Laboratory Makeup Air Systems: Design & Calculations

Laboratory facilities present unique makeup air challenges due to their requirement for 100% outdoor air, high exhaust rates from fume hoods and biological safety cabinets, and stringent pressure control requirements. Unlike typical commercial buildings that recirculate 70-90% of supply air, laboratories discharge all exhaust air to prevent cross-contamination, creating substantial makeup air demands that directly impact energy consumption and system design.

Physical Principles of Laboratory Makeup Air

Laboratory makeup air systems operate on the fundamental principle of mass conservation. Every kilogram of air exhausted must be replaced by an equal mass of outdoor air to maintain space pressure control. The relationship is expressed as:

$$\dot{m}{supply} = \dot{m}{exhaust} + \dot{m}_{exfiltration}$$

For pressurized laboratories (positive pressure relative to adjacent spaces):

$$Q_{supply} = Q_{exhaust} + Q_{pressurization}$$

where $Q_{supply}$ is total supply airflow (cfm), $Q_{exhaust}$ is total exhaust including fume hoods, biosafety cabinets, and general exhaust (cfm), and $Q_{pressurization}$ typically ranges from 100-300 cfm depending on laboratory size and door undercut area.

For negatively pressurized laboratories (containment spaces):

$$Q_{supply} = Q_{exhaust} - Q_{pressurization}$$

The makeup air system must condition outdoor air from ambient conditions to space setpoint, requiring sensible and latent cooling capacity calculated as:

$$\dot{Q}_{sensible} = 1.08 \times Q \times \Delta T$$

$$\dot{Q}_{latent} = 4840 \times Q \times \Delta W$$

where $Q$ is airflow (cfm), $\Delta T$ is temperature difference (°F), and $\Delta W$ is humidity ratio difference (lb water/lb dry air). The factor 1.08 incorporates air density (0.075 lb/ft³) and specific heat (0.24 Btu/lb·°F), while 4840 accounts for the latent heat of vaporization.

Laboratory Makeup Air System Architecture

graph TB
    OA[Outdoor Air Intake<br/>100% OA] --> PF[Prefilter<br/>MERV 8]
    PF --> ERW[Energy Recovery Wheel<br/>Sensible + Latent]
    ERW --> CC[Cooling Coil<br/>CHW or DX]
    CC --> FF[Final Filter<br/>MERV 14-16]
    FF --> SF[Supply Fan<br/>VFD Controlled]
    SF --> RH[Reheat Coil<br/>Hot Water or Electric]
    RH --> DD[Duct Distribution<br/>VAV or Constant Volume]
    DD --> LAB[Laboratory Space]

    LAB --> FH[Fume Hoods<br/>Variable Volume]
    LAB --> BSC[Biosafety Cabinets<br/>Class II Type B]
    LAB --> GE[General Exhaust<br/>Chemical Storage]

    FH --> EF1[Exhaust Fan 1<br/>Dedicated Hood System]
    BSC --> EF2[Exhaust Fan 2<br/>Biological Exhaust]
    GE --> EF3[Exhaust Fan 3<br/>General Lab Exhaust]

    EF1 --> ERW
    EF2 --> HEPA[HEPA Filter<br/>99.97% at 0.3μm]
    HEPA --> ERW
    EF3 --> ERW

    ERW --> ATM[Atmosphere<br/>Exhaust Discharge]

    style LAB fill:#e1f5ff
    style ERW fill:#ffe1e1
    style OA fill:#e1ffe1

Makeup Air Conditioning Strategies

Laboratory makeup air systems employ various conditioning strategies based on climate, exhaust heat load, and energy efficiency requirements:

StrategyApplicationsAdvantagesLimitationsTypical Energy Recovery
Direct Outdoor AirMild climates, low exhaust ratesSimple controls, low first costHigh energy use, poor humidity controlNone (0% recovery)
Sensible WheelAll climates, chemical labs70-80% sensible recovery, proven reliabilityNo latent recovery in humid climates70-80% sensible only
Enthalpy WheelHumid climates, general labs70-80% total recovery, humidity controlCross-contamination risk, requires purge70-80% total energy
Runaround LoopBiosafety labs, separated intake/exhaustZero cross-contamination, flexible placement50-65% sensible recovery, pumping energy50-65% sensible only
Heat PipeChemical labs, passive recoveryNo moving parts, no cross-contamination45-60% sensible recovery, fixed effectiveness45-60% sensible only
Dedicated OA with Chilled BeamsLow exhaust rate labs, high cooling loadsDecouples ventilation from coolingRequires low dewpoint supply air70-80% with wheel

Makeup Air Calculations for Laboratory Design

The design process begins with exhaust airflow determination. For a typical chemistry laboratory with four 6-foot fume hoods operating at 100 fpm face velocity:

$$Q_{hood} = \text{Face Area} \times \text{Face Velocity}$$

$$Q_{hood} = (6 \text{ ft} \times 5 \text{ ft}) \times 100 \text{ fpm} = 3000 \text{ cfm per hood}$$

Total hood exhaust for four hoods:

$$Q_{hood,total} = 4 \times 3000 = 12,000 \text{ cfm}$$

Adding general laboratory exhaust at 0.5 cfm/ft² for a 2,400 ft² lab:

$$Q_{general} = 2400 \text{ ft}^2 \times 0.5 \text{ cfm/ft}^2 = 1200 \text{ cfm}$$

Total exhaust requirement:

$$Q_{exhaust,total} = 12,000 + 1,200 = 13,200 \text{ cfm}$$

For positive pressurization at 0.05 in. w.c., add 200 cfm:

$$Q_{supply} = 13,200 + 200 = 13,400 \text{ cfm}$$

The makeup air cooling load for summer design conditions (95°F DB, 78°F WB outdoor to 75°F DB, 50% RH space condition):

$$\dot{Q}_{sensible} = 1.08 \times 13,400 \times (95 - 75) = 289,440 \text{ Btu/hr} = 24.1 \text{ tons}$$

For latent cooling, outdoor humidity ratio at 95°F/78°F WB is approximately 0.0158 lb/lb, while space condition at 75°F/50% RH is 0.0093 lb/lb:

$$\dot{Q}_{latent} = 4840 \times 13,400 \times (0.0158 - 0.0093) = 421,148 \text{ Btu/hr} = 35.1 \text{ tons}$$

Total cooling load without energy recovery:

$$\dot{Q}_{total} = 289,440 + 421,148 = 710,588 \text{ Btu/hr} = 59.2 \text{ tons}$$

With an 75% effective enthalpy wheel, the cooling load reduces to:

$$\dot{Q}_{total,ERV} = 710,588 \times (1 - 0.75) = 177,647 \text{ Btu/hr} = 14.8 \text{ tons}$$

Design Considerations per ASHRAE Standards

ASHRAE 62.1 requires laboratory ventilation rates based on occupancy and process emissions, typically resulting in 100% outdoor air systems. Key design parameters include:

  • Minimum ventilation rate: 0.18 cfm/ft² plus 5 cfm per occupant (ASHRAE 62.1)
  • Fume hood face velocity: 80-120 fpm per ANSI/AIHA Z9.5
  • Air change rate: 6-12 ACH minimum for general chemistry labs
  • Pressure differential: ±0.01 to ±0.05 in. w.c. relative to corridors
  • Supply air temperature: 55-58°F for humidity control in humid climates
  • Diversity factor: 0.6-0.8 for hood exhaust (not all hoods at full flow simultaneously)

The makeup air system must respond dynamically to variable exhaust demands. Modern laboratories use VAV fume hoods that modulate exhaust flow based on sash position, reducing face velocity from 100 fpm to 60-80 fpm when sashes close. The makeup air system tracks exhaust flow using direct airflow measurement or differential pressure control, maintaining space pressurization within ±0.01 in. w.c. under all operating conditions.

Energy recovery effectiveness depends on exhaust temperature. Labs with high internal heat gains from equipment maintain elevated exhaust temperatures year-round, improving winter heat recovery. Summer recovery effectiveness decreases when outdoor air temperatures approach exhaust temperatures, particularly during unoccupied periods when internal gains decrease.

System Components and Selection

Makeup air handling units for laboratories require corrosion-resistant construction (stainless steel or epoxy-coated) due to chemical exposure. Fan selection must account for high external static pressure from ductwork, filters, and energy recovery devices, typically 4-6 in. w.c. total.

Energy recovery wheels should include purge sections (10-15% of wheel face) to minimize cross-contamination. Molecular sieve or silica gel desiccant coatings provide latent recovery in humid climates. Wheel speeds of 10-20 rpm balance pressure drop with effectiveness.

Filtration follows a two-stage approach: MERV 8 prefilters protect coils and energy recovery, while MERV 14-16 final filters provide air cleanliness required for sensitive research operations.

Humidification may be required in cold climates where outdoor air moisture content falls below laboratory setpoints. Steam humidifiers avoid the contamination risk associated with evaporative systems in research environments.

The integration of makeup air with exhaust tracking, pressure control, and energy recovery forms the foundation of safe, energy-efficient laboratory operation.