HVAC Systems Encyclopedia

A comprehensive encyclopedia of heating, ventilation, and air conditioning systems

Stairwell Pressurization Systems

Stairwell pressurization systems maintain positive pressure within egress stairwells to prevent smoke infiltration during fire emergencies in high-rise buildings. These systems create a pressure barrier by injecting outdoor air into the stairwell, establishing a higher pressure than adjacent building spaces. The fundamental challenge involves maintaining sufficient pressure differential to prevent smoke entry while ensuring occupants can open stairwell doors during evacuation.

Pressure Differential Requirements

NFPA 92 and IBC establish minimum pressure differentials based on door status and building conditions. The pressure difference across a barrier prevents smoke migration through the relationship:

$$Q = C \cdot A \cdot \sqrt{2 \Delta P / \rho}$$

where $Q$ represents volumetric airflow through openings (cfm), $C$ is the flow coefficient (typically 0.65 for door gaps), $A$ is the leakage area (ft²), $\Delta P$ is the pressure differential (in. H₂O), and $\rho$ is air density (lb/ft³).

Design Pressure Targets

ConditionMinimum PressureMaximum PressureApplication
Doors closed0.10 in. H₂O0.35 in. H₂OAll doors closed scenario
Single door open0.05 in. H₂ON/AOne door open on fire floor
Multiple doors openMaintain flowN/AEvacuation scenario
Door opening forceN/A30 lbfMaximum acceptable force

The minimum 0.10 in. H₂O differential with all doors closed provides adequate smoke barrier performance. The maximum 0.35 in. H₂O limit prevents excessive door opening forces. During single door opening events, the system must maintain at least 0.05 in. H₂O across closed doors on other floors to prevent smoke spread.

Door Opening Force Calculations

Door opening force directly correlates to pressure differential through door geometry. The force required to overcome pressure differential acting on a door area follows:

$$F_{pressure} = \Delta P \cdot A_{door} \cdot \frac{W}{2}$$

where $F_{pressure}$ is the force component from pressure (lbf), $A_{door}$ is door area (ft²), and $W$ is door width (ft). The factor $W/2$ accounts for the moment arm from the door hinge to the center of pressure.

For a standard 3 ft × 7 ft door, the relationship becomes:

$$F_{total} = \Delta P \times 21 \text{ ft}^2 \times 1.5 \text{ ft} + F_{closure} + F_{friction}$$

where $F_{closure}$ represents door closer force and $F_{friction}$ accounts for latch and hinge resistance. IBC limits total opening force to 30 lbf for accessible egress, which constrains maximum allowable pressure differential.

Force Limitation Analysis

graph TD
    A[Pressure Differential] --> B[Door Area Force]
    A --> C[System Response]
    B --> D{Opening Force Check}
    D -->|> 30 lbf| E[Pressure Relief Required]
    D -->|≤ 30 lbf| F[Acceptable Operation]
    E --> G[Activate Relief Dampers]
    E --> H[Reduce Supply Flow]
    C --> G
    C --> H

When pressure differential exceeds thresholds that produce opening forces above 30 lbf, the system must immediately reduce pressure through relief mechanisms or supply flow modulation.

Multiple Injection Point Strategy

Tall stairwells require multiple supply air injection points to overcome stack effect and maintain uniform pressure distribution. Single injection point systems create pressure gradients from stack effect:

$$\Delta P_{stack} = \rho \cdot g \cdot h \cdot \left(\frac{1}{T_{outside}} - \frac{1}{T_{stairwell}}\right)$$

where $g$ is gravitational acceleration (32.2 ft/s²), $h$ is vertical height (ft), and temperatures are in absolute scale (°R).

Injection Point Spacing

For a 500 ft tall stairwell with 40°F outdoor temperature and 70°F stairwell temperature:

$$\Delta P_{stack} = 0.075 \times 32.2 \times 500 \times \left(\frac{1}{500} - \frac{1}{530}\right) = 0.15 \text{ in. H}_2\text{O}$$

This stack effect creates bottom-to-top pressure gradient requiring multiple injection points. Recommended spacing:

Building HeightMaximum Injection SpacingTypical Injection Points
< 75 ftSingle point at bottom1 location
75-150 ft75 ft vertical2-3 locations
150-300 ft50-75 ft vertical4-6 locations
> 300 ft40-60 ft vertical8+ locations

Each injection point delivers proportional airflow based on zone volume and leakage area. Upper injection points compensate for stack effect pressure loss, maintaining uniform differential across building height.

Modulating Pressure Relief Systems

Pressure relief dampers prevent over-pressurization during variable door conditions. The system responds to door openings through barometric or mechanical relief:

Relief Damper Control Sequence

sequenceDiagram
    participant PS as Pressure Sensor
    participant C as Controller
    participant RD as Relief Damper
    participant SF as Supply Fan

    PS->>C: Pressure > 0.35 in. H₂O
    C->>RD: Modulate open 25%
    PS->>C: Pressure still high
    C->>RD: Modulate open 50%
    PS->>C: Pressure acceptable
    C->>RD: Hold position
    Note over PS,SF: Door opens on fire floor
    PS->>C: Pressure drops to 0.08 in. H₂O
    C->>RD: Modulate close
    C->>SF: Increase speed 10%

Relief damper sizing requires sufficient capacity to discharge excess flow during minimum door opening scenarios:

$$Q_{relief} = Q_{supply} - Q_{leakage} - Q_{door}$$

where $Q_{relief}$ is relief damper capacity (cfm), $Q_{supply}$ is total supply flow, $Q_{leakage}$ is normal stairwell leakage, and $Q_{door}$ represents flow through open doors.

Barometric vs. Mechanical Relief

Relief TypeResponse TimeAccuracyComplexityApplication
Barometric dampers1-2 seconds±0.05 in. H₂OLowBuildings < 200 ft
Motorized dampers5-15 seconds±0.02 in. H₂OMediumBuildings 200-400 ft
VFD supply fan3-8 seconds±0.01 in. H₂OHighBuildings > 400 ft

Barometric relief dampers open mechanically at preset pressure, providing rapid response without controls. Motorized dampers offer precise modulation through building automation integration. Variable frequency drive supply fan control provides finest pressure regulation by adjusting airflow at the source rather than relieving excess pressure.

System Commissioning Verification

Acceptance testing verifies pressure differential maintenance across door operation scenarios:

  1. All doors closed test: Verify 0.10-0.35 in. H₂O across all floors
  2. Single door open test: Open one door per floor sequentially, maintain ≥0.05 in. H₂O on other floors
  3. Door force test: Measure opening force at maximum pressure, confirm ≤30 lbf
  4. Relief damper response: Verify modulation within specified time and accuracy
  5. Stack effect compensation: Test system during maximum indoor-outdoor temperature difference

Temperature-induced stack effect creates the most challenging operational condition, requiring seasonal commissioning verification to confirm year-round performance across extreme weather conditions.

Sections

Smoke Control Through Stairwell Pressurization

Comprehensive analysis of stairwell pressurization for smoke control including design pressure differentials, open door scenarios, injection strategies, and NFPA 92 acceptance testing protocols.

Fire Service Access Stairwell Pressurization

Enhanced pressurization requirements for fire service access stairwells including door force limits, vestibule design, emergency power, and code compliance per IBC and NFPA.

Makeup Air Requirements for Stairwell Pressurization

Engineering calculation methods for determining makeup air volumes in high-rise stairwell pressurization systems, including leakage compensation and door-opening demand.