Ventilation Security Areas
Ventilation in Security Areas
Security area ventilation in justice facilities requires precise control of airflow patterns, pressure relationships, and air quality while maintaining operational security. The HVAC system must prevent contamination migration, control odor transfer, support security functions, and operate reliably under institutional conditions.
Security Zone Classification
Justice facilities divide into distinct security zones, each requiring specific ventilation approaches based on occupancy type, security level, and operational requirements.
Primary Security Zone Types
| Zone Type | Security Level | Pressure Relationship | Air Changes/Hour | Recirculation |
|---|---|---|---|---|
| Maximum Security Cells | High | Negative to corridor | 12-15 ACH | Limited |
| General Population Housing | Medium | Negative to corridor | 10-12 ACH | Permitted |
| Intake/Booking | High | Negative to adjacent | 15-20 ACH | Not permitted |
| Visiting Areas | Medium | Neutral to corridor | 10-12 ACH | Permitted |
| Control Rooms | Critical | Positive to all areas | 6-8 ACH | Permitted |
| Sally Ports | High | Negative to both sides | 20-30 ACH | Not permitted |
| Medical/Isolation | High | Negative isolation | 12-15 ACH | Not permitted |
| Administrative | Low | Positive to secure areas | 4-6 ACH | Permitted |
graph TB
subgraph "Security Zone Pressure Hierarchy"
A[Control Room<br/>+0.10 in. wg]
B[Administrative Corridor<br/>+0.05 in. wg]
C[General Housing Corridor<br/>Reference 0.00 in. wg]
D[Housing Units<br/>-0.02 in. wg]
E[Sally Port<br/>-0.05 in. wg]
F[Intake/Booking<br/>-0.08 in. wg]
G[Isolation Cells<br/>-0.10 in. wg]
A -->|Airflow| B
B -->|Airflow| C
C -->|Airflow| D
C -->|Airflow| E
E -->|Airflow| F
D -->|Airflow| G
end
style A fill:#90EE90
style B fill:#98FB98
style C fill:#FFFFE0
style D fill:#FFB6C1
style E fill:#FFA07A
style F fill:#FF6347
style G fill:#DC143C
Ventilation Rate Calculations
Security area ventilation rates depend on occupancy density, contaminant load, and operational requirements. The required outdoor air follows ASHRAE Standard 62.1 with correctional facility modifications.
Outdoor Air Requirement
$$V_{oa} = R_p \times P + R_a \times A_z$$
Where:
- $V_{oa}$ = outdoor air flow rate (cfm)
- $R_p$ = people outdoor air rate (cfm/person)
- $P$ = zone population (persons)
- $R_a$ = area outdoor air rate (cfm/ft²)
- $A_z$ = zone floor area (ft²)
For correctional housing:
- $R_p$ = 5-10 cfm/person (minimum)
- $R_a$ = 0.06 cfm/ft²
Air Change Method
$$ACH = \frac{Q \times 60}{V}$$
Where:
- $ACH$ = air changes per hour
- $Q$ = airflow rate (cfm)
- $V$ = room volume (ft³)
Minimum ACH requirements:
$$Q_{min} = \frac{ACH_{required} \times V}{60}$$
Pressure Differential Control
Pressure relationships between zones maintain contamination control and security integrity.
$$\Delta P = \frac{Q_{net}^2 \times \rho}{2 \times C_d^2 \times A^2}$$
Where:
- $\Delta P$ = pressure differential (in. wg)
- $Q_{net}$ = net airflow through opening (cfm)
- $\rho$ = air density (lb/ft³)
- $C_d$ = discharge coefficient (typically 0.6-0.7)
- $A$ = opening area (ft²)
Target pressure differentials:
- Critical boundaries: 0.05-0.10 in. wg
- Standard boundaries: 0.02-0.05 in. wg
flowchart LR
subgraph "Pressure Control Strategy"
A[Supply Air<br/>Measurement] --> B{Pressure<br/>Controller}
C[Exhaust Air<br/>Measurement] --> B
D[Differential<br/>Pressure Sensor] --> B
B --> E[Supply<br/>Damper Control]
B --> F[Exhaust<br/>Damper Control]
E --> G[Maintain Target<br/>Differential]
F --> G
end
Sally Port Ventilation
Sally ports serve as secure transition zones between security levels, requiring specialized ventilation to prevent air transfer between zones during door operations.
Design Requirements
- Minimum 20-30 ACH when unoccupied
- 100% exhaust with no recirculation
- Negative pressure relative to both adjacent zones
- Interlocked operation with door controls
- Purge cycle between door operations
Purge Cycle Calculation
$$t_{purge} = \frac{3 \times V}{Q}$$
Where:
- $t_{purge}$ = purge time (minutes)
- $V$ = sally port volume (ft³)
- $Q$ = exhaust airflow (cfm)
- Factor of 3 represents three complete air changes
Typical purge time: 1-2 minutes minimum
Integration with Security Systems
HVAC systems in security areas integrate with facility security infrastructure to support operational requirements and emergency response.
Key Integration Points
Door Interlock Systems
- Ventilation mode changes with door status
- Purge cycles before door operation
- Alarm conditions for ventilation failure
Fire Alarm Systems
- Smoke control mode activation
- Automatic damper positioning
- Pressurization sequence control
Security Management Systems
- Zone status monitoring
- Pressure alarm reporting
- Override capability for emergencies
Access Control Systems
- Coordinated door/ventilation operation
- Delayed egress coordination
- Emergency release integration
sequenceDiagram
participant Door as Sally Port Door
participant HVAC as HVAC Controller
participant Security as Security System
participant BMS as Building Management
Security->>Door: Request Door Open
Door->>HVAC: Door Request Signal
HVAC->>HVAC: Check Purge Status
alt Purge Complete
HVAC->>Security: Permit Door Open
Security->>Door: Unlock Door
Door->>HVAC: Door Open Signal
HVAC->>HVAC: Increase Ventilation
else Purge Incomplete
HVAC->>Security: Delay Door Open
HVAC->>HVAC: Complete Purge Cycle
HVAC->>Security: Permit Door Open
end
HVAC->>BMS: Log Event
Control Room Pressurization
Control rooms require positive pressurization to protect occupants from potential airborne threats and maintain equipment reliability.
Design Criteria
- Positive pressure: +0.05 to +0.10 in. wg relative to all adjacent areas
- Filtration: MERV 13 minimum, MERV 14 preferred
- Redundancy: Dual supply fans with automatic changeover
- Sealing: Room construction to maintain pressure under normal infiltration
Supply air calculation with infiltration:
$$Q_{supply} = Q_{ventilation} + Q_{pressurization} + Q_{infiltration}$$
Where pressurization flow:
$$Q_{pressurization} = \frac{A \times C_d \times \sqrt{2 \times \Delta P \times \rho}}{0.075}$$
Odor and Contaminant Control
Security areas generate unique contaminant loads requiring dedicated exhaust and filtration strategies.
Exhaust Priorities
- Dedicated exhaust from toilets and showers
- No recirculation from high-contamination areas
- Separate exhaust systems for different security zones
- Chemical/biological filtration where required
Minimum Exhaust Rates
- Toilet rooms: 50 cfm per fixture
- Shower areas: 2 cfm/ft² or 50 cfm minimum
- General cells: 50% of supply air minimum
- Booking areas: 100% outdoor air, 100% exhaust
Standards and References
ASHRAE Standards:
- ASHRAE 62.1: Ventilation for Acceptable Indoor Air Quality (Correctional Facilities section)
- ASHRAE 170: Ventilation of Health Care Facilities (for medical areas)
Correctional Standards:
- ACA Standards for Adult Correctional Institutions (environmental conditions)
- National Institute of Corrections design guidelines
- State-specific correctional facility standards
Related Codes:
- International Mechanical Code (IMC) Chapter 4
- NFPA 90A: Installation of Air-Conditioning and Ventilating Systems
- Local amendments for justice facilities
Commissioning Considerations
Security area ventilation requires thorough commissioning to verify proper operation under all operational modes.
Critical Verification Points
- Pressure differential verification under all door positions
- Purge cycle timing verification
- Interlock functionality testing
- Alarm point verification
- Emergency mode operation
- Redundant system changeover
- Balancing with security operations staff present
All testing must occur with security personnel coordination to prevent operational disruptions and maintain facility security during commissioning activities.
Sections
Holding Cell HVAC: Ventilation & Odor Control
Technical guide to holding cell ventilation systems, air change rates, security grilles, toilet exhaust, and odor control for short-term detention facilities.
Sally Port HVAC: Pressure Control & Vehicle Exhaust
Engineering guide to sally port HVAC systems in correctional facilities: pressure relationships, vehicle exhaust removal, interlocked ventilation, and security integration.
Booking Area HVAC Systems in Justice Facilities
Engineering guide for booking area ventilation design in correctional facilities, covering variable occupancy loads, odor control strategies, and security ventilation.
Isolation Rooms in Correctional Facilities
Technical guidance for designing HVAC systems in justice facility isolation rooms including negative pressure requirements, ACH rates, and infection control per ASHRAE 170.