Outdoor Air Reset for Demand-Controlled Ventilation
Overview
Outdoor air (OA) reset represents an advanced control strategy that dynamically adjusts minimum ventilation rates based on actual occupancy demand while maintaining compliance with ASHRAE 62.1 ventilation requirements. This approach optimizes energy consumption by reducing unnecessary conditioning of outdoor air during periods of low occupancy while enabling economizer operation when outdoor conditions permit.
Reset Control Fundamentals
Occupancy-Based Reset Schedule
The minimum outdoor air setpoint adjusts proportionally to measured or inferred occupancy:
$$V_{oa,min} = V_{oa,design} \times \frac{N_{actual}}{N_{design}} + V_{oa,floor}$$
Where:
- $V_{oa,min}$ = minimum outdoor air flow rate (CFM)
- $V_{oa,design}$ = design outdoor air flow rate (CFM)
- $N_{actual}$ = actual measured occupancy (people)
- $N_{design}$ = design occupancy (people)
- $V_{oa,floor}$ = minimum floor ventilation rate (CFM)
CO₂-Based Reset Algorithm
For spaces without direct occupancy sensing, CO₂ concentration provides an indirect measure:
$$V_{oa,reset} = V_{oa,floor} + (V_{oa,design} - V_{oa,floor}) \times \frac{C_{space} - C_{ambient}}{C_{setpoint} - C_{ambient}}$$
Where:
- $C_{space}$ = space CO₂ concentration (ppm)
- $C_{ambient}$ = outdoor CO₂ concentration (typically 400 ppm)
- $C_{setpoint}$ = design CO₂ setpoint (typically 1000-1100 ppm)
Reset Schedule Implementation
Typical Reset Schedules by Application
| Application | Design OA (%) | Minimum Reset (%) | Reset Basis | Response Time |
|---|---|---|---|---|
| Assembly hall | 100 | 30 | CO₂ + schedule | 15-20 min |
| Classroom | 100 | 40 | CO₂ sensor | 10-15 min |
| Restaurant | 100 | 50 | CO₂ + time | 10-15 min |
| Gymnasium | 100 | 35 | CO₂ + schedule | 20-30 min |
| Theater | 100 | 25 | Occupancy count | 15-20 min |
| Conference room | 100 | 30 | CO₂ sensor | 8-12 min |
Control Sequence Logic
graph TD
A[Start: Calculate Required OA] --> B{Occupancy Sensor Available?}
B -->|Yes| C[Use Direct Occupancy Count]
B -->|No| D[Use CO₂-Based Inference]
C --> E[Calculate OA Reset Value]
D --> E
E --> F{OA Temp vs Space Temp}
F -->|OA < Space -5°F| G[Enable Economizer Mode]
F -->|OA > Space -5°F| H[Use Reset Minimum OA]
G --> I[Modulate to 100% OA if Cooling Required]
H --> J[Maintain Reset Minimum Position]
I --> K{Space Conditions Met?}
J --> K
K -->|No| L[Increase Mechanical Cooling]
K -->|Yes| M[Hold Current Position]
L --> M
M --> A
Economizer Integration
Dual-Path Control Strategy
OA reset systems must coordinate with economizer operation to maximize energy savings:
$$\text{OA}{damper} = \max(OA{reset}, OA_{economizer})$$
The outdoor air damper position responds to the greater of ventilation demand or economizer cooling demand.
Economizer Lockout Conditions
| Parameter | Enable Economizer | Disable Economizer |
|---|---|---|
| Dry-bulb temp | < 65°F | > 70°F |
| Enthalpy | < 28 BTU/lb | > 30 BTU/lb |
| Dew point | < 55°F | > 60°F |
| Differential temp | OA < RA - 5°F | OA > RA - 2°F |
Control Logic Architecture
Multi-Stage Reset Algorithm
flowchart LR
A[Occupancy/CO₂ Input] --> B[Calculate Ventilation Demand]
B --> C[Apply ASHRAE 62.1 Multiplier]
C --> D{Compare to Design}
D -->|Below Design| E[Calculate Reset Percentage]
D -->|At/Above Design| F[Use 100% Design OA]
E --> G[Apply Floor Limit]
G --> H{Check Economizer Eligibility}
F --> H
H -->|Eligible| I[Compare OA vs Cooling Demand]
H -->|Not Eligible| J[Command Reset OA Position]
I -->|Cooling Available| K[Command Economizer OA Position]
I -->|No Cooling Benefit| J
K --> L[Modulate to Space Conditions]
J --> L
Energy Optimization
Heating Season Benefits
During heating, OA reset reduces heating energy by conditioning less outdoor air:
$$Q_{saved} = \rho \times c_p \times V_{oa,reduced} \times (T_{space} - T_{oa}) \times 60$$
Where:
- $Q_{saved}$ = heating energy saved (BTU/hr)
- $\rho$ = air density (0.075 lb/ft³)
- $c_p$ = specific heat of air (0.24 BTU/lb·°F)
- $V_{oa,reduced}$ = outdoor air reduction from reset (CFM)
- $T_{space}$ = space temperature (°F)
- $T_{oa}$ = outdoor air temperature (°F)
Cooling Season Optimization
When outdoor conditions are unfavorable for economizer operation, reset minimizes cooling load:
$$Q_{cooling,saved} = \rho \times V_{oa,reduced} \times (h_{oa} - h_{space}) \times 60$$
Where $h$ represents enthalpy (BTU/lb).
ASHRAE 62.1 Compliance
Ventilation Rate Procedure
OA reset must maintain minimum ventilation rates per ASHRAE 62.1:
$$V_{oz} = R_p \times P_z + R_a \times A_z$$
Where:
- $V_{oz}$ = outdoor air flow rate required in zone (CFM)
- $R_p$ = people outdoor air rate (CFM/person)
- $P_z$ = zone population (people)
- $R_a$ = area outdoor air rate (CFM/ft²)
- $A_z$ = zone floor area (ft²)
The reset schedule must never reduce OA below this calculated minimum.
System Ventilation Efficiency
Multi-zone systems require the ventilation efficiency factor:
$$E_v = \frac{1 + X_s - Z_d}{1 + X_s}$$
Where:
- $E_v$ = system ventilation efficiency
- $X_s$ = uncorrected system outdoor air fraction
- $Z_d$ = zone outdoor air fraction (critical zone)
Implementation Best Practices
Sensor Placement:
- Position CO₂ sensors in breathing zone (4-6 ft above floor)
- Average multiple sensors in large spaces
- Locate away from air supply diffusers and OA intakes
- Calibrate sensors quarterly
Control Tuning:
- Set reset floor at 50-60% of design OA for most applications
- Use 10-15 minute averaging for CO₂-based reset
- Implement 5-10 minute delay before reducing OA
- Enable faster response when increasing OA (2-5 minutes)
Economizer Coordination:
- Program economizer to override reset when conditions favorable
- Maintain 10-15% minimum OA during economizer operation
- Monitor mixed air temperature to prevent coil freezing
- Disable economizer if OA dewpoint exceeds 60°F in humid climates
Performance Verification
Required Monitoring Points:
- Outdoor air damper position (%)
- Outdoor air flow rate (CFM)
- Mixed air temperature (°F)
- Space CO₂ concentration (ppm)
- Occupancy count or inference
- Economizer enable status
Energy Savings Validation:
$$\text{Savings} = \frac{E_{baseline} - E_{reset}}{E_{baseline}} \times 100%$$
Typical savings range from 15-35% of HVAC energy consumption, depending on climate, occupancy variability, and system configuration.
Key Engineering Considerations
Reset control effectiveness depends on accurate occupancy sensing or CO₂ measurement. Verify sensor accuracy before commissioning. Configure reset algorithms to comply with minimum ventilation requirements under all operating conditions. Coordinate with economizer controls to maximize free cooling opportunities while maintaining indoor air quality standards per ASHRAE 62.1 and local code requirements.
Design reset schedules based on actual occupancy patterns rather than theoretical maximums. Monitor system performance during the first year to optimize reset parameters and validate energy savings assumptions.