participant Smoke as Smoke Dampers
participant Fans as Smoke Exhaust Fans
FA->>FA: Smoke Detector Activation
FA->>BAS: Fire Alarm Signal
BAS->>HVAC: Shutdown Non-Emergency HVAC
HVAC-->>BAS: Shutdown Confirmed
BAS->>Smoke: Close Smoke Dampers
Smoke-->>BAS: Damper Position Confirmed
BAS->>Fans: Start Smoke Exhaust
Fans-->>BAS: Fan Running Status
BAS->>BAS: Log All Actions with Timestamp
Test Protocol (Non-Emergency Simulation):
- Coordinate with fire alarm technician and building authority
- Place fire alarm in test mode
- Activate smoke detector in designated zone
- Verify HVAC shutdown occurs within design time (typically 30-90 seconds)
- Confirm smoke dampers close and latch
- Verify smoke exhaust fans start and achieve design pressure differential
- Test stairwell pressurization: measure pressure in stairwell relative to floor
- Confirm elevator recall and HVAC shutdown coordination
- Reset fire alarm, verify HVAC systems restart properly
Critical Coordination Points:
- HVAC shutdown must occur before smoke damper closure to prevent pressure damage
- Stairwell pressurization fans override normal HVAC controls
- Emergency power transfer must maintain smoke control system operation
Emergency Power Transfer Test
Emergency power testing validates automatic transfer switch operation and HVAC equipment restart sequencing during utility power failure.
Transfer Sequence
- Notify building occupants and utility of planned test
- Verify generator in automatic mode, fuel level adequate
- Record all HVAC equipment operating status before test
- Simulate utility failure (open normal power breaker)
- Verify automatic transfer switch transfers to emergency power
- Confirm HVAC equipment on emergency circuits restarts per load sequencing
- Monitor voltage and frequency stability during startup
- Allow 15 minutes of emergency operation
- Transfer back to utility power
- Verify all equipment returns to normal operation
Load Sequencing Verification:
Emergency HVAC loads must start sequentially to prevent generator overload. Typical sequence with 5-second intervals:
- Critical exhaust fans (fume hoods, hazardous areas)
- Smoke control equipment
- Primary chilled water pumps
- Critical air handling units
- Condenser water pumps
- Cooling tower fans
Optimal Start Integration Test
Optimal start algorithms predict the required pre-occupancy HVAC runtime to achieve comfort conditions at occupancy time while minimizing energy consumption.
Optimization Test Procedure
- Enable optimal start function in BAS
- Set occupancy time to known value (e.g., 8:00 AM)
- Allow building to drift to unoccupied setpoints overnight
- Monitor actual start time chosen by optimal start algorithm
- Record space temperatures at occupancy time
- Evaluate accuracy: spaces should reach setpoint within 15 minutes of occupancy
- Repeat test over multiple days with varying outdoor conditions
- Verify algorithm adjusts start time based on learned building thermal response
Integration Verification:
- Optimal start overrides normal scheduled start time
- All associated equipment (boilers, chillers, pumps) starts with AHUs
- Setpoint recovery occurs without excessive equipment cycling
- Algorithm adapts to seasonal changes and building use patterns
Night Setback Operation Test
Night setback testing validates unoccupied mode temperature drift, equipment shutdown sequencing, and energy reduction compared to occupied operation.
Test Requirements:
- Configure unoccupied setpoints (typically 55°F heating, 85°F cooling)
- Verify schedule transitions to unoccupied mode
- Confirm space temperatures drift toward setback setpoints
- Monitor equipment status: non-critical equipment should shut down
- Verify minimum equipment operation maintains setback limits
- Measure energy consumption during unoccupied period
- Compare to occupied energy consumption (expect 40-60% reduction)
Integration testing represents the convergence of individual equipment capabilities into coordinated building systems. Systematic verification of economizer sequences, demand control ventilation, building pressurization, smoke control, emergency power, and optimization algorithms ensures HVAC installations deliver design performance across all operating modes while maintaining safety and efficiency objectives throughout the building lifecycle.