Process Exhaust for Textile Dyeing & Finishing

Process exhaust systems in textile dyeing and finishing facilities control chemical vapors, dye aerosols, heat, and humidity from processing equipment. Proper exhaust design protects worker health, maintains product quality, and ensures regulatory compliance with OSHA PELs and ACGIH TLVs.

Exhaust System Requirements

Dye Bath Exhaust

Dye baths generate steam, chemical vapors, and aerosols during high-temperature processing. Exhaust hoods must capture emissions at the source before dispersal into the workspace.

Capture velocity calculations:

$$V_c = \frac{Q}{A} = \frac{Q}{10 \times X^2 + A_{hood}}$$

where:

  • $V_c$ = capture velocity (fpm)
  • $Q$ = exhaust flow rate (cfm)
  • $X$ = distance from hood face to emission source (ft)
  • $A_{hood}$ = hood face area (ft²)

Required capture velocities by contaminant:

Contaminant TypeCapture VelocityACGIH Classification
Steam and moisture50-100 fpmLow toxicity vapor
Dye powder dispersion100-200 fpmModerate toxicity particulate
Solvent vapors200-500 fpmHigh toxicity vapor
Acid/alkali mists100-200 fpmCorrosive aerosol

Chemical Vapor Control

Finishing chemicals including formaldehyde resins, softeners, and flame retardants require dedicated exhaust during application and curing.

Vapor generation rate:

$$G = \frac{M \times VP \times MW}{R \times T}$$

where:

  • $G$ = generation rate (lb/hr)
  • $M$ = chemical application rate (gal/hr)
  • $VP$ = vapor pressure (mmHg)
  • $MW$ = molecular weight (lb/lbmol)
  • $R$ = gas constant (10.73 psia·ft³/lbmol·°R)
  • $T$ = absolute temperature (°R)

Required exhaust rates:

$$Q_{exhaust} = \frac{G \times SF}{C_{max} \times \rho_{air}}$$

where:

  • $Q_{exhaust}$ = exhaust flow rate (cfm)
  • $SF$ = safety factor (typically 2-5)
  • $C_{max}$ = maximum allowable concentration (ppm or mg/m³)
  • $\rho_{air}$ = air density (0.075 lb/ft³ at standard conditions)

Local Exhaust Hood Design

Hood Types and Applications

graph TD
    A[Process Exhaust Sources] --> B[Dye Baths]
    A --> C[Finishing Ranges]
    A --> D[Chemical Mixing]
    A --> E[Drying Ovens]

    B --> F[Canopy Hoods]
    C --> G[Slot Hoods]
    D --> H[Enclosed Hoods]
    E --> I[Direct Connection]

    F --> J[Exhaust Fan]
    G --> J
    H --> J
    I --> J

    J --> K[Air Pollution Control]
    K --> L[Stack Discharge]

    style B fill:#e1f5ff
    style C fill:#e1f5ff
    style D fill:#e1f5ff
    style E fill:#e1f5ff
    style K fill:#fff4e1

Canopy Hood Sizing

For open dye baths and processing tanks:

$$Q = V_c \times P \times (H + D)$$

where:

  • $Q$ = exhaust flow rate (cfm)
  • $V_c$ = capture velocity (50-100 fpm for steam)
  • $P$ = tank perimeter (ft)
  • $H$ = hood height above source (ft)
  • $D$ = tank depth (ft)

Canopy hood overhang requirements:

Tank DimensionMinimum OverhangRecommended Overhang
< 3 ft6 inches12 inches
3-6 ft12 inches18 inches
> 6 ft18 inches24 inches

Slot Hood Design

For finishing ranges and continuous processes:

$$Q = 50 \times V_{slot} \times L \times W_{slot}$$

where:

  • $V_{slot}$ = slot velocity (2000-3000 fpm)
  • $L$ = slot length (ft)
  • $W_{slot}$ = slot width (typically 1.5-3 inches)

Slot spacing and plenum design:

$$S = \sqrt{\frac{2 \times V_{slot}^2}{\rho \times \Delta P}}$$

where:

  • $S$ = slot spacing (ft)
  • $\Delta P$ = static pressure across slots (in. w.g.)
  • $\rho$ = air density (lb/ft³)

Exhaust System Components

flowchart LR
    A[Emission Source] --> B[Capture Hood]
    B --> C[Ductwork]
    C --> D[Air Cleaner]
    D --> E[Exhaust Fan]
    E --> F[Stack]

    G[Makeup Air] -.-> A

    H[Dampers] --> C
    I[Access Doors] --> D
    J[Monitoring] --> E

    style A fill:#ffe1e1
    style D fill:#e1ffe1
    style F fill:#e1e1ff

    subgraph "Emission Control"
    D
    end

    subgraph "Air Moving"
    E
    end

Duct Velocity Requirements

Minimum transport velocities prevent settling and maintain capture:

Material TypeMinimum VelocityDesign Velocity
Vapors and gases1000 fpm1500-2000 fpm
Fine dusts (dye powder)2000 fpm2500-3000 fpm
Heavy dusts3500 fpm4000-4500 fpm
Sticky aerosols2500 fpm3000-3500 fpm

Static Pressure Calculations

Total system pressure loss:

$$SP_{total} = SP_{hood} + SP_{duct} + SP_{fittings} + SP_{cleaner} + SP_{discharge}$$

Hood entry loss:

$$SP_{hood} = \frac{V_d^2 \times C_e}{4005}$$

where:

  • $SP_{hood}$ = hood static pressure (in. w.g.)
  • $V_d$ = duct velocity (fpm)
  • $C_e$ = entry loss coefficient (0.25-1.78 depending on hood type)

Duct friction loss:

$$SP_{duct} = \frac{f \times L \times V_d^2}{4005 \times D}$$

where:

  • $f$ = friction factor (0.02-0.04 for galvanized steel)
  • $L$ = duct length (ft)
  • $D$ = duct diameter (ft)

Emission Control Equipment

Scrubber Selection

Chemical vapors and acid mists require wet scrubbing:

Scrubber efficiency:

$$\eta = 1 - e^{-\frac{K \times L \times A}{Q}}$$

where:

  • $\eta$ = collection efficiency
  • $K$ = mass transfer coefficient
  • $L$ = scrubber height (ft)
  • $A$ = cross-sectional area (ft²)

Liquid-to-gas ratio:

ContaminantL/G RatioTypical Range
Acid vapors5-20 gal/1000 cfm10-15 recommended
Alkaline mists3-10 gal/1000 cfm5-8 recommended
Solvent vapors10-30 gal/1000 cfm15-20 recommended
Dye aerosols8-15 gal/1000 cfm10-12 recommended

Carbon Adsorption

For volatile organic compounds (VOCs) from finishing chemicals:

Bed depth calculation:

$$D = \frac{Q \times C \times t}{A \times \rho_{carbon} \times W_c}$$

where:

  • $D$ = bed depth (ft)
  • $C$ = inlet concentration (lb/ft³)
  • $t$ = service time (hours)
  • $\rho_{carbon}$ = carbon density (25-30 lb/ft³)
  • $W_c$ = carbon capacity (typically 0.2-0.4 lb VOC/lb carbon)

Makeup Air Requirements

Exhaust systems require balanced makeup air to prevent building depressurization:

$$Q_{makeup} = Q_{exhaust} - Q_{infiltration}$$

Maintain building pressure at -0.02 to -0.05 in. w.g. relative to outdoors to contain odors while ensuring adequate makeup air delivery.

Makeup air temperature:

$$T_{supply} = T_{room} - \frac{Q_{exhaust} \times (T_{room} - T_{outdoor})}{Q_{makeup} \times \eta_{heat}}$$

where $\eta_{heat}$ accounts for heat recovery efficiency if applicable.

Design Standards and References

ACGIH Industrial Ventilation Manual: Provides hood design criteria, capture velocities, and duct sizing methodology for chemical processes.

ASHRAE Industrial Ventilation Applications: Details specific requirements for textile processing exhaust including heat and moisture loads.

NFPA 91: Standard for exhaust systems handling flammable vapors common in solvent-based finishing processes.

Proper process exhaust design requires detailed analysis of emission sources, chemical properties, production rates, and regulatory requirements. System performance verification through hood face velocity measurements and worker exposure monitoring ensures adequate protection.