HVAC Systems Encyclopedia

A comprehensive encyclopedia of heating, ventilation, and air conditioning systems

Seismic Restraints for HVAC Equipment: Detailed Guide

Seismic Restraints for HVAC Equipment

Proper seismic restraint design protects HVAC equipment from earthquake-induced forces and prevents catastrophic failures. This guide covers force calculations, anchorage design, and installation requirements per IBC, ASCE 7, and SMACNA standards.

Seismic Force Calculations

Horizontal Seismic Force (Fp)

The horizontal seismic design force for nonstructural components is calculated using ASCE 7 equation 13.3-1:

$$F_p = \frac{0.4 a_p S_{DS} W_p}{(R_p/I_p)} \left(1 + 2\frac{z}{h}\right)$$

Subject to:

$$F_{p,\text{max}} = 1.6 S_{DS} I_p W_p$$

$$F_{p,\text{min}} = 0.3 S_{DS} I_p W_p$$

Where:

  • $F_p$ = seismic design force applied to component (lbs or kN)
  • $a_p$ = component amplification factor (typically 2.5 for mechanical equipment)
  • $S_{DS}$ = design spectral response acceleration at short periods
  • $W_p$ = component operating weight including contents
  • $R_p$ = component response modification factor (varies by equipment type)
  • $I_p$ = component importance factor (1.0 or 1.5)
  • $z$ = height of attachment point above grade
  • $h$ = average roof height of structure

Equipment Response Modification Factors

Equipment TypeRp ValueNotes
Mechanical equipment2.5General HVAC equipment
Vibration isolated equipment2.5With seismic snubbers
Distributed systems2.5Ducts, piping below 12 in diameter
Equipment on vibration isolators2.5If Fp ≥ 1.6 times isolator restoring force
Tanks and vessels2.5Storage tanks, water heaters
Boilers and pressure vessels1.0High hazard equipment

Anchorage Design Requirements

Minimum Anchorage Strength

Anchors must resist both horizontal and vertical seismic forces:

Horizontal Force: $$F_h = F_p$$

Vertical Force (concurrent): $$F_v = 0.2 S_{DS} W_p$$

Anchorage Safety Factors

Anchor design strength must exceed applied loads with appropriate safety factors:

$$\phi R_n \geq \text{Required Strength}$$

Where:

  • $\phi$ = strength reduction factor (0.65 for cast-in anchors, 0.55 for post-installed)
  • $R_n$ = nominal anchor strength in tension or shear

Equipment Anchorage Configurations

Curb-Mounted Rooftop Units

graph TB
    subgraph "RTU Seismic Anchorage"
        A[Rooftop Unit] --> B[Roof Curb]
        B --> C[Anchor Bolts Through Curb]
        C --> D[Structural Roof Deck]
        E[Seismic Restraints] --> A
        E --> F[Lateral Bracing]
        F --> D
    end

    style A fill:#e1f5ff
    style B fill:#fff4e1
    style D fill:#f0f0f0

Design Criteria:

  • Minimum 4 anchor bolts per curb
  • Bolt diameter ≥ 1/2 inch for units < 1000 lbs
  • Bolt diameter ≥ 5/8 inch for units > 1000 lbs
  • Embed depth per manufacturer and structural requirements
  • Lateral restraints at 4 corners if Fp exceeds curb weight

Floor-Mounted Equipment on Isolators

graph TB
    subgraph "Equipment with Seismic Restraints"
        A[Equipment Base] --> B[Vibration Isolators]
        B --> C[Inertia Base/Housekeeping Pad]
        D[Seismic Snubbers] -.->|Gap δ| A
        D --> C
        C --> E[Anchor Bolts]
        E --> F[Structural Floor]
    end

    subgraph "Snubber Gap Calculation"
        G[Normal Operation: Gap Active]
        H[Seismic Event: Snubbers Engage]
    end

    style A fill:#e1f5ff
    style C fill:#fff4e1
    style D fill:#ffe1e1
    style F fill:#f0f0f0

Seismic Snubber Requirements:

  • Maximum clearance gap: 1/4 inch
  • Snubber capacity must resist full Fp
  • All-directional restraint (both horizontal axes)
  • Vertical restraint if required by ASCE 7
  • Minimum 4 snubbers per equipment base

Suspended Equipment Bracing

For ceiling-hung equipment (fan coil units, air handlers), restraint consists of:

graph LR
    subgraph "Suspended Unit Restraint System"
        A[Suspended Equipment] --> B[Support Rods]
        A --> C[Lateral Bracing Cables/Rods]
        B --> D[Structure Above]
        C --> D
        E[4-Point Lateral Bracing] --> A
    end

    style A fill:#e1f5ff
    style C fill:#ffe1e1
    style D fill:#f0f0f0

Bracing Configuration:

  • Minimum 4-point lateral restraint
  • Brace angle 45° from horizontal (30° to 60° acceptable)
  • Brace capacity ≥ Fp/number of braces in direction
  • No reliance on ceiling grid for seismic resistance
  • Direct attachment to structural elements

Code Compliance Requirements

IBC Seismic Design Categories

SDCSDS RangeEquipment Anchoring Required
ASDS < 0.167gNo specific requirements
B0.167g ≤ SDS < 0.33gLimited requirements
C0.33g ≤ SDS < 0.50gFull anchorage and bracing
D, E, FSDS ≥ 0.50gEnhanced requirements, special inspections

ASHRAE Guideline 13 Provisions

Equipment Weight Thresholds:

  • Equipment < 400 lbs: Simplified anchorage acceptable (SDC A-C)
  • Equipment ≥ 400 lbs: Full seismic analysis required
  • Equipment > 10,000 lbs: Enhanced design and special inspection

Installation Height Considerations:

  • Ground-mounted: Standard analysis
  • Roof-mounted: Amplification factor z/h applies
  • Equipment > 30 ft above grade: Increased force coefficients

SMACNA Seismic Restraint Manual

Key provisions from SMACNA guidelines:

Duct Bracing:

  • Ducts ≥ 6 sq ft cross-section require lateral bracing
  • Maximum brace spacing: 30 ft for longitudinal, 12 ft for transverse
  • Brace capacity: 100 lbs minimum, or calculated seismic force

Pipe Bracing:

  • Pipes ≥ 2.5 inch diameter require seismic bracing (SDC C-F)
  • Maximum brace spacing: 40 ft for longitudinal, 12 ft for transverse
  • Four-way bracing at changes in direction

Equipment Installation:

  • Concrete housekeeping pads minimum 4 inches thick
  • Grout or shim between equipment and mounting surface
  • Anchor bolts installed per ACI 318 provisions
  • Field verification of substrate strength

Vibration Isolation with Seismic Restraint

Restoring Force Check

For equipment on vibration isolators, verify:

$$F_p \geq 1.6 \times k \times \delta_{static}$$

Where:

  • $k$ = isolator spring stiffness (lbs/inch)
  • $\delta_{static}$ = static deflection under equipment weight (inches)

If this criterion is not satisfied, use Rp = 1.0 instead of 2.5.

Snubber Gap Calculation

Maximum allowable gap between equipment and snubber:

$$\delta_{gap} = \min\left(\frac{1}{4}\text{ inch}, \frac{\delta_{static}}{2}\right)$$

This prevents equipment from gaining excessive momentum before engaging seismic restraints.

Installation and Inspection

Critical Installation Steps

  1. Substrate verification: Confirm concrete strength (minimum 2500 psi) and thickness
  2. Anchor installation: Follow manufacturer torque specifications
  3. Gap verification: Measure and document snubber clearances
  4. Alignment: Ensure equipment level and properly supported
  5. Documentation: Record anchor types, embedment depths, torque values

Special Inspection Requirements

SDC D, E, F require special inspection for:

  • Equipment with Ip = 1.5 (essential facilities)
  • Supports for equipment weighing > 400 lbs
  • Post-installed anchors in concrete
  • Field welding of seismic braces

Common Installation Errors

  • Insufficient embedment depth for anchors
  • Oversized holes reducing anchor capacity
  • Missing or improperly adjusted seismic snubbers
  • Inadequate edge distance for concrete anchors
  • Reliance on non-structural elements (architectural features, ceiling grid)
  • Incorrect torque application to anchor bolts

Design Calculation Example

Given:

  • Rooftop air handler: Wp = 2,500 lbs
  • Location: SDC D, SDS = 1.0g
  • Height: z = 40 ft, h = 45 ft
  • Importance factor: Ip = 1.0

Calculation:

$$F_p = \frac{0.4 \times 2.5 \times 1.0 \times 2500}{2.5/1.0} \left(1 + 2\frac{40}{45}\right) = 2,778 \text{ lbs}$$

Check maximum: $$F_{p,max} = 1.6 \times 1.0 \times 1.0 \times 2500 = 4,000 \text{ lbs}$$ ✓

Check minimum: $$F_{p,min} = 0.3 \times 1.0 \times 1.0 \times 2500 = 750 \text{ lbs}$$ ✓

Design force: Fp = 2,778 lbs

Required anchor shear strength (4 bolts): $$V_{required} = \frac{2778}{4} = 695 \text{ lbs per bolt}$$

Select 5/8" diameter expansion anchor with φVn ≥ 695 lbs.

Conclusion

Seismic restraint design requires careful attention to code-mandated force calculations, proper anchorage selection, and installation quality. Following ASCE 7 methodology, IBC requirements, and SMACNA guidelines ensures equipment remains functional and safe during seismic events. Proper documentation and special inspection provide verification that installed systems meet design intent and regulatory requirements.

Sections

HVAC Seismic Bracing Systems: Design & Installation

Comprehensive guide to cable bracing, rigid strut systems, and longitudinal/lateral restraints for HVAC equipment per ASCE 7 and SMACNA seismic standards.

Anchorage Methods

Overview

Anchorage methods secure HVAC equipment and components to building structures, providing resistance to seismic forces, wind loads, and operational vibrations. Proper anchor selection and installation ensure structural integrity, code compliance, and system reliability throughout the equipment lifecycle.

Concrete Anchor Types

Expansion Anchors

Expansion anchors develop holding capacity through radial forces against concrete walls:

Sleeve-Type Expansion Anchors:

  • Conical sleeve expands against drilled hole sides
  • Torque-controlled installation: 50-100 ft-lb typical
  • Allowable tension: 1,500-5,000 lbf depending on size and concrete strength
  • Minimum embedment: 3 to 4 inches for 3/8 to 5/8 inch diameter
  • Not suitable for shallow embedments or cracked concrete
  • Requires 3,000 psi minimum concrete strength

Drop-In Anchors:

Ductwork and Piping Supports for Seismic Restraint

Engineering guidance for seismic support systems including hanger types, rod sizing calculations, support spacing, and anchorage requirements per SMACNA and MSS standards.

IBC ASCE 7 Requirements

Seismic Design Categories (SDC)

SDC Classification

Buildings are assigned a Seismic Design Category (A through F) based on:

  • Occupancy category (I, II, III, or IV)
  • Mapped spectral response accelerations (Ss and S1)
  • Site class (A through F)

SDC Levels:

SDCSeismic RiskHVAC Requirements
AMinimalNo seismic restraints required
BLowLimited restraint requirements
CModerateRestraints required for equipment > 400 lb
DHighRestraints required for equipment > 400 lb, enhanced detailing
EVery HighRestraints required for equipment > 20 lb, stringent requirements
FNear-faultRestraints required for equipment > 20 lb, most stringent

Determination Process

  1. Establish occupancy category from IBC Table 1604.5
  2. Obtain mapped spectral accelerations Ss and S1 from ASCE 7 maps
  3. Determine site class from geotechnical investigation
  4. Calculate design spectral response accelerations SDS and SD1
  5. Assign SDC from ASCE 7 Tables 11.6-1 and 11.6-2

Component Importance Factor (Ip)

Ip Values

The component importance factor reflects the hazard to human life and need for continued operation: