Latent Loads from Occupancy in High-Density Spaces
Occupant Latent Heat Generation
Human occupants generate latent heat through two primary physiological mechanisms: perspiration (evaporation from skin) and respiration (moisture in exhaled breath). The latent heat component represents 20-50% of total metabolic heat release depending on activity level and environmental conditions.
The total latent heat gain from occupants is calculated as:
$$Q_{lat} = N \cdot q_{lat} \cdot CLF$$
Where:
- $Q_{lat}$ = total latent heat gain (Btu/hr or W)
- $N$ = number of occupants
- $q_{lat}$ = latent heat gain per person (Btu/hr)
- $CLF$ = cooling load factor (typically 1.0 for latent loads)
Moisture Generation Mechanism
The moisture generation rate from occupants is expressed as:
$$\dot{m}{moisture} = N \cdot \frac{q{lat}}{h_{fg}}$$
Where:
- $\dot{m}_{moisture}$ = moisture generation rate (lb/hr or kg/hr)
- $h_{fg}$ = latent heat of vaporization (1050 Btu/lb or 2440 kJ/kg at standard conditions)
This moisture addition increases the space humidity ratio:
$$\Delta W = \frac{\dot{m}{moisture}}{\dot{m}{air}} = \frac{N \cdot q_{lat}}{h_{fg} \cdot \rho_{air} \cdot \dot{V}}$$
Where:
- $\Delta W$ = humidity ratio increase (lb moisture/lb dry air)
- $\dot{V}$ = ventilation airflow rate (CFM or m³/s)
- $\rho_{air}$ = air density (0.075 lb/ft³ or 1.2 kg/m³)
Latent Load by Activity Level
ASHRAE Fundamentals provides standardized latent heat generation rates based on activity intensity:
| Activity Level | Sensible Heat (Btu/hr) | Latent Heat (Btu/hr) | Total Heat (Btu/hr) | SHR |
|---|---|---|---|---|
| Seated at rest | 245 | 105 | 350 | 0.70 |
| Seated, light work | 255 | 145 | 400 | 0.64 |
| Standing, light work | 250 | 200 | 450 | 0.56 |
| Walking 2 mph | 250 | 250 | 500 | 0.50 |
| Light bench work | 275 | 275 | 550 | 0.50 |
| Moderate dancing | 305 | 545 | 850 | 0.36 |
| Heavy work/athletics | 345 | 705 | 1050 | 0.33 |
Note: Values assume 75°F space temperature. Latent fraction increases as space temperature rises.
Sensible Heat Ratio Impact
The sensible heat ratio (SHR) for occupied spaces is calculated as:
$$SHR = \frac{Q_{sensible}}{Q_{sensible} + Q_{latent}}$$
High-density occupancy drives SHR down to 0.60-0.75, significantly below the typical cooling coil SHR of 0.75-0.80. This mismatch creates humidity control challenges requiring specialized equipment selection.
graph TD
A[Occupant Metabolism] --> B[Sensible Heat<br/>Convection + Radiation]
A --> C[Latent Heat<br/>Perspiration + Respiration]
B --> D[Temperature Rise]
C --> E[Humidity Ratio Increase]
D --> F{Space Conditions}
E --> F
F --> G[Required SHR = 0.60-0.75]
G --> H[Cooling Coil Selection]
H --> I[Adequate Latent Capacity]
style C fill:#e6f3ff
style E fill:#e6f3ff
style G fill:#fff4e6
style I fill:#e6ffe6
Dehumidification Requirements
graph LR
A[Return Air<br/>78°F, 65% RH] --> B[Cooling Coil]
B --> C[Supply Air<br/>55°F, 90% RH]
C --> D[Duct Heat Gain]
D --> E[Diffuser Discharge<br/>58°F, 85% RH]
E --> F[Space Mixing]
F --> A
G[Occupant Moisture<br/>0.5 lb/hr per person] --> F
H[Ventilation Air<br/>95°F, 55% RH] --> B
style B fill:#cce6ff
style G fill:#ffe6cc
Coil Performance Requirements
To handle high latent loads, the cooling coil must achieve sufficient moisture removal:
$$\dot{m}{removed} = \rho{air} \cdot \dot{V} \cdot (W_{entering} - W_{leaving})$$
Where:
- $W_{entering}$ = entering air humidity ratio
- $W_{leaving}$ = leaving air humidity ratio
The apparatus dew point (ADP) must be selected to provide adequate latent capacity:
$$ADP_{required} = T_{space} - \frac{Q_{total}}{1.08 \cdot \dot{V} \cdot BF}$$
Where $BF$ is the coil bypass factor (typically 0.05-0.15 for dehumidification applications).
Moisture Load Distribution
High-occupancy spaces experience time-varying latent loads:
| Time Period | Occupancy Factor | Latent Load Factor | Effective SHR |
|---|---|---|---|
| Pre-occupancy | 0% | 0% | 0.95 |
| Partial occupancy | 50% | 50% | 0.82 |
| Full occupancy | 100% | 100% | 0.68 |
| Post-occupancy | 10% | 5% | 0.90 |
Latent load diversity accounts for simultaneous occupancy patterns. Design diversity factors range from 0.75-0.95 depending on space function.
Design Considerations
Critical parameters for high-latent-load applications:
- Supply air temperature: Lower supply air temperatures (52-55°F) improve dehumidification but require careful condensation control
- Coil rows: 6-8 row coils with face velocities below 500 FPM maximize moisture removal
- Reheat strategies: Subcool-and-reheat approaches maintain humidity control during partial load
- Dedicated outdoor air systems (DOAS): Separately condition ventilation air to reduce space latent load
- Desiccant dehumidification: Supplement mechanical cooling in extreme latent load conditions (SHR < 0.65)
Relative humidity control challenges:
- Occupant comfort range: 30-60% RH per ASHRAE Standard 55
- Mold prevention: maintain below 60% RH per ASHRAE Standard 62.1
- Condensation avoidance: surface temperatures must exceed dew point
- Part-load operation: reduced sensible loads increase space RH if latent capacity is insufficient
System Selection Criteria
Select HVAC equipment based on space SHR requirements:
$$\frac{Q_{lat,space}}{Q_{sen,space}} \leq \frac{Q_{lat,coil}}{Q_{sen,coil}}$$
When space latent load fraction exceeds coil latent capacity fraction, supplemental dehumidification is required. This commonly occurs in theaters, auditoriums, gymnasiums, and assembly spaces where occupant density exceeds 15 ft²/person and activity levels are moderate to high.
Reference: ASHRAE Handbook—Fundamentals, Chapter 18: Nonresidential Cooling and Heating Load Calculations (metabolic heat generation rates and occupancy load profiles).