Fume Hoods
Laboratory fume hoods provide critical containment for chemical vapors, gases, and particulates. HVAC system design must ensure proper exhaust rates, face velocities, and room air balance while optimizing energy consumption.
Fume Hood Types
Conventional (Constant Air Volume)
Fixed exhaust rate regardless of sash position:
- Simple operation
- Higher energy consumption
- Face velocity varies with sash position
- Suitable for teaching labs, limited budgets
Variable Air Volume (VAV)
Exhaust modulates with sash position:
- Maintains constant face velocity
- Significant energy savings (40-60%)
- More complex controls
- Standard for research laboratories
Auxiliary Air (Add-Air)
Supplemental air supply at hood face:
- Reduces conditioned air consumption
- Not recommended (containment concerns)
- Prohibited by many institutions
- Legacy installations only
Ductless (Filtered)
Carbon filter recirculation to room:
- No duct connection required
- Limited chemical compatibility
- Filter saturation monitoring critical
- Not appropriate for all applications
Face Velocity Requirements
Design Face Velocity
ASHRAE and AIHA recommendations:
| Application | Face Velocity | Notes |
|---|---|---|
| Standard chemicals | 80-100 fpm | Most common |
| High hazard | 100-120 fpm | Highly toxic materials |
| Low hazard | 60-80 fpm | Nuisance materials |
| Perchloric acid | 100-120 fpm | Dedicated system |
| Radioisotope | 100-125 fpm | Specialized requirements |
Sash Position Considerations
Face velocity calculated at working opening:
$$V_{face} = \frac{Q_{exhaust}}{A_{opening}}$$
Full Open Sash: Maximum exhaust, design face velocity Partially Closed: Reduced exhaust (VAV), maintained face velocity Fully Closed: Minimum exhaust (bypass air or slot)
Exhaust System Design
Individual Exhaust
One fan per hood:
- No cross-contamination
- Independent operation
- Higher capital cost
- More roof penetrations
Manifold Exhaust
Multiple hoods share exhaust system:
- Lower cost
- Fewer penetrations
- Dilution of concentrated vapors
- Requires careful design
System Configurations
Constant Volume Manifold:
- Bypass dampers at each hood
- Central fan runs constant
- Individual hood VAV possible
Variable Volume Manifold:
- Total exhaust varies with demand
- Variable speed fan(s)
- Significant energy savings
- Complex controls
Exhaust Fan Selection
| Criteria | Specification |
|---|---|
| Material | Corrosion-resistant |
| Location | Roof preferred (negative duct) |
| Redundancy | Consider backup fan |
| Capacity | All hoods at maximum |
Stack Design
Discharge above roof:
- 10 ft minimum above roof
- 2 ft above adjacent air intakes
- Adequate exit velocity (3,000+ fpm)
- Rain protection
Room Air Balance
Makeup Air
Supply air must balance exhaust:
$$\dot{V}{supply} = \dot{V}{fume\ hoods} + \dot{V}{general\ exhaust} - \dot{V}{infiltration}$$
Maintain slight negative pressure relative to corridor.
Air Change Rates
Laboratory air changes (total supply):
| Risk Level | Minimum ACH |
|---|---|
| General chemistry | 6-10 |
| Organic chemistry | 8-12 |
| High hazard | 10-15 |
| Teaching lab | 6-8 |
Supply Air Distribution
Position supply to avoid disrupting hoods:
- Maintain <50 fpm at hood face
- No supply directly opposing hood
- Perforated ceiling or high sidewall
Control Systems
VAV Hood Controls
Monitor and modulate:
- Sash position sensor
- Face velocity measurement
- Exhaust damper/valve
- Alarm on low face velocity
Room Pressure Control
Track supply with exhaust changes:
- Direct pressure control
- Offset tracking
- Cascade control
- Response time matching
Building Automation
BAS integration requirements:
- Hood status monitoring
- Alarm management
- Energy monitoring
- Occupancy scheduling
Performance Testing
ASHRAE 110 Method
Standard test protocol:
- Face Velocity Test: Measure velocity uniformity
- Flow Visualization: Observe smoke patterns
- Tracer Gas Test: Quantify containment (as manufactured: <0.05 ppm; as installed: <0.10 ppm)
Periodic Verification
Annual testing minimum:
- Face velocity measurement
- Visual inspection
- Alarm verification
- Sash sensor calibration
Continuous Monitoring
Real-time parameters:
- Face velocity or exhaust flow
- Sash position
- Room pressure differential
- Alarm status
Energy Efficiency
VAV Hood Benefits
Energy savings from VAV:
$$Savings = \sum hours \times (Q_{CV} - Q_{VAV}) \times \Delta h \times Cost$$
Typical 40-60% reduction in hood-related energy.
Occupancy-Based Control
Further reduction when labs unoccupied:
- Setback face velocity (50-60 fpm)
- Maintain minimum air changes
- Rapid return to normal on entry
Sash Management
Operator behavior programs:
- Close sashes when not in use
- Alarm on extended full-open
- Training and awareness
- Significant savings potential
Heat Recovery
For high exhaust volumes:
- Runaround coils (no cross-contamination)
- Heat pipe systems
- Energy wheels (careful with contaminants)
- Return on investment analysis
Special Hood Types
Perchloric Acid Hoods
Dedicated system with:
- Stainless steel construction
- Wash-down system
- No manifold connection
- Direct exhaust
Radioisotope Hoods
HEPA filtration with:
- Bag-in/bag-out filter
- Higher face velocity
- Glove box option
- Special waste handling
Walk-In Hoods
Large equipment accommodation:
- Higher exhaust volumes
- Multiple sash options
- Floor-level exhaust
Effective fume hood HVAC integration ensures occupant safety while managing the substantial energy requirements of these critical containment devices through appropriate system design and control strategies.
Sections
Variable Air Volume Fume Hoods
VAV fume hood systems with sash position sensing, face velocity control algorithms, energy savings analysis, and safety interlock design per ANSI/AIHA Z9.5 standards.