Data Center Liquid Cooling Systems

Liquid Cooling Fundamentals

Liquid cooling technologies have become essential for modern data centers managing heat densities exceeding 20-30 kW per rack. The superior thermal properties of liquids compared to air—specific heat capacity approximately 4,000 times greater and thermal conductivity 25 times higher—enable efficient heat removal at elevated server inlet temperatures while reducing energy consumption.

ASHRAE Technical Committee 9.9 (Mission Critical Facilities, Technology Spaces, and Electronic Equipment) provides design guidance for liquid cooling implementations, emphasizing reliability, efficiency, and compatibility with existing infrastructure.

Heat Transfer Comparison

The fundamental heat transfer equation for liquid cooling systems:

$$Q = \dot{m} \cdot c_p \cdot \Delta T$$

Where:

  • $Q$ = heat removal rate (W)
  • $\dot{m}$ = mass flow rate (kg/s)
  • $c_p$ = specific heat capacity (J/kg·K)
  • $\Delta T$ = temperature differential (K)

For single-phase liquid cooling, the convective heat transfer coefficient:

$$h = \frac{Nu \cdot k}{D_h}$$

Where:

  • $h$ = convective heat transfer coefficient (W/m²·K)
  • $Nu$ = Nusselt number (dimensionless)
  • $k$ = thermal conductivity of fluid (W/m·K)
  • $D_h$ = hydraulic diameter (m)

Direct-to-Chip Cooling

Direct-to-chip (DTC) cooling employs cold plates mounted directly to high-power processors (CPUs, GPUs, ASICs) to extract heat at the source. This approach bypasses thermal interface resistance associated with heat sinks and air cooling.

Cold Plate Design

Cold plates typically utilize microchannel or pin-fin geometries to maximize surface area and turbulence. The thermal resistance from junction to fluid:

$$R_{j-f} = R_{die} + R_{TIM} + R_{coldplate} + R_{conv}$$

Where typical values for high-performance cold plates achieve $R_{coldplate}$ of 0.01-0.03 K/W.

System Architecture

graph TB
    A[Heat Source - CPU/GPU] -->|Cold Plate| B[Primary Loop - Dielectric Fluid]
    B --> C[Coolant Distribution Unit CDU]
    C --> D[Heat Exchanger]
    D --> E[Secondary Loop - Facility Water]
    E --> F[Chiller Plant]
    F --> E
    E --> D
    D --> C
    C --> B

    style A fill:#ff6b6b
    style B fill:#4ecdc4
    style C fill:#45b7d1
    style D fill:#96ceb4
    style E fill:#dfe6e9
    style F fill:#74b9ff

Rear Door Heat Exchangers

Rear door heat exchangers (RDHx) provide passive cooling by replacing standard rack doors with water-to-air heat exchangers. Hot exhaust air passes through the heat exchanger coils, rejecting heat to facility water before returning to the room.

Performance Characteristics

ParameterPassive RDHxActive RDHx
Heat Removal Capacity20-35 kW35-60 kW
Pressure Drop0-10 Pa50-150 Pa
Water Flow Rate15-30 L/min30-50 L/min
Supply Water Temperature15-20°C15-25°C
Approach Temperature3-5 K2-4 K
Power Consumption0 W (passive)200-400 W (fans)

The heat exchange effectiveness:

$$\epsilon = \frac{Q_{actual}}{Q_{max}} = \frac{T_{air,in} - T_{air,out}}{T_{air,in} - T_{water,in}}$$

For typical installations, effectiveness ranges from 0.60-0.85 depending on air and water flow rates.

Immersion Cooling

Immersion cooling submerges IT equipment directly in dielectric fluid, eliminating air cooling entirely. Two primary approaches exist: single-phase and two-phase immersion.

Single-Phase Immersion

Servers operate fully submerged in dielectric fluid (mineral oil, synthetic fluids, or engineered fluids) maintained below boiling point. Fluid circulation transfers heat to external heat exchangers.

Heat transfer follows natural or forced convection:

$$Nu = C \cdot Re^m \cdot Pr^n$$

Where constants C, m, n depend on geometry and flow regime. For forced convection in server chassis: $Nu = 0.023 \cdot Re^{0.8} \cdot Pr^{0.4}$ (Dittus-Boelter correlation).

Two-Phase Immersion

Servers submerge in low-boiling-point dielectric fluid (boiling point 40-65°C). Heat causes fluid vaporization at component surfaces; vapor condenses on overhead coils, releasing latent heat.

The boiling heat transfer coefficient:

$$q’’ = h_{boiling} \cdot (T_{surface} - T_{sat})$$

Nucleate boiling achieves heat transfer coefficients of 5,000-20,000 W/m²·K, dramatically exceeding single-phase convection (500-2,000 W/m²·K).

Immersion Cooling Comparison

CharacteristicSingle-PhaseTwo-Phase
Fluid Temperature30-50°C40-65°C (boiling point)
Heat Transfer ModeConvectionBoiling/condensation
Heat Transfer Coefficient500-2,000 W/m²·K5,000-20,000 W/m²·K
Pumping PowerModerateMinimal (natural circulation)
Fluid CostLowerHigher
Material CompatibilityBroaderRequires compatibility testing
Component TemperatureHigher varianceIsothermal (at saturation)
graph LR
    subgraph Single-Phase
    A1[Server Components] -->|Heat| B1[Dielectric Fluid]
    B1 -->|Pumped Flow| C1[Heat Exchanger]
    C1 -->|Cooled Fluid| B1
    end

    subgraph Two-Phase
    A2[Server Components] -->|Heat| B2[Liquid Vaporizes]
    B2 -->|Vapor Rises| C2[Condenser Coils]
    C2 -->|Condensed Liquid| B2
    end

    style A1 fill:#ff6b6b
    style B1 fill:#4ecdc4
    style C1 fill:#96ceb4
    style A2 fill:#ff6b6b
    style B2 fill:#ffeaa7
    style C2 fill:#74b9ff

Hybrid Cooling Architectures

Hybrid approaches combine air and liquid cooling to optimize cost and performance. Common configurations include:

  1. Liquid-assisted air cooling: Direct-to-chip cooling for high-power processors (CPUs, GPUs) with air cooling for remaining components (memory, storage, networking)

  2. Zoned cooling: Liquid cooling for high-density racks (>20 kW) with air cooling for standard racks

  3. Progressive migration: Rear door heat exchangers as bridge technology before full direct-to-chip deployment

Hybrid System Energy Balance

For a hybrid rack with liquid-cooled processors and air-cooled components:

$$Q_{total} = Q_{liquid} + Q_{air}$$

Where typical distributions achieve 60-80% heat removal via liquid with corresponding PUE improvements of 15-30% compared to air-only cooling.

Cooling StrategyPUE RangeTypical Rack DensityCapital Cost Index
Air Only (Hot/Cold Aisle)1.4-1.88-15 kW1.0×
Rear Door Heat Exchanger1.3-1.515-30 kW1.2-1.4×
Direct-to-Chip Hybrid1.15-1.325-50 kW1.5-2.0×
Full Immersion (Single-Phase)1.05-1.1550-100 kW1.8-2.5×
Full Immersion (Two-Phase)1.03-1.1100-250 kW2.5-3.5×

Coolant Distribution Units

Coolant Distribution Units (CDUs) serve as the interface between primary liquid cooling loops and facility water infrastructure. CDUs provide:

  • Heat exchange between primary (dielectric fluid) and secondary (facility water) loops
  • Pumping for primary coolant circulation
  • Filtration and fluid conditioning
  • Leak detection and monitoring
  • Temperature and flow control

CDU sizing follows the relationship:

$$\dot{m}{coolant} = \frac{Q{IT}}{\rho \cdot c_p \cdot \Delta T}$$

For a 100 kW IT load with 10 K temperature differential and water as coolant:

$$\dot{m} = \frac{100,000}{1000 \cdot 4186 \cdot 10} = 2.39 \text{ L/s} \approx 143 \text{ L/min}$$

Design Considerations

Fluid Selection Criteria:

  • Dielectric strength for electrical isolation
  • Thermal conductivity and specific heat capacity
  • Viscosity across operating temperature range
  • Material compatibility with server components
  • Environmental impact and disposal requirements
  • Cost and availability

Reliability Requirements:

  • Redundant pumps and leak detection
  • Quick-disconnect couplings for serviceability
  • Pressure monitoring and relief valves
  • Filtration to prevent particle contamination
  • Fluid quality monitoring (conductivity, pH)

Integration Challenges:

  • Server warranty implications
  • Staff training requirements
  • Maintenance procedures
  • Decommissioning and fluid disposal
  • Emergency shutdown protocols

ASHRAE TC 9.9 recommends liquid cooling for applications exceeding 20 kW/rack density where air cooling becomes economically or physically impractical. The selection between direct-to-chip, immersion, or hybrid approaches depends on density requirements, infrastructure constraints, and total cost of ownership analysis.