HVAC Systems Encyclopedia

A comprehensive encyclopedia of heating, ventilation, and air conditioning systems

Laboratory HVAC Systems

Laboratory HVAC Systems

Laboratory HVAC systems provide continuous exhaust ventilation for chemical fume hoods, biological safety cabinets, and other containment devices while maintaining precise pressure relationships and high air change rates to ensure occupant safety and experimental integrity. These systems differ fundamentally from conventional building HVAC through continuous 100% outside air operation, elimination of recirculation, sophisticated pressure cascade control, and variable air volume coordination between room supply and exhaust. Design complexity increases significantly with the number of fume hoods, diversity of research activities, and stringency of containment requirements. ASHRAE Applications Handbook Chapter 16 and ANSI/AIHA Z9.5 establish the engineering framework for laboratory ventilation design.

Fundamental Design Criteria

Air Change Requirements

Laboratory ventilation rates substantially exceed commercial building standards to ensure rapid contaminant dilution and removal.

Minimum air change rates by laboratory type:

Laboratory ClassificationAir Changes per HourBasisStandard Reference
General chemistry laboratory6-12 ACHRisk assessmentASHRAE Applications Ch. 16
Teaching laboratory6-10 ACHModerate hazardANSI Z9.5
Research laboratory (chemical)8-12 ACHHigh hazard potentialANSI Z9.5
Biological laboratory (BSL-1, BSL-2)6-12 ACHInfection controlCDC/NIH BMBL
Radioisotope laboratory8-12 ACHContamination control10 CFR 20
Animal research facility10-15 ACHOdor and allergen controlGuide for Care and Use
High-hazard laboratory12-20 ACHMaximum protectionSite-specific assessment

Air change rate calculation:

$$ACH = \frac{Q_{room}}{V_{room}} \times 60$$

Where:

  • $Q_{room}$ = Room airflow rate (CFM)
  • $V_{room}$ = Room volume (ft³)
  • 60 = Minutes per hour

Actual ventilation rate determination: Total room supply airflow must account for both minimum air changes and fume hood makeup requirements:

$$Q_{supply} = \max\left(ACH \times \frac{V_{room}}{60}, Q_{exhaust} + Q_{infiltration}\right)$$

Where:

  • $Q_{exhaust}$ = Total laboratory exhaust (fume hoods + auxiliary exhausts)
  • $Q_{infiltration}$ = Required exfiltration for negative pressure maintenance

Pressure Relationships

Laboratory spaces operate under negative pressure relative to adjacent corridors and offices to prevent contaminant migration during door openings or envelope leakage.

Pressure cascade hierarchy:

  1. Office/administrative areas: 0 Pa (reference)
  2. Corridor: -2.5 Pa to -5 Pa relative to office
  3. General laboratory: -5 Pa to -10 Pa relative to corridor
  4. High-hazard laboratory: -10 Pa to -15 Pa relative to corridor
  5. Biological safety laboratory (BSL-3): -12.5 Pa minimum relative to corridor
  6. Radioisotope laboratory: -12.5 Pa to -25 Pa relative to corridor

Pressure differential maintenance: Differential pressure results from volumetric imbalance between supply and exhaust:

$$\Delta P = \frac{\rho (Q_{exhaust} - Q_{supply})^2}{2 C^2 A^2}$$

Where:

  • $\Delta P$ = Pressure differential (in w.c.)
  • $\rho$ = Air density (0.075 lb/ft³ at standard conditions)
  • $Q_{exhaust}$ = Total exhaust airflow (CFM)
  • $Q_{supply}$ = Supply airflow (CFM)
  • $C$ = Discharge coefficient (0.65 typical for door undercut)
  • $A$ = Leakage area (ft²)

Simplified relationship for initial design: For standard laboratory envelope tightness:

$$Q_{exhaust} - Q_{supply} = 150 \text{ CFM per door for } -5 \text{ Pa differential}$$

Pressure control tolerance: Control systems must maintain pressure within ±1.25 Pa of setpoint under all operating conditions including door openings, sash position changes, and hood on/off cycling.

Fume Hood Requirements

Fume Hood Exhaust Volumes

Chemical fume hoods constitute the dominant exhaust load and variable component in laboratory HVAC systems.

Face velocity criteria: ANSI Z9.5 establishes 80-120 FPM face velocity for chemical fume hoods with 100 FPM as standard design basis. Containment testing per ASHRAE 110 validates actual containment performance.

Exhaust airflow calculation:

$$Q_{hood} = V_{face} \times A_{opening}$$

Where:

  • $Q_{hood}$ = Hood exhaust (CFM)
  • $V_{face}$ = Face velocity (100 FPM typical)
  • $A_{opening}$ = Sash opening area (ft²)

Standard hood sizing:

Hood WidthSash Height (18" working height)Full Open Area100 FPM Airflow6" Sash Opening Airflow
4 ft28 in9.3 ft²930 CFM200 CFM
5 ft28 in11.7 ft²1,170 CFM250 CFM
6 ft28 in14.0 ft²1,400 CFM300 CFM
8 ft28 in18.7 ft²1,870 CFM400 CFM

Minimum exhaust during sash closure: VAV hoods reduce to minimum airflow (typically 150-200 CFM for 4-6 ft hoods) when sash closes to maintain slight negative pressure in hood interior and prevent chemical vapor stratification.

Variable Air Volume Hood Control

VAV fume hood systems modulate exhaust volume based on sash position, achieving 50-70% energy reduction compared to constant volume systems while maintaining constant face velocity.

Control sequence:

  1. Sash position sensor (infrared or ultrasonic) measures vertical opening
  2. Controller calculates required airflow: $Q = 100 \text{ FPM} \times W \times H$
  3. Exhaust valve modulates to maintain setpoint
  4. Airflow measurement station (pitot array or thermal dispersion) provides feedback
  5. Room pressure controller adjusts supply air to track exhaust changes
  6. System stabilizes at new operating point

Response time requirement: VAV systems must respond to sash position changes within 1-3 seconds to prevent face velocity excursions during rapid sash movement. This requires:

  • Fast-acting VAV valves (< 5 second full stroke)
  • Controller scan rate: 0.5-1.0 second
  • Supply air tracking response: 2-5 seconds

Minimum turndown ratio: VAV hoods must achieve turndown ratio of 4:1 to 10:1 (full open to minimum closed flow) depending on hood size and minimum exhaust requirements.

Supply air tracking: Room supply air must track hood exhaust changes while maintaining pressure differential:

$$Q_{supply}(t) = Q_{exhaust}(t) - Q_{offset}$$

Where:

  • $Q_{offset}$ = Fixed offset for negative pressure (150-300 CFM typical)
  • Response must occur within 2-5 seconds of exhaust change

Control stability: VAV laboratory systems require careful tuning to prevent hunting between supply and exhaust control loops. Proportional-integral (PI) control with feed-forward from hood sash position provides optimal stability.

Makeup Air Systems

100% Outside Air Requirement

Laboratory HVAC systems operate with 100% outside air—no recirculation permitted—due to unknown chemical contaminants, biological agents, and regulatory restrictions (OSHA, ANSI Z9.5).

Energy implications:

  • Heating load: $Q_h = 1.08 \times CFM \times (T_{室} - T_{OA})$
  • Cooling load: $Q_c = 4.5 \times CFM \times (\Delta h)$ where $\Delta h$ = enthalpy difference
  • Annual heating energy typically 3-5 times conventional building
  • Annual cooling energy typically 1.5-2.5 times conventional building

Makeup air delivery strategies:

StrategyDescriptionApplicationAdvantageDisadvantage
Low-velocity general supplyCeiling diffusers, 50-100 FPMGeneral laboratoriesUniform temperaturePoor hood protection
High-velocity perimeter supplySlots/diffusers at exterior walls, 150-300 FPMCold climate labsPerimeter load offsetHigher noise
Laminar ceiling supplyFull ceiling coverage, < 50 FPMCleanroom labsMaximum uniformityHighest cost
Makeup air collarsDirect supply above each hoodConstant volume labsDirect replacementCross-drafts at hood

Cross-draft prevention: Supply air must not create velocities exceeding 50 FPM at hood face to prevent containment disruption. Supply diffusers should be located:

  • Minimum 6 ft from hood face
  • Directed away from hood opening
  • At ceiling height, not at working level

Energy Recovery Limitations

Energy recovery between laboratory exhaust and supply air faces significant constraints due to contamination concerns and cross-contamination prevention.

Prohibited recovery methods:

  • Rotary heat wheels (direct cross-contamination path)
  • Heat pipe exchangers in chemical labs (tube rupture concern)
  • Run-around loops with common glycol (cross-contamination if leak)

Permitted recovery methods:

  • Run-around glycol loops with dedicated loops per system
  • Plate heat exchangers with verified separation
  • Runaround loops on non-chemical exhausts (animal facilities)
  • Exhaust air heat pumps for building heating water

Recovery effectiveness limitations: Due to contamination prevention requirements, laboratory heat recovery effectiveness typically limited to 40-60% versus 70-80% in conventional buildings.

System Configurations

Constant Air Volume vs. Variable Air Volume

Constant volume systems:

  • All hoods exhaust at maximum design airflow continuously
  • Supply air equals exhaust minus offset (constant)
  • Simple controls and operation
  • Energy inefficient: 100% airflow 24/7
  • Used in high-hazard labs requiring maximum ventilation

Variable air volume systems:

  • Hood exhaust modulates with sash position
  • Supply air tracks exhaust to maintain pressure
  • Complex controls requiring sophisticated coordination
  • Energy efficient: 40-60% average airflow reduction
  • Standard for research and teaching laboratories

Hybrid approach: Some laboratories combine VAV hoods with constant volume auxiliary exhausts (biosafety cabinets, general exhaust) requiring supply air to track only hood variations while maintaining base load.

Central vs. Dedicated Exhaust Systems

Central manifolded exhaust:

  • Multiple hoods connect to common exhaust duct
  • Single large fan serves multiple rooms or floor
  • Lower initial cost per hood
  • Chemical compatibility concerns (acids + bases)
  • Cross-contamination potential during upset
  • Complex control with multiple VAV hoods

Dedicated hood exhaust:

  • Individual fan per hood or per room
  • Direct vertical discharge
  • Chemical compatibility not an issue
  • Easier VAV control
  • Higher installation cost
  • Better safety through isolation

Manufacturer recommendations: ANSI Z9.5 recommends dedicated exhaust systems for incompatible chemicals (particularly perchloric acid hoods requiring wash-down ductwork) and high-hazard materials.

Controls and Monitoring

Critical Control Parameters

Laboratory HVAC controls must continuously monitor and control:

  1. Face velocity (80-120 FPM)
  2. Hood exhaust airflow (accuracy ±10%)
  3. Room supply airflow (accuracy ±10%)
  4. Room static pressure (±1.25 Pa tolerance)
  5. Supply air temperature (±2°F)
  6. Outside air volume (100% of supply)

Alarm conditions requiring notification:

  • Face velocity < 80 FPM or > 120 FPM
  • Room pressure above -2.5 Pa (loss of negative pressure)
  • Loss of airflow measurement signal
  • Supply/exhaust fan failure
  • Sash position exceeds safe working height

Building Automation Integration

Laboratory HVAC requires sophisticated building automation with:

  • Stand-alone microprocessor controllers at each hood and room
  • Peer-to-peer communication between supply and exhaust controllers
  • Real-time pressure monitoring with fast loop response (1-5 second)
  • Historical trending for commissioning and troubleshooting
  • Remote monitoring capability for after-hours alarm response
  • Integration with chemical inventory management systems (advanced facilities)

Interlock requirements:

  • Supply fan proven on before exhaust fan energizes (prevents positive pressure)
  • Exhaust fan failure triggers supply fan shutdown after brief delay
  • Loss of hood airflow triggers local and remote alarms
  • Emergency power transfer must maintain minimum ventilation

Laboratory HVAC systems represent the most complex and energy-intensive building ventilation application, requiring expertise in safety engineering, control systems, and HVAC fundamentals. Proper design, commissioning, and ongoing performance verification ensure researcher safety while maintaining experimental integrity and managing operating costs.

Sections

Fume Hood Systems: Design & Performance

Engineering analysis of chemical fume hood systems including face velocity calculations, containment principles, bypass configurations, VAV control strategies, and ASHRAE 110 testing methods.

Laboratory Exhaust Systems

Comprehensive guide to laboratory exhaust systems including fume hood exhaust design, manifolded systems, stack height calculations, wind effects, and re-entrainment prevention per ANSI Z9.5 standards.

Fume Hoods

HVAC design for laboratory fume hood systems including face velocity requirements, exhaust configurations, and control strategies.

Laboratory Makeup Air Systems: Design & Calculations

Technical guide to laboratory makeup air system design, including mass balance calculations, conditioning strategies, and energy recovery for 100% outdoor air applications.

Laboratory HVAC Control Systems

Engineering analysis of laboratory HVAC control systems including pressure tracking algorithms, VAV fume hood sash position control, supply-exhaust coordination, room pressurization sequences, and safety interlocks per ASHRAE and ANSI Z9.5 standards.

Biosafety Cabinets

HVAC considerations for biosafety cabinet integration including exhaust connections, airflow requirements, and containment verification.