Setback Recovery in Assembly Spaces
Overview
Setback recovery in assembly spaces presents unique challenges due to high thermal mass, large volume-to-occupancy ratios, and intermittent use patterns. Proper recovery strategy design ensures occupant comfort at event start while minimizing energy consumption during unoccupied periods.
Recovery Time Calculation
The fundamental recovery time equation accounts for building thermal capacitance and available heating capacity:
$$t_{recovery} = \frac{C_{building} \cdot (T_{setpoint} - T_{setback})}{Q_{available} - Q_{losses}}$$
Where:
- $t_{recovery}$ = recovery time (hours)
- $C_{building}$ = effective building thermal capacitance (Btu/°F)
- $T_{setpoint}$ = occupied setpoint temperature (°F)
- $T_{setback}$ = setback temperature (°F)
- $Q_{available}$ = available heating capacity (Btu/hr)
- $Q_{losses}$ = envelope heat losses during recovery (Btu/hr)
Effective Thermal Capacitance
For assembly spaces, calculate effective thermal capacitance including structural mass:
$$C_{building} = \sum (m_i \cdot c_{p,i} \cdot f_i)$$
Where:
- $m_i$ = mass of component i (lb)
- $c_{p,i}$ = specific heat of material i (Btu/lb·°F)
- $f_i$ = engagement factor (0.3-0.8 for typical recovery periods)
Material Engagement Factors:
| Material | 2-Hour Recovery | 4-Hour Recovery | 8-Hour Recovery |
|---|---|---|---|
| Concrete slab | 0.35 | 0.50 | 0.70 |
| Concrete block | 0.40 | 0.55 | 0.75 |
| Gypsum board | 0.80 | 0.90 | 0.95 |
| Steel structure | 0.60 | 0.75 | 0.85 |
Recovery Curve Characteristics
graph TD
A[Recovery Initiation] --> B{Outdoor Temperature}
B -->|Below 32°F| C[Full Heating + Preheat AHUs]
B -->|32-50°F| D[Staged Heating]
B -->|Above 50°F| E[Minimum Heating]
C --> F[Monitor Temperature Rise Rate]
D --> F
E --> F
F --> G{Temperature Rise Rate}
G -->|Below Target| H[Increase Heating Output]
G -->|At Target| I[Maintain Current Output]
G -->|Above Target| J[Reduce Heating Output]
H --> K[Approach Setpoint]
I --> K
J --> K
K --> L[Occupied Mode]
Temperature Rise Profile
graph LR
subgraph "Recovery Phase Analysis"
A[0-30 min:<br/>Rapid Rise<br/>3-5°F/hr] --> B[30-90 min:<br/>Moderate Rise<br/>2-3°F/hr]
B --> C[90-120 min:<br/>Slow Rise<br/>1-2°F/hr]
C --> D[Setpoint<br/>Achieved]
end
Recovery Time Targets
ASHRAE 90.1 does not mandate specific recovery times but requires optimal start controls for buildings >10,000 ft². Typical assembly space targets:
| Space Type | Setback ΔT | Target Recovery | Equipment Sizing Factor |
|---|---|---|---|
| Theater/auditorium | 10-15°F | 2-3 hours | 1.5-2.0× design load |
| Arena/stadium | 8-12°F | 3-4 hours | 1.3-1.5× design load |
| Convention center | 10-12°F | 2-3 hours | 1.4-1.7× design load |
| Religious facility | 12-18°F | 2-4 hours | 1.6-2.2× design load |
Optimal Start Control Strategy
Optimal start algorithms adjust equipment start time based on current conditions and learned building response.
Basic Optimal Start Algorithm
$$t_{start} = t_{occupancy} - \left(K_1 \cdot \Delta T + K_2 \cdot (T_{outdoor} - T_{ref}) + K_3\right)$$
Where:
- $t_{start}$ = equipment start time
- $t_{occupancy}$ = scheduled occupancy time
- $\Delta T$ = $(T_{setpoint} - T_{current})$
- $K_1$ = temperature difference coefficient (typically 8-15 min/°F)
- $K_2$ = outdoor temperature coefficient (typically 1-3 min/°F)
- $K_3$ = base time offset (typically 15-30 min)
- $T_{ref}$ = reference outdoor temperature (typically 40-50°F)
Adaptive Learning
Modern controls employ adaptive algorithms that refine coefficients based on actual performance:
$$K_{1,new} = K_{1,old} + \alpha \cdot \frac{(t_{actual} - t_{predicted})}{\Delta T}$$
Where $\alpha$ is the learning rate (typically 0.1-0.3).
Thermal Mass Effects
High thermal mass in assembly spaces significantly impacts recovery characteristics.
Thermal Mass Benefits:
- Reduces temperature swing during unoccupied periods
- Provides thermal energy storage during recovery
- Dampens outdoor temperature fluctuations
Thermal Mass Challenges:
- Extends recovery time requirements
- Increases equipment sizing factor
- Complicates control algorithm tuning
Mass-to-Volume Ratio Impact
$$R_{mv} = \frac{\sum (m_i \cdot c_{p,i})}{V \cdot \rho_{air} \cdot c_{p,air}}$$
Where:
- $R_{mv}$ = mass-to-volume ratio (dimensionless)
- $V$ = conditioned space volume (ft³)
- $\rho_{air}$ = air density (0.075 lb/ft³)
- $c_{p,air}$ = air specific heat (0.24 Btu/lb·°F)
Typical Assembly Space Values:
| Construction Type | $R_{mv}$ | Recovery Multiplier |
|---|---|---|
| Light frame | 1-3 | 1.0-1.2 |
| Heavy frame | 3-6 | 1.2-1.5 |
| Concrete/masonry | 6-12 | 1.5-2.0 |
| Below-grade | 10-20 | 2.0-2.5 |
Recovery Enhancement Strategies
Outdoor Air Reset During Recovery
Minimize outdoor air to design minimum (ASHRAE 62.1 ventilation rates apply only during occupancy):
$$Q_{OA,recovery} = \max(0.15 \text{ cfm/ft}^2, 500 \text{ cfm})$$
This maintains slight building pressurization while minimizing heating load.
Economizer Lockout
Disable economizer operation during recovery to maximize heating coil capacity. Enable only when:
$$T_{space} \geq (T_{setpoint} - 2°F) \text{ AND } t \geq (t_{occupancy} - 30 \text{ min})$$
Staged Equipment Operation
Sequence heating equipment to optimize efficiency:
- Phase 1 (0-30% recovery): Activate all heating stages, 100% return air
- Phase 2 (30-70% recovery): Modulate to maintain target rise rate
- Phase 3 (70-100% recovery): Reduce to occupied mode, introduce ventilation air
Equipment Sizing for Recovery
Total heating capacity must accommodate both envelope losses and thermal mass recovery:
$$Q_{total} = Q_{design} + Q_{recovery}$$
Where:
$$Q_{recovery} = \frac{C_{building} \cdot \Delta T_{setback}}{t_{recovery,target}}$$
For assembly spaces with 2-3 hour recovery targets, this typically results in 1.4-2.0× design heating load capacity.
Economizer Contribution
When outdoor conditions permit, economizer operation can reduce mechanical cooling during shoulder seasons but provides no heating benefit. Do not credit economizer capacity toward recovery heating requirements.
Control Sequence Optimization
Recommended Recovery Sequence:
- Pre-start (t - 5 min): Enable fans, verify operation
- Initial recovery (t + 0 min): Full heating, minimum OA, economizer locked out
- Mid recovery (50% complete): Begin modulating heating output
- Late recovery (80% complete): Increase OA to design minimum
- Occupied transition (90% complete): Enable economizer, full occupied mode
- Occupied mode (100%): Normal control sequences active
Design Recommendations
Per ASHRAE 90.1-2019 Section 6.4.3.3.3: Buildings >10,000 ft² must employ automatic time clock control with optimum start capabilities. For assembly spaces specifically:
- Implement adaptive optimal start with minimum 30-day learning period
- Size heating equipment for 2-3 hour recovery from 10-15°F setback
- Monitor and trend recovery performance monthly
- Adjust setback depth based on unoccupied duration and outdoor temperature
- Consider separate setback strategies for conditioned vs. unconditioned periods
Verification Testing: Commission optimal start by testing at various outdoor temperatures and setback conditions to verify occupancy targets are met within ±2°F at scheduled time.
Performance Metrics
Track these key performance indicators to optimize recovery strategy:
- Percentage of occupancy periods meeting temperature target (target: >95%)
- Average recovery energy per degree-hour (Btu/°F·hr)
- Optimal start accuracy (target: ±15 minutes)
- Equipment runtime during recovery vs. occupied periods
- Seasonal recovery time trends
Reference: ASHRAE Handbook—HVAC Applications, Chapter 4 (Places of Assembly); ASHRAE Standard 90.1-2019; ASHRAE Guideline 36-2021