Duct Losses in Industrial Exhaust Systems

Pressure losses in industrial exhaust ductwork consume fan energy and determine the required static pressure capability of the ventilation system. These losses arise from two distinct mechanisms: friction between the air stream and duct walls, and turbulent dissipation in fittings such as elbows, transitions, and branch entries.

Physical Principles of Duct Losses

Air flowing through a duct experiences resistance due to viscous shear at the boundary layer and form drag from flow separation. The total pressure loss represents irreversible conversion of mechanical energy to thermal energy through turbulent dissipation.

For fully developed turbulent flow in circular ducts, the Darcy-Weisbach equation governs friction losses:

$$\Delta P_f = f \cdot \frac{L}{D} \cdot \frac{\rho V^2}{2} = f \cdot \frac{L}{D} \cdot VP$$

Where:

  • $\Delta P_f$ = friction pressure loss (Pa or in. w.g.)
  • $f$ = Darcy friction factor (dimensionless)
  • $L$ = duct length (m or ft)
  • $D$ = duct diameter (m or ft)
  • $\rho$ = air density (kg/m³ or lb/ft³)
  • $V$ = air velocity (m/s or ft/min)
  • $VP$ = velocity pressure = $\frac{\rho V^2}{2}$ (Pa or in. w.g.)

The friction factor depends on Reynolds number and relative roughness. For typical industrial exhaust ductwork (galvanized steel, $\epsilon/D \approx 0.0005$), the friction factor ranges from 0.015 to 0.025 for Reynolds numbers between 10,000 and 100,000.

graph LR
    A[Fan Discharge] -->|Straight Duct| B[Friction Loss ΔPf]
    B -->|Elbow| C[Fitting Loss ΔPfit]
    C -->|Transition| D[Fitting Loss ΔPfit]
    D -->|Branch Entry| E[Fitting Loss ΔPfit]
    E -->|Straight Duct| F[Friction Loss ΔPf]
    F -->|Hood Entry| G[Total Pressure Loss]

    style B fill:#e1f5ff
    style C fill:#fff4e1
    style D fill:#fff4e1
    style E fill:#fff4e1
    style F fill:#e1f5ff

    subgraph "Pressure Loss Components"
    B
    C
    D
    E
    F
    end

Fitting Losses

Fittings generate localized turbulence and flow separation, resulting in pressure losses expressed as multiples of velocity pressure:

$$\Delta P_{fit} = C_L \cdot VP$$

Where $C_L$ is the loss coefficient (dimensionless), determined experimentally for each fitting geometry.

Loss Coefficients by Fitting Type

Fitting TypeConfigurationLoss Coefficient (CL)Notes
Elbows90° smooth radius (r/D = 1.5)0.22Minimum loss configuration
90° smooth radius (r/D = 1.0)0.35Standard industrial elbow
90° mitered, no vanes1.20High loss, avoid if possible
90° mitered, with turning vanes0.40Vanes reduce separation
45° elbow (r/D = 1.5)0.15Lower angle reduces loss
TransitionsGradual expansion (10° included angle)0.18Optimal expansion rate
Gradual expansion (20° included angle)0.40Increased separation
Abrupt expansion1.00Complete velocity head loss
Gradual contraction (any angle)0.05Minimal loss in contraction
Branch Entries45° entry, tapered0.15Best practice design
90° straight entry0.50Moderate loss
Straight-through tee0.90Significant separation
Hood EntriesBell mouth entry0.05Smooth acceleration
Plain opening0.50Standard hood entry
Inward flange0.93Poor entry geometry

Source: ACGIH Industrial Ventilation Manual, 30th Edition; ASHRAE Fundamentals Handbook

Calculation Methods

ASHRAE Method

ASHRAE provides friction loss charts (Duct Friction Chart, Chapter 21) based on the Colebrook equation for commercial duct systems. For round galvanized ducts at standard air density (0.075 lb/ft³), the chart relates friction loss per 100 ft to duct diameter and airflow rate.

For rectangular ducts, convert to equivalent circular diameter:

$$D_e = 1.30 \cdot \frac{(a \cdot b)^{0.625}}{(a + b)^{0.25}}$$

Where $a$ and $b$ are the rectangular duct dimensions.

ACGIH Method

The ACGIH Industrial Ventilation Manual emphasizes velocity pressure losses for industrial exhaust systems containing particulate. The total system loss calculation proceeds:

  1. Calculate velocity pressure at each duct segment: $VP = \frac{V^2}{4005}$ (in. w.g., V in ft/min)
  2. Determine friction loss: $\Delta P_f = f \cdot (L/D) \cdot VP$
  3. Sum fitting losses: $\Sigma \Delta P_{fit} = \Sigma (C_L \cdot VP)$
  4. Total static pressure requirement: $SP_{total} = \Sigma \Delta P_f + \Sigma \Delta P_{fit} + SP_{hood}$

Design Considerations

Velocity Selection: Industrial exhaust systems require minimum transport velocities to prevent particulate settling. Typical ranges:

  • Vapor, gases: 1000-2000 ft/min
  • Light dust: 2000-3000 ft/min
  • Heavy dust, metal chips: 3500-4500 ft/min

Higher velocities increase pressure losses (proportional to $V^2$), creating tension between transport requirements and energy consumption.

Duct Roughness: Particulate buildup increases effective roughness and friction factor over time. Design should include cleanout provisions and anticipate 10-20% pressure loss increase during service intervals.

Balancing: Branch systems require careful fitting selection to achieve design airflows without damper losses. Blast gate dampers introduce high losses ($C_L$ = 0.5-2.0 depending on position) and should be sized for minimal restriction in the open position.

Pressure Loss Budget

For efficient system design, allocate the total fan static pressure capability:

  • Hood entry loss: 10-15%
  • Duct friction losses: 40-50%
  • Fitting losses: 25-35%
  • Filter or air cleaner: 10-25%
  • Reserve for system degradation: 10-15%

This allocation ensures adequate capture velocity at hoods while limiting fan energy consumption to practical levels for continuous industrial operation.