Demand-Controlled Ventilation (DCV)
Demand-controlled ventilation (DCV) adjusts outdoor air supply based on actual occupancy, providing energy savings while maintaining indoor air quality in educational facilities with highly variable occupancy patterns.
DCV Fundamentals
Operating Principle
DCV modulates ventilation based on occupancy indicators:
$$\dot{V}{OA} = \dot{V}{min} + K \times (Indicator - Baseline)$$
Where:
- $\dot{V}_{OA}$ = outdoor air flow rate
- $\dot{V}_{min}$ = minimum (unoccupied) ventilation
- K = proportional gain
- Indicator = CO₂, occupancy count, or other
Occupancy Detection Methods
| Method | Technology | Response Time | Accuracy |
|---|---|---|---|
| CO₂ sensing | NDIR sensors | Minutes | Good for groups |
| Occupancy counting | Video, infrared | Immediate | Very accurate |
| Schedule-based | Time clock | Pre-programmed | Variable |
| Motion detection | PIR sensors | Immediate | Presence only |
CO₂ as Proxy
CO₂ concentration indicates occupancy:
$$CO_2 = CO_{2,outdoor} + \frac{N \times G}{Q}$$
Where:
- N = number of occupants
- G = CO₂ generation rate (~0.31 L/min for adults)
- Q = ventilation rate
ASHRAE 62.1 Basis:
- 1,000 ppm indoor = approximately 15 CFM/person
- 800 ppm differential above outdoor
Educational Facility Applications
Classroom Implementation
Classrooms experience predictable but variable occupancy:
Typical Pattern:
- Empty: Before school, after hours
- Partial: Study halls, small groups
- Full: Standard class periods
- Peak: Special events
DCV Benefits:
- 30-50% ventilation energy savings
- Automatic response to actual occupancy
- Maintained IAQ regardless of schedule changes
Assembly Spaces
Gyms, auditoriums, cafeterias with highly variable loads:
Characteristics:
- Very low to maximum occupancy
- Short notice events
- Extended vacancy periods
DCV Essential: Fixed ventilation would be grossly oversized or undersized.
Laboratory Spaces
Science labs with fume hood requirements:
- DCV for general area when hoods satisfy minimum OA
- Coordinate with exhaust requirements
- Maintain proper pressure relationships
System Design
CO₂ Sensor Placement
Proper sensor location critical:
Recommended Locations:
- 3-6 ft above floor (breathing zone)
- Away from supply diffusers
- Away from doors and windows
- Minimum 3 ft from occupants
- Representative of space conditions
Avoid:
- Direct sunlight
- Near HVAC equipment
- Stagnant areas
- High traffic paths
Control Strategies
Single-Zone DCV:
- One sensor controls one zone
- Simplest implementation
- Common for classrooms
Multi-Zone DCV:
- Multiple zones share AHU
- Critical zone reset
- System-level optimization
$$\dot{V}{OA,system} = \frac{\sum \dot{V}{OA,zone}}{E_v}$$
Where $E_v$ = system ventilation effectiveness
Setpoint Selection
| Space Type | Target CO₂ | Minimum OA |
|---|---|---|
| Classrooms | 800-1,000 ppm | 5 CFM/person + 0.06 CFM/ft² |
| Gymnasium | 800-1,000 ppm | 7.5 CFM/person + 0.06 CFM/ft² |
| Cafeteria | 800-1,000 ppm | 7.5 CFM/person + 0.18 CFM/ft² |
| Library | 800-1,000 ppm | 5 CFM/person + 0.06 CFM/ft² |
Equipment Requirements
CO₂ Sensors
Sensor Specifications:
- Technology: NDIR (non-dispersive infrared)
- Range: 0-2,000 ppm minimum
- Accuracy: ±50 ppm or ±3%
- Output: 4-20 mA or BACnet
Calibration:
- Factory calibration
- Annual verification
- Automatic baseline correction (ABC)
- Fresh air calibration option
Damper Actuators
Outdoor air dampers for DCV:
- Modulating capability (0-100%)
- Characterized for linear flow
- Fast response (<60 seconds)
- Reliable positioning feedback
Control Integration
BAS programming requirements:
- PID control loops
- Minimum/maximum limits
- Alarm generation
- Trend logging
- Override capability
Energy Savings
Savings Calculation
$$Savings = \sum_{hours} (\dot{V}{OA,design} - \dot{V}{OA,actual}) \times \Delta h \times Cost$$
Where:
- $\Delta h$ = enthalpy difference
- Cost = energy cost per unit
Typical Savings
| Climate | Occupancy Variation | Typical Savings |
|---|---|---|
| Heating-dominated | High | 20-40% |
| Cooling-dominated | High | 15-30% |
| Mild | Moderate | 10-20% |
Payback Analysis
Simple payback typically 1-3 years:
$$Payback = \frac{Sensor + Installation + Commissioning}{Annual\ Energy\ Savings}$$
Code Compliance
ASHRAE 62.1
DCV explicitly permitted:
- Section 6.2.7 Dynamic Reset
- Allows reduced OA when occupancy reduced
- Must maintain minimum rates
- Requires OA monitoring
Building Energy Codes
ASHRAE 90.1 and IECC require DCV for:
- High occupancy spaces (>25 people/1,000 ft²)
- Systems >3,000 CFM
- Specific climate zones
Educational Codes
State education department requirements:
- Minimum ventilation rates
- CO₂ monitoring often required
- Documentation and reporting
Commissioning and Maintenance
Commissioning Requirements
Verify DCV performance:
- Sensor calibration verification
- Control sequence testing
- Response time verification
- Minimum OA verification
- Alarm testing
Ongoing Maintenance
| Frequency | Activity |
|---|---|
| Monthly | Verify sensor readings |
| Quarterly | Check damper operation |
| Annual | Sensor calibration |
| Annual | Review trend data |
Performance Monitoring
Track key indicators:
- CO₂ levels during occupancy
- Outdoor air delivery
- Energy consumption
- Occupant complaints
Demand-controlled ventilation provides educational facilities with optimized indoor air quality while significantly reducing energy consumption, particularly valuable in spaces with variable occupancy patterns.