HVAC Systems Encyclopedia

A comprehensive encyclopedia of heating, ventilation, and air conditioning systems

Dormitory and Residence Hall HVAC Systems

Dormitory and Residence Hall HVAC Systems

Dormitory and residence hall HVAC systems must accommodate 24-hour residential occupancy with individual thermal comfort preferences, continuous bathroom exhaust requirements, and highly variable loads from unpredictable student behavior. Unlike classroom buildings with predictable schedules, residence halls experience peak cooling loads during evening hours (2100-2400), require year-round ventilation for odor control, and demand individual room-level temperature control to minimize complaints. ASHRAE 62.1 specifies minimum ventilation rates of 5 cfm per person plus 0.06 cfm/ft² for sleeping areas, with continuous bathroom exhaust at 25 cfm minimum per water closet and 50 cfm per bathtub/shower.

System Type Comparison

Packaged Terminal Air Conditioners (PTACs)

Configuration:

  • Self-contained wall-sleeve units (9,000-15,000 BTU/hr typical)
  • Direct outdoor air intake through wall penetration
  • Electric resistance or heat pump heating
  • Individual room thermostat control

Advantages:

  • Lowest first cost ($1,200-2,000 per unit installed)
  • Complete individual room control
  • Simple maintenance (replace entire unit)
  • No central equipment space required
  • Failure affects only one room

Disadvantages:

  • Outdoor air not filtered or conditioned before entering room
  • High operating cost (EER 9-11 typical, COP 2.5-3.5 heating)
  • Poor humidity control
  • Significant noise (45-55 dBA in occupied space)
  • Wall penetrations create envelope challenges
  • Short equipment life (10-12 years)

Operating costs (per 250 ft² room, annual):

$$C_{annual} = \frac{Q_{cool}}{EER \times 1000} \times h_{cool} \times c_e + \frac{Q_{heat}}{COP \times 3.413} \times h_{heat} \times c_e$$

For typical conditions (12,000 BTU/hr cooling, 1,000 hr/yr cooling, 1,500 hr/yr heating, $0.12/kWh):

  • Cooling: 1,200 kWh/yr = $144
  • Heating: 1,600 kWh/yr = $192
  • Total: $336/room/year

Four-Pipe Fan Coil Units

Configuration:

  • Separate chilled water and hot water piping to each room
  • 200-400 cfm fan coil with 3-speed control
  • Outdoor air ducted to unit or via separate ventilation system
  • Individual room thermostat with heating/cooling changeover

Advantages:

  • Quiet operation (NC 30-35 achievable)
  • Excellent individual control
  • High efficiency (central chiller/boiler, COP 4-6)
  • Filtered outdoor air
  • Humidity control possible
  • Longer equipment life (20-25 years)

Disadvantages:

  • Higher first cost ($3,500-5,000 per room including distribution)
  • Central plant required (chillers, boilers, pumps)
  • Piping penetrations through fire-rated assemblies require firestopping
  • Water leak risk in occupied spaces
  • Changeover lag during shoulder seasons

Operating costs (per room, annual):

  • Cooling: 700 kWh/yr = $84
  • Heating: 900 kWh/yr = $108
  • Pumping: 150 kWh/yr = $18
  • Total: $210/room/year

Annual savings vs PTAC: $126/room Payback on incremental cost: ($3,000 premium) / ($126 savings) = 23.8 years

Variable Refrigerant Flow (VRF)

Configuration:

  • Outdoor condensing units serving multiple indoor fan coils
  • Branch refrigerant piping to individual rooms (15-64 units per system)
  • Heat recovery capable (simultaneous heating/cooling)
  • Individual wireless or wired controllers

Advantages:

  • High efficiency (EER 14-18, COP 3.5-4.5)
  • Heat recovery between rooms reduces energy consumption
  • Zoned control without central plant
  • Minimal mechanical space requirements
  • Quiet indoor units (NC 25-30)

Disadvantages:

  • High first cost ($4,000-6,000 per room)
  • Complex controls and commissioning
  • Refrigerant leak concerns in occupied spaces
  • ASHRAE 15 compliance (refrigerant quantity limits)
  • Limited service technician availability
  • Outdoor unit noise concerns

Operating costs (per room, annual):

  • Combined heating/cooling: 950 kWh/yr = $114
  • Total: $114/room/year

Annual savings vs PTAC: $222/room Payback on incremental cost: ($4,500 premium) / ($222 savings) = 20.3 years

System Selection Matrix

CriterionPTAC4-Pipe Fan CoilVRF
First cost ($/room)$1,500$4,500$6,000
Operating cost ($/room/yr)$336$210$114
Life-cycle cost (20 yr, 5% discount)$8,678$7,120$7,422
Noise level45-55 dBA30-35 NC25-30 NC
Individual controlExcellentExcellentExcellent
Maintenance complexityLowMediumHigh
Suitable building size< 100 roomsAny> 50 rooms

Recommendation: Four-pipe fan coil systems provide optimal life-cycle cost for buildings > 100 rooms with central plant infrastructure. VRF systems work well for mid-size buildings (50-150 rooms) without space for central plant. PTACs remain appropriate only for low-budget projects or small buildings where operating cost is not prioritized.

Individual Room Control Requirements

Thermostat Specifications

Control authority per ASHRAE 62.1 Section 6.2.7.1:

  • Occupants must have control over thermal comfort in individual spaces
  • Minimum adjustable range: 68-76°F (20-24°C)
  • Maximum time to reach setpoint: 30 minutes
  • Deadband requirement: 3°F minimum between heating and cooling (energy code compliance)

Practical considerations:

  • Lockout ranges prevent excessive energy consumption (65-80°F typical)
  • Heat pump systems require deadband enforcement to prevent electric resistance backup
  • Wireless thermostats eliminate wiring but require battery maintenance
  • Communicating thermostats enable central monitoring and energy management

Ventilation Control

ASHRAE 62.1-2022 requirements for dormitory rooms:

$$V_{min} = R_p \times P_z + R_a \times A_z$$

Where:

  • $R_p$ = 5 cfm/person (Table 6-1, sleeping areas)
  • $R_a$ = 0.06 cfm/ft²
  • $P_z$ = Design occupancy (typically 2 persons per room)
  • $A_z$ = Room area (ft²)

Example calculation (250 ft² double room):

$$V_{min} = 5 \times 2 + 0.06 \times 250 = 10 + 15 = 25 \text{ cfm}$$

Implementation options:

  1. Constant volume outdoor air to each room via dedicated duct
  2. Transfer air from corridor (requires makeup air to corridor)
  3. PTAC outdoor air intake (unfiltered, unconditioned)
  4. Central DOAS with separate ventilation distribution

Corridor pressurization:

  • Maintain +0.02 to +0.05 in. w.c. relative to rooms
  • Prevents odor transfer between rooms
  • Supply air quantity = sum of room exhaust + exfiltration + room transfer air

Bathroom Exhaust Ventilation

Minimum Exhaust Rates

ASHRAE 62.1 Table 6-4 (residential dwelling units):

  • Water closet (toilet): 25 cfm per fixture, continuous or occupancy-based
  • Bathtub/shower: 50 cfm per fixture, continuous or occupancy-based
  • “Continuous” defined as 24/7 operation or averaged over 24 hours

IMC Section 403.3.2:

  • Bathrooms: 50 cfm intermittent OR 20 cfm continuous
  • Allows averaged ventilation with controls

Typical dormitory suite (2-person room with private bath):

  • 1 water closet: 25 cfm
  • 1 shower: 50 cfm
  • Total: 75 cfm per bathroom

For shared gang bathrooms (10 fixtures):

  • 10 water closets × 25 cfm = 250 cfm
  • 10 showers × 50 cfm = 500 cfm
  • Total: 750 cfm minimum

Exhaust System Design

Duct sizing (equal friction method, 0.1 in. w.c./100 ft):

For 75 cfm bathroom exhaust:

  • 4-inch duct: 1,900 fpm (excessive noise)
  • 5-inch duct: 1,200 fpm (acceptable)
  • 6-inch duct: 850 fpm (preferred for quiet operation)

Recommended maximum velocities:

  • Branch ducts: 1,000 fpm
  • Main ducts: 1,500 fpm
  • Roof discharge: 2,000 fpm minimum (prevent recirculation)

Exhaust fan control strategies:

  1. Continuous operation: Simplest, highest energy use, meets code literally
  2. Occupancy-based: Motion sensor activates to code minimum during occupancy
  3. Averaged ventilation: Run at reduced cfm (50% of code) continuously, boost during shower use
  4. Humidity-based: Maintain RH < 60% to prevent mold growth

Energy consumption comparison (per bathroom, annual):

StrategyHours/yearAverage cfmFan power (W)kWh/yearCost ($0.12/kWh)
Continuous 75 cfm8,7607515131$16
Occupancy-based4,380751566$8
Averaged (40 cfm cont.)8,76040870$8
Humidity-based3,000751545$5

Recommendation: Humidity-based control with RH setpoint of 55-60% provides code compliance, mold prevention, and lowest energy consumption.

Common Area Conditioning

Lobbies and Lounges

Design considerations:

  • High occupancy density during peak hours (0.5 person/10 ft² typical)
  • Large glazing areas create solar loads and perimeter zone challenges
  • 24-hour occupancy requires continuous conditioning
  • ASHRAE 62.1: 5 cfm/person + 0.06 cfm/ft² minimum ventilation

System recommendations:

  • Rooftop units (RTUs) with VAV reheat for large spaces (> 5,000 ft²)
  • Heat pumps for medium spaces (1,000-5,000 ft²)
  • Radiant ceiling panels for high-ceiling spaces (improved comfort, reduced stratification)

Occupancy-based control:

  • CO₂ sensors modulate outdoor air (demand-controlled ventilation)
  • Unoccupied night setback: 55°F heating, 85°F cooling
  • Motion sensors disable conditioning after 30 minutes of vacancy

Study Rooms and Computer Labs

Cooling loads:

  • Students: 250 BTU/hr sensible per person (sedentary activity)
  • Computers: 400-600 BTU/hr per workstation (monitor + desktop)
  • Lighting: 1.0-1.5 W/ft² LED
  • Total: 50-80 BTU/hr/ft² peak

Ventilation requirements:

  • Study rooms: 5 cfm/person + 0.06 cfm/ft² (same as classrooms)
  • Computer labs: May require additional exhaust for equipment heat

Example (500 ft² study room, 25 occupants):

$$V_{min} = 5 \times 25 + 0.06 \times 500 = 125 + 30 = 155 \text{ cfm}$$

Cooling load:

$$Q_{total} = 250 \times 25 + 500 \times 1.2 + 10 \times 400 = 11,850 \text{ BTU/hr}$$

Recommendation: Provide individual RTU or heat pump serving study areas separately from dorm rooms to allow extended hours without conditioning vacant rooms.

Laundry Facilities

Heat and moisture sources:

  • Washers: 1,500 W electric heating (minimal space load, most to drain)
  • Dryers: 5,000 W electric heating + 0.5 gal/hr moisture removal per machine
  • Occupant load: Transient, 5-10 persons peak

Exhaust requirements:

  • Dryer exhaust: 200 cfm per machine (per manufacturer, not conditioned air)
  • Space exhaust: 1.5 cfm/ft² to remove residual moisture and heat
  • Maintain negative pressure relative to adjacent spaces

Cooling load (10 dryers, 1,000 ft² room):

  • Dryers: 10 × 5,000 W × 3.413 = 170,650 BTU/hr
  • Latent (moisture): 10 × 0.5 gal/hr × 8.33 lb/gal × 1,060 BTU/lb = 44,148 BTU/hr
  • Occupants: 10 × 450 BTU/hr = 4,500 BTU/hr
  • Total: 219,000 BTU/hr (18 tons)

System design:

  • Separate RTU or split system for laundry room
  • 100% outdoor air makeup for dryer exhaust (2,000 cfm for 10 machines)
  • Indirect evaporative cooling economizer to reduce compressor load
  • Destratification fans to improve comfort during winter

Energy Management Strategies

Occupied/Unoccupied Scheduling

Challenge: Dormitories have no true “unoccupied” periods (24-hour residential use).

Approach:

  1. Individual room control: Students adjust setpoint to personal preference, no central override
  2. Common areas: Night setback 0000-0600 (55°F heating, 85°F cooling)
  3. Bathroom exhaust: Humidity-based control reduces runtime
  4. Domestic hot water: Recirculation pump schedule reduces circulation to 0200-0600

Annual energy savings (200-room building):

  • Common area setback: 15% reduction = 18,000 kWh = $2,160
  • Exhaust control: 40% reduction = 12,000 kWh = $1,440
  • DHW circulation: 30% reduction = 8,000 kWh = $960
  • Total: $4,560/year

Metering and Monitoring

Building-level metering:

  • Whole-building electric (utility meter)
  • Chilled water BTU meter (if district cooling)
  • Hot water BTU meter (if district heating)
  • Gas meter for boilers (if on-site generation)

Submetering recommended:

  • HVAC systems separate from plug loads (identify HVAC vs occupant behavior)
  • Common areas separate from dorm rooms
  • Domestic hot water separate from space heating

Benefits:

  • Benchmark performance against similar buildings (CBECS, Campus portfolio)
  • Identify anomalous consumption patterns
  • Support student sustainability education initiatives

Benchmarking data (source: CBECS 2018, dormitories):

  • Energy Use Intensity (EUI): 68 kBTU/ft²/yr median
  • HVAC energy: 38% of total (26 kBTU/ft²/yr)
  • DHW energy: 22% of total (15 kBTU/ft²/yr)

Seasonal Optimization

Shoulder season (outdoor temp 55-70°F):

  • Maximize free cooling via economizer (common area RTUs)
  • Fan coil systems: Disable chiller, provide cooling via outdoor air to AHU
  • Heat pump systems: Natural ventilation via operable windows (if code permits)

Summer night ventilation:

  • Operate common area AHUs at 100% outdoor air from 0200-0600
  • Pre-cool building mass before peak afternoon loads
  • Estimated savings: 8-12% cooling energy in mild climates

Winter humidity control:

  • Reduce outdoor air to code minimums when outdoor temp < 20°F
  • Monitor space RH to prevent over-drying (target 30-50% RH)
  • Humidification rarely required in dormitories (occupant moisture generation)

Conclusion

Successful dormitory HVAC design requires balancing first cost constraints, individual comfort control, code-mandated ventilation, and long-term energy efficiency. Four-pipe fan coil systems provide optimal life-cycle economics for large buildings, while PTACs remain viable for smaller facilities despite higher operating costs. Continuous bathroom exhaust with humidity-based control meets ASHRAE 62.1 requirements while minimizing energy waste. Common areas benefit from occupancy-based scheduling and demand-controlled ventilation. Proper system selection and energy management can reduce operating costs by 30-40% compared to code-minimum designs while improving occupant comfort and satisfaction.

Sections

Individual Room Control in Dormitory HVAC Systems

Technical guidance for dormitory room-level HVAC control including fan coil configurations, PTAC/PTHP applications, two-pipe vs four-pipe systems, setpoint limiting, occupancy setback, and network integration for energy management.

HVAC for Dormitory Common Areas

Engineering guidance for dormitory common area HVAC including lobby and lounge conditioning, study room ventilation, laundry exhaust systems, kitchenette requirements, and security integration.

Bathroom Exhaust Systems in Dormitories

Comprehensive guide to dormitory bathroom exhaust design including continuous vs intermittent operation, code requirements, system types, and moisture control.