HVAC Systems Encyclopedia

A comprehensive encyclopedia of heating, ventilation, and air conditioning systems

Ventilation Rates for Indoor Pool Facilities

Indoor swimming pools present unique ventilation challenges that distinguish them from conventional occupied spaces. The combination of high moisture loads, airborne chemical contaminants, and stringent comfort requirements demands ventilation systems engineered to address both air quality and thermodynamic constraints.

Fundamental Ventilation Drivers

Natatorium ventilation serves three primary functions: dilution of airborne contaminants, moisture control, and space pressurization. Unlike typical commercial spaces where ventilation primarily addresses occupant CO₂ generation, pool facilities must contend with continuous off-gassing of chloramines and other disinfection byproducts from the water surface.

Chloramine Formation and Off-Gassing

When chlorine-based disinfectants react with nitrogenous compounds introduced by swimmers (urea, sweat, cosmetics), they form combined chlorine compounds known as chloramines. The most problematic is nitrogen trichloride (NCl₃), which volatilizes readily at typical pool water temperatures.

The mass transfer rate of chloramines from water to air follows:

$$\dot{m}_{NCl_3} = k_L \cdot A \cdot (C_L - C_L^*)$$

Where:

  • $\dot{m}_{NCl_3}$ = mass transfer rate of trichloramine (lb/hr)
  • $k_L$ = overall mass transfer coefficient (ft/hr)
  • $A$ = water surface area (ft²)
  • $C_L$ = bulk liquid concentration (ppm)
  • $C_L^*$ = equilibrium concentration at the interface (ppm)

The mass transfer coefficient increases with water surface turbulence (wave action, fountains, slides) and air velocity across the surface. This explains why active pools generate higher contaminant loads than quiescent water bodies.

Code-Mandated Outdoor Air Requirements

ASHRAE 62.1 Minimum Rates

ASHRAE Standard 62.1 specifies minimum ventilation rates for natatoriums based on deck area and spectator occupancy:

Space TypeOutdoor Air RateApplication
Pool Deck (inactive)0.48 cfm/ft²Deck area method
Pool Deck (active/competition)0.48 cfm/ft² + occupant componentDeck + occupancy
Spectator AreasBased on Table 6-1 occupancyAssembly spaces

For a typical 25m × 12m pool (984 ft² water surface) with 1,500 ft² deck area:

$$V_{OA,min} = 0.48 \times 1500 = 720 \text{ cfm}$$

This represents the absolute minimum. Actual requirements frequently exceed code minimums due to contaminant control needs.

International Mechanical Code (IMC) Requirements

The IMC Section 403.3.2 mandates that natatoriums maintain negative pressure relative to adjacent occupied spaces, requiring exhaust-to-supply air imbalance. Most jurisdictions require 5-15% exhaust excess.

Contaminant Dilution Requirements

The critical ventilation driver is chloramine concentration control. Recommended maximum trichloramine concentrations:

  • Recreational pools: 0.5 mg/m³ (0.0002 gr/ft³)
  • Competition facilities: 0.3 mg/m³ (0.00012 gr/ft³)
  • Health/therapy pools: 0.2 mg/m³ (0.00008 gr/ft³)

The required ventilation rate for dilution follows:

$$Q_{dil} = \frac{\dot{m}{NCl_3}}{\rho{air} \cdot (C_{max} - C_{OA})}$$

Where:

  • $Q_{dil}$ = dilution airflow rate (cfm)
  • $\rho_{air}$ = air density (lb/ft³)
  • $C_{max}$ = maximum allowable indoor concentration (gr/lb)
  • $C_{OA}$ = outdoor air concentration (typically zero)

For typical recreational pools, this calculation yields 4-8 air changes per hour (ACH), significantly exceeding ASHRAE 62.1 minimums. Competition pools and facilities with poor water chemistry may require 8-12 ACH.

Exhaust Strategy and Air Distribution

Effective contaminant removal requires strategic exhaust placement. Chloramines are slightly denser than air (molecular weight ~120 vs. 29 for air), promoting settling toward deck level. However, thermal stratification from warm water surfaces creates upward convection currents.

graph TD
    A[Water Surface Evaporation] --> B[Warm Moist Plume Rising]
    B --> C[Ceiling-Level Stratification]
    C --> D[High-Level Return/Exhaust]
    A --> E[Chloramine Off-Gassing]
    E --> F[Deck-Level Contamination]
    F --> G[Low-Level Exhaust]
    H[Supply Air Distribution] --> I[Perimeter Delivery]
    I --> J[Surface Sweep Pattern]
    J --> D
    J --> G

Recommended Exhaust Distribution:

Exhaust LocationPercentage of TotalFunction
Deck level (< 3 ft)30-40%Direct chloramine capture
Water surface (< 8 ft)20-30%Intercept rising plume
Ceiling level30-50%General dilution/moisture control

Low-level exhaust should maintain 50-100 fpm velocity across deck surfaces without creating drafts in occupied zones. High-level exhaust integrates with dehumidification returns.

Space Pressurization Control

Natatoriums must operate at negative pressure (-0.02 to -0.05 in. w.c.) relative to adjacent spaces to prevent migration of humid, chloramine-laden air into corridors, locker rooms, and mechanical spaces. This pressurization is achieved through exhaust-supply imbalance.

Pressure Differential Calculation:

$$\Delta P = \frac{\rho \cdot v^2}{2} + \rho \cdot g \cdot h \cdot \Delta T_{adj}$$

Where the velocity pressure component dominates in properly sealed spaces. The required exhaust excess:

$$Q_{exhaust} = Q_{supply} + Q_{excess}$$

Typical $Q_{excess}$ = 10-15% of supply, adjusted based on:

  • Building envelope tightness (tighter = less excess needed)
  • Door traffic patterns (high traffic = more excess)
  • Adjacent space pressure requirements

Differential pressure sensors with direct digital control (DDC) modulation of exhaust fans maintain setpoint under varying conditions.

Energy Considerations

Ventilation represents the dominant energy load in natatorium HVAC systems. For a 2,000 ft² deck facility in a heating climate:

Annual Ventilation Energy Load (Heating Season):

$$Q_{vent,heating} = \dot{m}{OA} \cdot c_p \cdot (T{indoor} - T_{outdoor}) \cdot t_{heating}$$

At 1,500 cfm outdoor air, 82°F indoor, 35°F average outdoor, 6,000 heating hours:

$$Q_{vent,heating} = \frac{1500 \times 0.075}{60} \times 0.24 \times (82-35) \times 6000 = 2.55 \times 10^6 \text{ Btu}$$

This excludes latent load conditioning (typically 2-3× the sensible load) and represents ~40-60% of total facility heating energy.

Energy Recovery Strategies:

  1. Enthalpy wheels: 60-75% total effectiveness
  2. Plate heat exchangers: 50-65% sensible effectiveness
  3. Heat pipe systems: 45-55% sensible effectiveness
  4. Run-around loops: 50-60% sensible effectiveness

Chloramine corrosion limits recovery options. Enthalpy wheels risk cross-contamination; plate exchangers require corrosion-resistant materials (aluminum or coated). Many designers specify run-around glycol loops with separation between exhaust and supply airstreams.

Integration with Dehumidification Systems

Dedicated pool dehumidifiers provide the majority of space air circulation (8-12 ACH), while the ventilation system introduces outdoor air and exhausts contaminated air. The systems integrate at the dehumidifier return:

flowchart LR
    A[Outdoor Air] --> B[Preconditioning Coil]
    B --> C[Dehumidifier Return Mixing]
    D[Pool Space] --> E[Return Air]
    E --> C
    C --> F[Dehumidifier Unit]
    F --> G[Supply to Space]
    D --> H[Direct Exhaust]
    H --> I[Energy Recovery]
    I --> J[Exhaust to Atmosphere]
    J -.Heat Recovery.-> B

The outdoor air fraction in the dehumidifier return typically ranges from 15-35%, with modulating dampers maintaining space pressure while meeting minimum ventilation rates.

Summary

Natatorium ventilation rates are governed by chloramine dilution requirements rather than occupancy-based calculations. Typical facilities require 4-8 ACH minimum, with strategic exhaust placement at multiple levels to capture both deck-level contaminants and ceiling stratification. Negative pressurization through exhaust excess prevents migration to adjacent spaces. Energy recovery is essential for operational cost control but must address corrosion concerns inherent to chlorinated environments.

Proper ventilation system design balances air quality, comfort, pressure control, and energy efficiency—a significantly more complex challenge than conventional commercial HVAC applications.

Sections

Air Change Rates for Natatoriums

Technical analysis of air change rate requirements for indoor swimming pools including outdoor air calculations, activity-based ventilation rates, and zone-specific requirements.

Outdoor Air Requirements for Natatorium Ventilation

Technical analysis of outdoor air requirements for indoor pools including ASHRAE 62.1 calculations, chloramine dilution rates, makeup air provisions, and pressurization strategies.

Exhaust Air Volumes for Natatorium Design

Engineering calculations for natatorium exhaust air quantities, deck and ceiling exhaust strategies, velocity requirements, chloramine removal, and exhaust-to-supply ratios.

Ventilation Effectiveness in Natatoriums

Physics-based analysis of air distribution patterns, displacement vs mixing ventilation, stratification effects, CFD modeling, and contaminant removal efficiency in indoor pool facilities.