Minimal Conditioning Strategies for Unoccupied Spaces

Overview

Minimal conditioning represents the most aggressive energy conservation strategy during unoccupied periods, maintaining only the environmental conditions necessary to protect building systems, prevent equipment damage, and avoid moisture-related issues. This approach maximizes energy savings by allowing space temperatures to drift within wide deadbands while cycling equipment only when protection limits are reached.

Minimal Conditioning Operating Principles

Minimal conditioning mode operates on the principle that unoccupied spaces can tolerate extreme temperature excursions without compromising building integrity. The strategy focuses on three critical protection objectives:

  1. Equipment Protection: Preventing damage to temperature-sensitive building systems
  2. Envelope Protection: Avoiding condensation, freezing, or structural stress
  3. Recovery Capability: Maintaining sufficient thermal stability for reasonable morning warmup

The wide temperature deadband between heating and cooling setpoints eliminates unnecessary equipment cycling and allows natural thermal drift based on outdoor conditions and internal thermal mass.

Setpoint Strategy and Temperature Limits

Standard Minimal Conditioning Setpoints

ConditionHeating SetpointCooling SetpointDeadbandApplication
Winter Dominant55°F (13°C)90°F (32°C)35°FCold climates, well-insulated buildings
Moderate Climate58°F (14°C)88°F (31°C)30°FMixed climates, standard construction
Humidity Concern60°F (16°C)85°F (29°C)25°FHigh humidity regions, moisture-sensitive equipment
Equipment Intensive62°F (17°C)82°F (28°C)20°FServer rooms, laboratories (off-hours)

Extreme Setback Temperature Limits

Heating Protection Threshold: The minimum heating setpoint prevents:

  • Pipe freezing in perimeter zones
  • Condensation on cold surfaces
  • Equipment damage from low temperatures
  • Excessive morning recovery time

Cooling Protection Threshold: The maximum cooling setpoint prevents:

  • Electronic equipment overheating
  • High humidity and condensation risk
  • Material degradation from excessive heat
  • Occupant discomfort upon building re-entry

Equipment Cycling Strategy

Minimal Runtime Control Logic

graph TD
    A[Unoccupied Mode Active] --> B{Space Temperature}
    B -->|T < 55°F| C[Enable Heating]
    B -->|55°F ≤ T ≤ 90°F| D[All Equipment Off]
    B -->|T > 90°F| E[Enable Cooling]
    C --> F{T ≥ 58°F}
    F -->|Yes| D
    F -->|No| C
    E --> G{T ≤ 87°F}
    G -->|Yes| D
    G -->|No| E
    D --> H[Monitor Only]
    H --> B

Staging and Differential Control

The control system implements hysteresis to prevent short-cycling:

Heating Cycle:

  • Start heating at: 55°F
  • Stop heating at: 58°F (3°F differential)
  • Minimum runtime: 10 minutes

Cooling Cycle:

  • Start cooling at: 90°F
  • Stop cooling at: 87°F (3°F differential)
  • Minimum runtime: 15 minutes

This differential ensures equipment runs for meaningful periods when activated, reducing wear from frequent starts while maintaining protection limits.

Energy Savings Calculations

Heating Energy Reduction

The heating energy savings from minimal conditioning compared to occupied setpoints can be estimated using:

$$Q_{saved} = UA \cdot \Delta T_{sb} \cdot t_{unocc}$$

Where:

  • $Q_{saved}$ = energy saved (Btu or kWh)
  • $U$ = overall heat transfer coefficient (Btu/hr·ft²·°F)
  • $A$ = building envelope area (ft²)
  • $\Delta T_{sb}$ = setback temperature difference (°F)
  • $t_{unocc}$ = unoccupied duration (hours)

Percentage Energy Savings

For heating season, the fractional savings can be approximated as:

$$\text{Savings} = \left(1 - \frac{T_{indoor,sb} - T_{outdoor}}{T_{indoor,occ} - T_{outdoor}}\right) \times \frac{t_{unocc}}{t_{total}}$$

Where:

  • $T_{indoor,sb}$ = setback heating setpoint (55°F)
  • $T_{indoor,occ}$ = occupied heating setpoint (70°F)
  • $T_{outdoor}$ = average outdoor temperature during unoccupied period

Example Calculation:

  • Occupied setpoint: 70°F
  • Setback setpoint: 55°F
  • Average outdoor temperature: 30°F
  • Unoccupied fraction: 60% of week

$$\text{Savings} = \left(1 - \frac{55 - 30}{70 - 30}\right) \times 0.60 = \left(1 - \frac{25}{40}\right) \times 0.60 = 0.375 \times 0.60 = 22.5%$$

This example demonstrates 22.5% heating energy reduction from minimal conditioning setback.

Moisture and Condensation Control

Humidity Monitoring Requirements

Minimal conditioning must include humidity monitoring to prevent:

  • Surface condensation on cold surfaces
  • Mold growth from sustained high humidity
  • Material damage in humidity-sensitive spaces

Critical Humidity Thresholds:

  • Maximum relative humidity: 65% RH
  • Dew point alarm: 60°F
  • Condensation risk temperature: 55°F surface temperature

Condensation Prevention Logic

flowchart LR
    A[Monitor RH and Temperature] --> B{RH > 60%}
    B -->|Yes| C{Cooling Available?}
    B -->|No| D[Normal Minimal Mode]
    C -->|Yes| E[Enable Dehumidification]
    C -->|No| F[Enable Ventilation]
    E --> G{RH < 55%}
    F --> G
    G -->|Yes| D
    G -->|No| E

When relative humidity exceeds 60%, the system must provide dehumidification even if space temperature remains within the minimal conditioning deadband. This override protects building materials and equipment from moisture damage.

ASHRAE 90.1 Compliance

Energy Standard Requirements

ASHRAE 90.1 Section 6.4.3.3 establishes requirements for automatic setback controls:

Mandatory Provisions:

  • Automatic temperature reset during unoccupied periods
  • Setback to 55°F heating or setup to 90°F cooling
  • Override capability for temporary occupancy
  • Automatic return to occupied setpoints before scheduled occupancy

Zone-Level Controls: Each zone must have independent setback capability unless justified by system design limitations.

Exception Conditions

Minimal conditioning may not be appropriate for:

  • Spaces with continuous processes requiring stable temperatures
  • Areas with temperature-sensitive equipment or materials
  • Spaces requiring positive pressurization for contamination control
  • Zones where recovery time would exceed pre-occupancy period

Implementation Considerations

Morning Recovery Preparation

The building management system should initiate recovery from minimal conditioning mode based on:

$$t_{recovery} = \frac{C \cdot m \cdot \Delta T}{Q_{capacity}}$$

Where:

  • $t_{recovery}$ = required recovery time (hours)
  • $C$ = specific heat of air (0.24 Btu/lb·°F)
  • $m$ = air mass or effective building thermal mass
  • $\Delta T$ = temperature difference to overcome
  • $Q_{capacity}$ = available heating/cooling capacity

Typical Recovery Rates:

  • Lightweight construction: 2-4°F per hour
  • Medium thermal mass: 1.5-3°F per hour
  • Heavy thermal mass: 1-2°F per hour

Equipment Protection Features

Compressor Protection: When enabling cooling from minimal mode, implement:

  • Crankcase heater verification before start
  • Minimum off-time of 5 minutes between cycles
  • Staged startup for multiple compressors

Boiler/Furnace Protection: When enabling heating from minimal mode:

  • Purge cycle completion before ignition
  • Low temperature limit verification
  • Gradual capacity increase to prevent thermal shock

Performance Monitoring

Key Performance Indicators

Track these metrics to verify minimal conditioning effectiveness:

MetricTargetAction if Exceeded
Average Unoccupied Runtime< 15% of unoccupied hoursReview setpoint limits
Temperature Excursions< 5% of readings outside limitsCheck sensor calibration
Morning Recovery Failures0 per monthAdjust recovery start time
Humidity Excursions< 2% of readings > 65% RHEnable dehumidification override

Energy Baseline Comparison

Establish baseline energy consumption and compare monthly:

  • Total heating energy during unoccupied hours
  • Total cooling energy during unoccupied hours
  • Equipment runtime hours
  • Peak demand during recovery periods

Minimal conditioning should reduce unoccupied HVAC energy by 20-35% compared to standard setback strategies in most climates.

Conclusion

Minimal conditioning provides maximum energy savings during unoccupied periods while maintaining essential building protection. Success requires proper setpoint selection, robust humidity monitoring, intelligent equipment cycling logic, and adequate morning recovery capacity. When implemented according to ASHRAE 90.1 requirements and building-specific constraints, minimal conditioning delivers substantial operational cost reduction without compromising building integrity or occupant comfort upon return.