Smoke Detection & System Activation
Detection System Integration
Smoke control activation depends on rapid, reliable detection integrated with fire alarm and building management systems. Detection devices must meet NFPA 72 requirements while providing zone-specific information to enable appropriate smoke control responses per NFPA 92.
Detection Technologies
Spot-Type Smoke Detectors:
- Photoelectric or ionization sensors
- Spacing: 30 ft (9 m) typical per NFPA 72
- Response time: 20-60 seconds for 4% obscuration/ft
- Application: Standard ceiling heights up to 30 ft (9 m)
Projected Beam Detectors:
- Infrared beam interruption detection
- Spacing: Up to 100 ft (30 m) beam length
- Response time: 10-30 seconds for 1.5-3% obscuration/ft
- Application: High ceilings, atriums, warehouses
- Mounting: Walls or columns with clear line-of-sight
Aspirating Smoke Detection (ASD):
- Continuous air sampling through pipe network
- Sensitivity: 0.005-2% obscuration/ft
- Response time: 15-120 seconds depending on transport time
- Application: Critical areas requiring earliest warning
- Coverage: 2,000-4,000 sq ft per sampling point
The air transport time in aspirating systems affects total response:
$$ t_{total} = t_{detect} + t_{transport} = t_{detect} + \frac{L \cdot A}{Q} $$
Where:
- $t_{total}$ = total response time (s)
- $t_{detect}$ = detector element response time (s)
- $t_{transport}$ = air transport time through sampling pipe (s)
- $L$ = pipe length from sampling point to detector (ft)
- $A$ = pipe cross-sectional area (sq ft)
- $Q$ = sampling airflow rate (cfm)
Activation Sequence Design
Multi-Stage Activation Logic
Smoke control systems employ staged activation to prevent false alarms while ensuring rapid response:
| Stage | Trigger | Action | Timing |
|---|---|---|---|
| Pre-Alarm | Single detector 50% threshold | Alert monitoring | Immediate |
| Alarm | Single detector 100% or two detectors 50% | Initiate smoke control sequence | <10 seconds |
| Full Activation | Confirmed fire or manual activation | All smoke control modes active | <30 seconds |
| Post-Suppression | After sprinkler flow or manual | Enhanced exhaust mode | Sustained |
Sequence Flow Diagram
graph TD
A[Smoke Detected] --> B{Single or Multiple?}
B -->|Single Detector| C[Pre-Alarm State]
B -->|Multiple Detectors| D[Alarm Condition]
C --> E{Threshold Exceeded?}
E -->|Yes| D
E -->|No| F[Reset]
D --> G[Activate Smoke Control]
G --> H[HVAC Shutdown Selected Zones]
H --> I[Pressurization Systems Start]
I --> J[Exhaust Fans Energize]
J --> K[Dampers Position]
K --> L[Verify Differential Pressure]
L --> M{Pressure Target Met?}
M -->|No| N[Alarm System Failure]
M -->|Yes| O[Maintain Mode]
N --> P[Alert Fire Command Center]
O --> Q[Monitor Continuously]
Activation Timing Requirements
The total system activation time from detection to full operational mode must meet NFPA 92 performance objectives:
$$ t_{activation} = t_{detect} + t_{processing} + t_{equipment} $$
Where:
- $t_{detect}$ = smoke detection response time (typically 20-60 s)
- $t_{processing}$ = control logic processing and signal transmission (typically 3-10 s)
- $t_{equipment}$ = mechanical equipment startup and positioning (typically 15-45 s)
Target total activation time: 60-90 seconds maximum for full operational capacity.
Zoned Activation Strategy
sequenceDiagram
participant Det as Smoke Detector Zone 3
participant FACP as Fire Alarm Control Panel
participant SC as Smoke Control Panel
participant HVAC as HVAC Equipment Zone 3
participant ADJ as Adjacent Zones 2,4
Det->>FACP: Alarm Signal
FACP->>SC: Zone 3 Activation Command
SC->>HVAC: Shutdown Zone 3 Supply/Return
SC->>HVAC: Start Zone 3 Exhaust
SC->>ADJ: Pressurize Adjacent Zones
HVAC-->>SC: Status Confirmation
SC->>FACP: Operational Status
FACP->>Det: System Active Acknowledge
Fire Alarm System Integration
Interface Requirements
The smoke control system must receive discrete signals from the fire alarm control panel (FACP) per NFPA 72:
- Zone Identification: Unique signal for each smoke zone
- Detector Type: Differentiation between smoke, heat, and manual stations
- Signal Reliability: Supervised circuits with end-of-line resistors
- Power Supply: Secondary power source for 24-hour operation minimum
- Two-Way Communication: Status feedback from smoke control to FACP
Control Panel Architecture
| Component | Function | Redundancy |
|---|---|---|
| Primary Controller | Execute smoke control logic | Hot standby backup |
| Zone Input Modules | Receive FACP signals | Dual input circuits |
| Equipment Output Modules | Control fans, dampers | Fail-safe positioning |
| Differential Pressure Sensors | Monitor performance | Multiple per zone |
| Annunciation Panel | Display system status | Redundant displays |
Fail-Safe Design Principles
Failure Mode Analysis
All components must default to safe positions upon power loss or control failure:
Dampers:
- Smoke exhaust dampers: Fail OPEN
- Supply air dampers to fire zone: Fail CLOSED
- Pressurization supply dampers: Fail OPEN (if serving refuge areas)
- Return air dampers from fire zone: Fail CLOSED
Fans:
- Exhaust fans: Fail ON (with emergency power)
- Supply fans to fire zone: Fail OFF
- Pressurization fans: Fail ON (with emergency power)
Control Power:
- UPS backup: Minimum 4 hours for control circuits
- Emergency generator: Power to life safety equipment within 10 seconds
- Battery backup: Individual damper actuators maintain position for 4 hours
System Supervision and Monitoring
Continuous monitoring per NFPA 72 Chapter 10:
- Circuit integrity supervision (opens, shorts, ground faults)
- Equipment status verification (on/off, position feedback)
- Airflow and pressure monitoring (differential pressure across barriers)
- Power supply monitoring (primary, secondary, battery voltage)
- Communication path supervision (network integrity)
Trouble conditions must annunciate at the fire command center and transmit to the monitoring station within 200 seconds per NFPA 72.
Manual Activation and Override
Manual Activation:
- Manual pull stations trigger full smoke control activation
- Firefighter smoke control stations at fire command center
- Individual zone activation capability for testing and override
Manual Override Limitations:
- Only authorized personnel can override automatic operation
- Override actions logged with timestamp and user identification
- Automatic reversion to fire alarm control if new alarm received
Testing and Commissioning
Activation sequence verification requires:
- Detector Response Testing: Verify each detector initiates correct zone activation
- Sequence Timing: Measure total activation time from detection to full operation
- Equipment Response: Confirm all fans, dampers respond within specified times
- Pressure Verification: Measure differential pressures meet design targets
- Fail-Safe Testing: Simulate power loss and verify safe positioning
- Interface Testing: Confirm proper communication between fire alarm and smoke control
Documentation requirements per NFPA 92:
- Activation sequence diagrams
- Equipment response times
- Measured differential pressures
- Detector locations and coverage
- Training records for facility personnel
Performance Verification
The installed detection and activation system must demonstrate:
- Smoke detection within 60 seconds in test smoke conditions
- Full system activation within 90 seconds of detection
- Target differential pressures achieved within 30 seconds of fan startup
- Maintained pressurization for minimum 20-minute duration
- Proper fail-safe operation under all simulated failure modes
Regular annual testing maintains system reliability and occupant safety in compliance with NFPA 92 Section 8.5.