Atrium Exhaust Rate Calculations for Smoke Control

Fundamental Principles

Atrium exhaust rate calculations determine the volumetric flow rate required to maintain a smoke layer interface at a specified height above the fire source. The design basis follows NFPA 92 methodologies, which relate fire heat release rate to plume mass flow and required exhaust capacity.

The objective is to maintain tenable conditions below the smoke layer for occupant egress while preventing smoke descent to occupied levels.

Fire Size and Heat Release Rate

Design Fire Basis

The design fire represents the assumed steady-state heat release rate (HRR) used for exhaust calculations. NFPA 92 provides guidance for selecting design fires based on occupancy and combustible loading.

Common Design Fire Categories:

Occupancy TypeDesign HRRBasis
Retail/Mercantile5,000 kWMultiple burning items
Office2,500-5,000 kWWorkstation fire
Assembly2,500 kWSeating/furnishings
High-Hazard Storage10,000+ kWCommodity storage

Heat Release Rate Assumptions

The heat release rate determines plume characteristics and mass flow. Selection criteria include:

  • Expected fuel load and configuration
  • Fire growth rate (t-squared fire development)
  • Sprinkler activation effects (if applicable)
  • Code-mandated minimum values

For unsprinklered spaces, use steady-state HRR values. For sprinklered spaces, HRR may be reduced to account for fire suppression, though NFPA 92 recommends conservative approaches.

Plume Mass Flow Rate Calculations

Axisymmetric Plume Equation

For fires located away from walls with unlimited air entrainment, the axisymmetric plume equation applies:

$$\dot{m}_p = 0.071 , Q_c^{1/3} , z^{5/3} + 0.0018 , Q_c$$

Where:

  • $\dot{m}_p$ = plume mass flow rate (kg/s)
  • $Q_c$ = convective heat release rate (kW)
  • $z$ = height above fire source to smoke layer interface (m)

The convective heat release rate is:

$$Q_c = \chi_c , Q$$

Where:

  • $Q$ = total heat release rate (kW)
  • $\chi_c$ = convective fraction (typically 0.60-0.70)

Balcony Spill Plume Equation

For fires beneath balconies or adjacent to walls, use the balcony spill plume equation:

$$\dot{m}_p = 0.36 , (z - z_b)^{1/3} , W , Q_c^{1/3}$$

Where:

  • $z_b$ = height of balcony above fire (m)
  • $W$ = effective width of balcony opening (m)

Wall Plume Equation

For fires against walls with restricted air entrainment:

$$\dot{m}_p = 0.058 , Q_c^{1/3} , z^{5/3} + 0.0018 , Q_c$$

The coefficient reduces from 0.071 to 0.058 due to restricted entrainment on one side.

Volumetric Exhaust Rate Calculation

Basic Exhaust Rate Formula

Convert plume mass flow rate to volumetric exhaust rate:

$$V_e = \frac{\dot{m}_p}{\rho_s}$$

Where:

  • $V_e$ = volumetric exhaust rate (m³/s)
  • $\rho_s$ = smoke layer density (kg/m³)

For typical conditions, smoke layer density:

$$\rho_s = \rho_{\infty} , \frac{T_{\infty}}{T_s}$$

Where:

  • $\rho_{\infty}$ = ambient air density (1.20 kg/m³ at 20°C)
  • $T_{\infty}$ = ambient temperature (K)
  • $T_s$ = smoke layer temperature (K)

Smoke Layer Temperature Estimation

The average smoke layer temperature rise above ambient:

$$\Delta T = \frac{Q_c}{\dot{m}_p , c_p}$$

Where:

  • $c_p$ = specific heat of air (1.01 kJ/kg·K)

Exhaust Capacity and CFM Calculations

Conversion to CFM

For US practice, convert m³/s to CFM:

$$V_e , (\text{CFM}) = V_e , (\text{m}^3/\text{s}) \times 2119$$

Design Margin

Add design margin to calculated exhaust rate:

$$V_{design} = V_e \times (1 + \text{margin})$$

Typical margins range from 10-20% to account for:

  • Calculation uncertainties
  • System leakage
  • Plug-holing effects
  • Non-uniform smoke layer

Exhaust Rate Tables

Axisymmetric Plume Exhaust Requirements

Fire Size: 2,500 kW (χc = 0.65)

Clear Height (m)Clear Height (ft)Mass Flow (kg/s)Exhaust Rate (m³/s)Exhaust Rate (CFM)
62029.225.754,500
93051.845.696,600
124079.770.2148,700
1550112.398.8209,400
1860149.4131.5278,600

Fire Size: 5,000 kW (χc = 0.65)

Clear Height (m)Clear Height (ft)Mass Flow (kg/s)Exhaust Rate (m³/s)Exhaust Rate (CFM)
62043.238.080,500
93076.667.4142,900
1240117.9103.8219,900
1550166.2146.3310,000
1860221.1194.6412,300

Assumptions: Ambient temperature 20°C, average smoke temperature 150°C, density 0.83 kg/m³

Exhaust Fan Sizing

Fan Selection Criteria

Size exhaust fans to provide calculated volumetric flow at system operating pressure:

  1. Volumetric capacity - Must meet or exceed calculated exhaust rate
  2. Pressure capability - Overcome system pressure losses (ductwork, dampers, louvers)
  3. Temperature rating - Rated for elevated smoke temperatures (minimum 250°F/121°C)
  4. Reliability - Dual fans or redundancy for critical applications

System Pressure Loss Estimation

Total system pressure loss:

$$\Delta P_{total} = \Delta P_{duct} + \Delta P_{fittings} + \Delta P_{damper} + \Delta P_{discharge}$$

Typical values:

  • Ductwork: 0.08-0.15 in. w.g. per 100 ft
  • Fire/smoke dampers: 0.10-0.25 in. w.g.
  • Louvers/grilles: 0.10-0.30 in. w.g.

Total system pressure: 0.5-1.5 in. w.g. for typical atrium installations

Exhaust System Configuration

graph TD
    A[Fire Source] -->|Heat Release| B[Smoke Plume]
    B -->|Air Entrainment| C[Rising Smoke Column]
    C -->|Accumulation| D[Smoke Layer at Height z]
    D -->|Smoke Layer Interface| E[Clear Layer Below]
    D -->|Exhaust Flow| F[Exhaust Inlets in Ceiling/Upper Wall]
    F --> G[Exhaust Duct System]
    G --> H[Exhaust Fans]
    H --> I[Discharge to Exterior]

    J[Makeup Air Inlets] -->|Replacement Air| E

    style A fill:#ff6b6b
    style D fill:#4a4a4a,color:#fff
    style E fill:#a8dadc
    style H fill:#457b9d,color:#fff

Calculation Procedure

Step-by-step exhaust rate determination:

  1. Establish design fire size - Select HRR based on occupancy and fuel load
  2. Determine clear height - Measure vertical distance from fire source to desired smoke layer interface
  3. Select plume equation - Choose axisymmetric, wall, or balcony spill plume based on geometry
  4. Calculate convective HRR - Apply convective fraction (Qc = χc × Q)
  5. Compute plume mass flow - Use appropriate plume equation with z and Qc
  6. Estimate smoke temperature - Calculate ΔT and smoke layer temperature
  7. Determine smoke density - Apply ideal gas law correction for temperature
  8. Calculate volumetric exhaust rate - Divide mass flow by smoke density
  9. Convert to design units - Convert m³/s to CFM if required
  10. Apply design margin - Add 10-20% safety factor
  11. Size exhaust fans - Select fans based on flow and pressure requirements

Critical Design Considerations

Smoke Layer Stability

Maintain exhaust rate balance to prevent:

  • Plug-holing - Excessive exhaust causing clear air entrainment
  • Smoke descent - Insufficient exhaust allowing smoke layer to descend

Makeup Air Requirements

Provide makeup air equal to exhaust rate to:

  • Prevent excessive building depressurization
  • Maintain intended smoke flow patterns
  • Avoid unintended door forces

Makeup air should enter below the smoke layer at low velocity (<500 fpm) to avoid disrupting stratification.

Multiple Atrium Considerations

For interconnected atria, analyze each space separately and provide isolation capability through automatic dampers or dedicated exhaust systems.

NFPA 92 Compliance

Design atrium exhaust systems per NFPA 92 Standard for Smoke Control Systems, addressing:

  • Design fire selection methodology
  • Plume equation applicability and limitations
  • Smoke layer interface height requirements
  • System acceptance testing criteria
  • Maintenance and inspection requirements

The Authority Having Jurisdiction determines acceptable design parameters and testing protocols.