Atrium Smoke Control Systems
Atrium smoke control systems protect occupants in large-volume spaces by managing smoke movement and maintaining tenable conditions during fire events. These systems address unique challenges posed by multi-story open spaces where conventional compartmentation strategies cannot be applied.
Design Philosophy
Atrium smoke control relies on maintaining a smoke layer above the occupied zone while providing sufficient time for evacuation. The primary objective is to keep the smoke layer interface at least 6 feet above the highest walking surface or occupiable level within the atrium.
Design Approaches
Three fundamental strategies govern atrium smoke control design:
| Approach | Method | Application | Advantages |
|---|---|---|---|
| Smoke Filling | Allow smoke accumulation with calculated fill time | Low-rise atriums with rapid egress | Minimal mechanical systems |
| Steady Smoke Layer | Exhaust smoke at rate equal to plume production | Mid-rise atriums | Maintains constant layer height |
| Natural Venting | Utilize buoyancy-driven flow through roof openings | Tall atriums with adequate height | No mechanical power required |
Fire Plume Characteristics
The smoke production rate from a fire determines exhaust requirements. The axisymmetric plume model provides the foundation for calculations.
Plume Mass Flow Rate
For fires not impinging on walls, the plume mass flow rate at height $z$ above the fire source:
$$\dot{m}_p = 0.071 Q_c^{1/3} (z - z_0)^{5/3}$$
Where:
- $\dot{m}_p$ = plume mass flow rate (kg/s)
- $Q_c$ = convective heat release rate (kW)
- $z$ = height above fire source (m)
- $z_0$ = virtual origin height (m)
Virtual Origin Correction
For fires with characteristic diameter $D$, the virtual origin:
$$z_0 = -1.02D + 0.083Q_c^{2/5}$$
This correction accounts for the physical size of the fuel source and prevents overestimation of plume entrainment near the fire base.
Exhaust Volumetric Flow Rate
The required volumetric exhaust rate depends on the plume mass flow and smoke layer temperature:
$$V = \frac{\dot{m}_p}{\rho_s}$$
Where $\rho_s$ is the smoke density at the layer temperature. For engineering calculations:
$$V = \dot{m}_p \left(\frac{T_s}{353}\right)$$
With $V$ in m³/s, $\dot{m}_p$ in kg/s, and $T_s$ in Kelvin.
System Configuration
graph TB
subgraph "Atrium Space"
A[Fire Source] -->|Heat & Smoke| B[Rising Plume]
B --> C[Smoke Layer]
C --> D[Smoke Layer Interface]
D -.->|Maintained Above| E[Occupied Zone]
end
subgraph "Exhaust System"
C --> F[Exhaust Inlets]
F --> G[Smoke Exhaust Fans]
G --> H[Discharge to Exterior]
end
subgraph "Makeup Air"
I[Makeup Air Inlets] --> E
I --> J[Low-Level Openings]
end
style C fill:#ff9999
style E fill:#99ff99
style G fill:#9999ff
Design Process Flow
flowchart TD
A[Define Design Fire] --> B[Calculate Heat Release Rate]
B --> C[Determine Clear Height]
C --> D[Calculate Plume Mass Flow]
D --> E{Natural Venting Feasible?}
E -->|Yes| F[Size Natural Vents]
E -->|No| G[Design Mechanical Exhaust]
F --> H[Calculate Vent Area]
H --> I[Verify Makeup Air Path]
G --> J[Select Fan Capacity]
J --> K[Design Ductwork]
K --> I
I --> L[Verify Layer Interface Height]
L --> M{Acceptable?}
M -->|Yes| N[Complete Design]
M -->|No| O[Increase Exhaust Rate]
O --> D
Code Requirements per NFPA 92
Design Fire Specifications
NFPA 92 provides guidance on design fire selection based on occupancy and fuel characteristics:
- Retail spaces: 5 MW steady-state fire
- Office atriums: 3 MW steady-state fire
- Assembly occupancies: Evaluate based on specific fuel loads
Design fires must consider both fire growth rate and steady-state heat release for time-dependent analysis.
Clear Height Requirements
Minimum clear height beneath the smoke layer:
- 6 feet above highest occupied level
- Additional height for thermal radiation consideration when layer temperature exceeds 200°F
Makeup Air Provisions
Makeup air must equal exhaust rate and enter below the smoke layer to prevent disruption of the stratified smoke layer. Maximum makeup air velocity: 200 fpm in occupied areas.
Mechanical vs. Natural Systems
Mechanical Exhaust Systems
Advantages:
- Precise control of exhaust rate
- Independent of environmental conditions
- Suitable for any atrium height
- Can integrate with HVAC systems
Design considerations:
- Fan temperature rating minimum 250°F
- Redundant fan capacity or backup power
- Inlet placement minimum 10 feet from plume centerline
- Ductwork slope to drain condensate
Natural Venting Systems
Required vent area for natural venting:
$$A_v = \frac{\dot{m}p}{\rho\infty C_v \sqrt{2g\Delta\rho h / \rho_\infty}}$$
Where:
- $A_v$ = vent area (m²)
- $C_v$ = vent coefficient (typically 0.6-0.7)
- $g$ = gravitational acceleration (9.81 m/s²)
- $\Delta\rho$ = density difference across vent
- $h$ = height of neutral plane above vent
Critical factors:
- Adequate atrium height (typically >60 feet)
- Reliable vent actuation mechanisms
- Wind effects on discharge
- Winter heating load impacts
System Integration
Atrium smoke control systems must coordinate with building HVAC:
- Normal operation: Standard HVAC maintains comfort conditions
- Smoke control mode: HVAC systems shut down or reconfigure to prevent smoke circulation
- Pressurization: Adjacent spaces may require pressurization to prevent smoke migration
Control sequences must be programmed in the fire alarm system with hardwired interfaces to HVAC controls for reliability.
Performance Verification
Computational fluid dynamics (CFD) modeling validates design assumptions for complex geometries or unusual fire scenarios. Physical testing after installation confirms:
- Exhaust flow rates within 10% of design
- Smoke layer interface maintenance at design height
- Makeup air flow patterns do not disrupt stratification
- Control system activation and sequencing
Periodic testing per NFPA 92 requirements ensures ongoing system functionality and compliance with the original design intent.
Sections
Smoke Layer Management in Atrium Smoke Control
Engineering principles for smoke layer interface height, depth calculation, tenability maintenance, and steady-state exhaust balance in atrium smoke control systems per NFPA 92.
Atrium Exhaust Rate Calculations for Smoke Control
Comprehensive guide to calculating exhaust rates for atrium smoke control systems using NFPA 92 plume equations, fire size assumptions, and mass flow rate calculations.
Makeup Air Systems for Atrium Smoke Control
Technical analysis of makeup air requirements, velocity limits, inlet positioning, and plume entrainment effects in atrium smoke exhaust systems per NFPA 92 standards.
NFPA 92 Atrium Smoke Control Requirements
Comprehensive guide to NFPA 92 Standard requirements for atrium smoke control design, including algebraic equations, CFD modeling criteria, and acceptance testing protocols.