HVAC Systems Encyclopedia

A comprehensive encyclopedia of heating, ventilation, and air conditioning systems

Ventilation Security Areas

Ventilation in Security Areas

Security area ventilation in justice facilities requires precise control of airflow patterns, pressure relationships, and air quality while maintaining operational security. The HVAC system must prevent contamination migration, control odor transfer, support security functions, and operate reliably under institutional conditions.

Security Zone Classification

Justice facilities divide into distinct security zones, each requiring specific ventilation approaches based on occupancy type, security level, and operational requirements.

Primary Security Zone Types

Zone TypeSecurity LevelPressure RelationshipAir Changes/HourRecirculation
Maximum Security CellsHighNegative to corridor12-15 ACHLimited
General Population HousingMediumNegative to corridor10-12 ACHPermitted
Intake/BookingHighNegative to adjacent15-20 ACHNot permitted
Visiting AreasMediumNeutral to corridor10-12 ACHPermitted
Control RoomsCriticalPositive to all areas6-8 ACHPermitted
Sally PortsHighNegative to both sides20-30 ACHNot permitted
Medical/IsolationHighNegative isolation12-15 ACHNot permitted
AdministrativeLowPositive to secure areas4-6 ACHPermitted
graph TB
    subgraph "Security Zone Pressure Hierarchy"
        A[Control Room<br/>+0.10 in. wg]
        B[Administrative Corridor<br/>+0.05 in. wg]
        C[General Housing Corridor<br/>Reference 0.00 in. wg]
        D[Housing Units<br/>-0.02 in. wg]
        E[Sally Port<br/>-0.05 in. wg]
        F[Intake/Booking<br/>-0.08 in. wg]
        G[Isolation Cells<br/>-0.10 in. wg]

        A -->|Airflow| B
        B -->|Airflow| C
        C -->|Airflow| D
        C -->|Airflow| E
        E -->|Airflow| F
        D -->|Airflow| G
    end

    style A fill:#90EE90
    style B fill:#98FB98
    style C fill:#FFFFE0
    style D fill:#FFB6C1
    style E fill:#FFA07A
    style F fill:#FF6347
    style G fill:#DC143C

Ventilation Rate Calculations

Security area ventilation rates depend on occupancy density, contaminant load, and operational requirements. The required outdoor air follows ASHRAE Standard 62.1 with correctional facility modifications.

Outdoor Air Requirement

$$V_{oa} = R_p \times P + R_a \times A_z$$

Where:

  • $V_{oa}$ = outdoor air flow rate (cfm)
  • $R_p$ = people outdoor air rate (cfm/person)
  • $P$ = zone population (persons)
  • $R_a$ = area outdoor air rate (cfm/ft²)
  • $A_z$ = zone floor area (ft²)

For correctional housing:

  • $R_p$ = 5-10 cfm/person (minimum)
  • $R_a$ = 0.06 cfm/ft²

Air Change Method

$$ACH = \frac{Q \times 60}{V}$$

Where:

  • $ACH$ = air changes per hour
  • $Q$ = airflow rate (cfm)
  • $V$ = room volume (ft³)

Minimum ACH requirements:

$$Q_{min} = \frac{ACH_{required} \times V}{60}$$

Pressure Differential Control

Pressure relationships between zones maintain contamination control and security integrity.

$$\Delta P = \frac{Q_{net}^2 \times \rho}{2 \times C_d^2 \times A^2}$$

Where:

  • $\Delta P$ = pressure differential (in. wg)
  • $Q_{net}$ = net airflow through opening (cfm)
  • $\rho$ = air density (lb/ft³)
  • $C_d$ = discharge coefficient (typically 0.6-0.7)
  • $A$ = opening area (ft²)

Target pressure differentials:

  • Critical boundaries: 0.05-0.10 in. wg
  • Standard boundaries: 0.02-0.05 in. wg
flowchart LR
    subgraph "Pressure Control Strategy"
        A[Supply Air<br/>Measurement] --> B{Pressure<br/>Controller}
        C[Exhaust Air<br/>Measurement] --> B
        D[Differential<br/>Pressure Sensor] --> B
        B --> E[Supply<br/>Damper Control]
        B --> F[Exhaust<br/>Damper Control]
        E --> G[Maintain Target<br/>Differential]
        F --> G
    end

Sally Port Ventilation

Sally ports serve as secure transition zones between security levels, requiring specialized ventilation to prevent air transfer between zones during door operations.

Design Requirements

  1. Minimum 20-30 ACH when unoccupied
  2. 100% exhaust with no recirculation
  3. Negative pressure relative to both adjacent zones
  4. Interlocked operation with door controls
  5. Purge cycle between door operations

Purge Cycle Calculation

$$t_{purge} = \frac{3 \times V}{Q}$$

Where:

  • $t_{purge}$ = purge time (minutes)
  • $V$ = sally port volume (ft³)
  • $Q$ = exhaust airflow (cfm)
  • Factor of 3 represents three complete air changes

Typical purge time: 1-2 minutes minimum

Integration with Security Systems

HVAC systems in security areas integrate with facility security infrastructure to support operational requirements and emergency response.

Key Integration Points

Door Interlock Systems

  • Ventilation mode changes with door status
  • Purge cycles before door operation
  • Alarm conditions for ventilation failure

Fire Alarm Systems

  • Smoke control mode activation
  • Automatic damper positioning
  • Pressurization sequence control

Security Management Systems

  • Zone status monitoring
  • Pressure alarm reporting
  • Override capability for emergencies

Access Control Systems

  • Coordinated door/ventilation operation
  • Delayed egress coordination
  • Emergency release integration
sequenceDiagram
    participant Door as Sally Port Door
    participant HVAC as HVAC Controller
    participant Security as Security System
    participant BMS as Building Management

    Security->>Door: Request Door Open
    Door->>HVAC: Door Request Signal
    HVAC->>HVAC: Check Purge Status
    alt Purge Complete
        HVAC->>Security: Permit Door Open
        Security->>Door: Unlock Door
        Door->>HVAC: Door Open Signal
        HVAC->>HVAC: Increase Ventilation
    else Purge Incomplete
        HVAC->>Security: Delay Door Open
        HVAC->>HVAC: Complete Purge Cycle
        HVAC->>Security: Permit Door Open
    end
    HVAC->>BMS: Log Event

Control Room Pressurization

Control rooms require positive pressurization to protect occupants from potential airborne threats and maintain equipment reliability.

Design Criteria

  • Positive pressure: +0.05 to +0.10 in. wg relative to all adjacent areas
  • Filtration: MERV 13 minimum, MERV 14 preferred
  • Redundancy: Dual supply fans with automatic changeover
  • Sealing: Room construction to maintain pressure under normal infiltration

Supply air calculation with infiltration:

$$Q_{supply} = Q_{ventilation} + Q_{pressurization} + Q_{infiltration}$$

Where pressurization flow:

$$Q_{pressurization} = \frac{A \times C_d \times \sqrt{2 \times \Delta P \times \rho}}{0.075}$$

Odor and Contaminant Control

Security areas generate unique contaminant loads requiring dedicated exhaust and filtration strategies.

Exhaust Priorities

  1. Dedicated exhaust from toilets and showers
  2. No recirculation from high-contamination areas
  3. Separate exhaust systems for different security zones
  4. Chemical/biological filtration where required

Minimum Exhaust Rates

  • Toilet rooms: 50 cfm per fixture
  • Shower areas: 2 cfm/ft² or 50 cfm minimum
  • General cells: 50% of supply air minimum
  • Booking areas: 100% outdoor air, 100% exhaust

Standards and References

ASHRAE Standards:

  • ASHRAE 62.1: Ventilation for Acceptable Indoor Air Quality (Correctional Facilities section)
  • ASHRAE 170: Ventilation of Health Care Facilities (for medical areas)

Correctional Standards:

  • ACA Standards for Adult Correctional Institutions (environmental conditions)
  • National Institute of Corrections design guidelines
  • State-specific correctional facility standards

Related Codes:

  • International Mechanical Code (IMC) Chapter 4
  • NFPA 90A: Installation of Air-Conditioning and Ventilating Systems
  • Local amendments for justice facilities

Commissioning Considerations

Security area ventilation requires thorough commissioning to verify proper operation under all operational modes.

Critical Verification Points

  • Pressure differential verification under all door positions
  • Purge cycle timing verification
  • Interlock functionality testing
  • Alarm point verification
  • Emergency mode operation
  • Redundant system changeover
  • Balancing with security operations staff present

All testing must occur with security personnel coordination to prevent operational disruptions and maintain facility security during commissioning activities.

Sections

Holding Cell HVAC: Ventilation & Odor Control

Technical guide to holding cell ventilation systems, air change rates, security grilles, toilet exhaust, and odor control for short-term detention facilities.

Sally Port HVAC: Pressure Control & Vehicle Exhaust

Engineering guide to sally port HVAC systems in correctional facilities: pressure relationships, vehicle exhaust removal, interlocked ventilation, and security integration.

Booking Area HVAC Systems in Justice Facilities

Engineering guide for booking area ventilation design in correctional facilities, covering variable occupancy loads, odor control strategies, and security ventilation.

Isolation Rooms in Correctional Facilities

Technical guidance for designing HVAC systems in justice facility isolation rooms including negative pressure requirements, ACH rates, and infection control per ASHRAE 170.