HVAC Systems Encyclopedia

A comprehensive encyclopedia of heating, ventilation, and air conditioning systems

Fire Safety Engineering

Fire safety engineering integrates HVAC system design with life safety objectives to control smoke movement, maintain tenable conditions during evacuation, and prevent fire spread through building air distribution systems. HVAC systems play a critical role in occupant safety during fire events through smoke control, compartmentation, and pressurization strategies.

Smoke Control System Design

Smoke control systems manage smoke movement during fire events to protect egress paths and designated refuge areas. Design approaches depend on building geometry, occupancy classification, and code requirements.

Smoke Control Methods

Pressurization Systems

  • Stairwell pressurization: 0.10-0.15 in. w.g. minimum pressure differential
  • Elevator shaft pressurization: 0.05-0.10 in. w.g. across closed doors
  • Vestibule pressurization: series pressurization for enhanced protection
  • Zoned smoke control: pressure differential zoning with barriers

Smoke Exhaust Systems

  • Dedicated smoke exhaust fans with temperature-rated construction
  • Exhaust rates: 4-6 air changes per hour for smoke zones
  • Makeup air provisions: 50-100% of exhaust air volume
  • Smoke reservoir design: minimum 20% of floor-to-ceiling height

Design Pressure Differentials

ApplicationMinimum PressureMaximum PressureDesign Basis
Stairwell (doors closed)0.10 in. w.g.0.35 in. w.g.NFPA 92A
Stairwell (single door open)0.05 in. w.g.Maintain flow direction
Elevator shaft0.05 in. w.g.0.20 in. w.g.Stack effect mitigation
Refuge area0.05 in. w.g.0.25 in. w.g.Positive pressure
Smoke zone boundary0.05 in. w.g.0.15 in. w.g.Zone isolation

Tenability Criteria

Maintain tenable conditions in protected areas:

  • Visibility: greater than 30 ft (10 m) in egress paths
  • Temperature: below 140°F (60°C) at head height
  • Carbon monoxide: less than 1,400 ppm for 30-minute exposure
  • Oxygen concentration: greater than 15% by volume
  • Smoke layer height: minimum 6 ft (1.8 m) above floor level

Fire and Smoke Dampers

Fire dampers and smoke dampers prevent fire and smoke propagation through air distribution systems where ductwork penetrates fire-rated assemblies.

Fire Damper Requirements

Installation Locations

  • Duct penetrations through fire-rated walls (1-hour minimum)
  • Duct penetrations through fire-rated floor/ceiling assemblies
  • Corridor wall penetrations in non-sprinklered buildings
  • Shaft penetrations (except by specific code exceptions)

Fire Damper Classifications

Damper TypeClosure TemperatureFire RatingTypical Application
Static fire damper165°F (74°C)1.5 or 3 hoursFire walls, area separation
Dynamic fire damper165°F (74°C)1.5 or 3 hoursOperating air systems
Ceiling radiation damper165°F (74°C)1 or 2 hoursMembrane penetrations
Combination fire/smoke165°F (74°C)1.5 or 3 hoursDual function applications

Fusible Link Ratings

  • Standard rating: 165°F (74°C) for typical applications
  • Intermediate rating: 212°F (100°C) for high ambient areas
  • High rating: 286°F (141°C) for commercial kitchens or boiler rooms

Smoke Damper Requirements

Operational Characteristics

  • Closure actuation: smoke detector signal or fire alarm system
  • Leakage classification: Class I (10 cfm/ft²), Class II (40 cfm/ft²), Class III (120 cfm/ft²)
  • Temperature rating: 250°F (121°C) minimum for smoke dampers
  • Elevated temperature rating: 350°F (177°C) for combination dampers

Installation Standards

Code RequirementApplicationActuation MethodLeakage Class
NFPA 90AAir distribution systemsSmoke detectorClass I or II
NFPA 105Smoke barrier penetrationsFire alarm signalClass I
IBC Section 717Shaft penetrationsArea smoke detectorClass II
IMC Section 607Corridor penetrationsDuct smoke detectorClass II

NFPA Code Requirements

NFPA 90A: Air Conditioning and Ventilating Systems

Duct System Protection

  • Duct smoke detectors required for systems exceeding 2,000 cfm
  • Detector locations: downstream of filters, upstream of branch connections
  • Fan shutdown sequence: within 60 seconds of detector activation
  • Outside air intake closure: smoke dampers at outdoor air intakes

Duct Construction and Materials

  • Fire-rated duct systems through fire-rated shafts
  • Noncombustible or limited-combustible materials
  • Duct insulation flame spread index: 25 maximum
  • Smoke developed index: 50 maximum

NFPA 92: Smoke Control Systems

Design Documentation Requirements

  • Rational analysis based on physical principles
  • Computational fluid dynamics (CFD) modeling for complex geometries
  • Full-scale acceptance testing procedures
  • Operations and maintenance manuals

System Performance Testing

Test ParameterAcceptance CriteriaTest Method
Pressure differential±20% of design valueDifferential pressure gauge
Airflow volume±10% of design valuePitot tube traverse
Door opening force≤30 lbf (133 N)Force gauge at latch
Smoke detector responseAlarm within 30 secondsCanned smoke test
Damper closure time≤60 secondsVisual observation
Fan start time≤30 secondsControl system verification

NFPA 101: Life Safety Code

Smoke Compartmentation

  • Maximum smoke compartment area: 22,500 ft² (2,090 m²)
  • Maximum travel distance to smoke barrier: 200 ft (61 m)
  • Smoke barrier rating: 1-hour minimum
  • HVAC system isolation across smoke barriers

Integration with Fire Alarm Systems

Control Sequences

Fire Alarm Activation Response

  1. Shut down air handling units serving fire zone
  2. Close smoke dampers in smoke barrier penetrations
  3. Activate smoke control pressurization fans
  4. Override economizer controls to 100% outdoor air (if applicable)
  5. Disable variable air volume box minimum flow setpoints
  6. Release magnetic hold-open devices on fire doors

Interface Requirements

  • Hard-wired connections between fire alarm panel and HVAC controls
  • Dedicated fire alarm circuits (non-multiplexed)
  • Supervised circuit monitoring with trouble indication
  • Manual override capability at fire command center
  • Annunciation of smoke control system status

Duct Smoke Detector Integration

Detector Placement

  • Return air systems: prior to air entering return air plenum
  • Supply air systems: downstream of fan, upstream of first branch
  • Detector sampling tube velocity: 200-1,500 fpm
  • Maximum detector spacing: per manufacturer’s listing

Control Actions

Detector LocationPrimary ActionSecondary ActionOverride Capability
Return air ductShut down fanClose outdoor air damperFire department only
Supply air ductShut down fanActivate alarmFire department only
Smoke control zoneActivate pressurizationClose zone dampersAutomatic by system
Elevator lobbyRecall elevatorsPressurize shaftManual at fire panel

Pressurization System Design

Stairwell Pressurization

Supply Air Calculations

  • Door leakage component: Q_door = 60 A√(ΔP)
  • Construction leakage: Q_wall = 0.2 cfm/ft² at design pressure
  • Minimum airflow: sum of all leakage paths with safety factor
  • Relief damper sizing: accommodate single door opening scenario

Fan Selection Criteria

  • Multiple fan speeds or VFD control for door opening compensation
  • Pressure rise: 1.5-2.0 in. w.g. at design flow
  • Temperature rating: 250°F (121°C) for 1 hour minimum
  • Redundant fan configuration for critical facilities

Zoned Smoke Control

Pressure Zoning Strategy

  • Fire zone: negative pressure (exhaust)
  • Adjacent zones: neutral or slight positive pressure
  • Remote zones: normal HVAC operation
  • Vertical shafts: positive pressure relative to fire floor

Makeup Air Requirements

Exhaust Rate (cfm)Makeup Air SourceDistribution MethodTemperature Control
10,000-30,000Dedicated fanLow-level dischargeHeated to 65°F min
30,000-75,000Multiple fansPerimeter distributionHeated or tempered
>75,000Centralized MUA unitOverhead distributionFull heating capacity

Fire-Rated Construction

Fire Resistance Requirements

Ductwork in Fire-Rated Assemblies

  • 2-hour shaft: 2-hour duct or dampers at entry/exit
  • 1-hour shaft: 1-hour duct or dampers at entry/exit
  • Fire barrier penetration: damper with equal rating to barrier
  • Grease duct in shaft: may require additional protection

Shaft Penetration Protection

Shaft RatingDuct Protection MethodDamper RequirementInspection Access
2-hour2-hour duct systemNot required if duct ratedEvery floor
2-hourUnprotected duct1.5-hour damper both endsAt penetration
1-hour1-hour duct systemNot required if duct ratedEvery floor
1-hourUnprotected duct1.5-hour damper both endsAt penetration

Kitchen Exhaust Systems

Grease Duct Fire Protection

  • Duct material: 16 gauge (1.5 mm) carbon steel minimum
  • Clearance to combustibles: 18 in. (450 mm) minimum
  • Fire suppression system: actuation closes supply air dampers
  • Exhaust fan interlock: continues operation during suppression

Testing and Commissioning

Fire Damper Testing

Installation Verification

  • Sleeve alignment with structural opening
  • Clearance for full blade travel without interference
  • Fusible link orientation and temperature rating
  • Access door location for inspection and testing

Operational Testing

  • Drop test: manual release of fusible link mechanism
  • Closure verification: complete seating of blades
  • Airflow impact: minimal pressure drop when open
  • Reset procedure: proper blade return and link replacement

Smoke Control System Commissioning

Pre-functional Checks

  1. Verify all dampers installed per design drawings
  2. Confirm pressure sensor calibration and location
  3. Test all duct smoke detectors with canned smoke
  4. Verify control sequence programming against specifications
  5. Inspect air distribution pathways for obstructions

Functional Performance Tests

  1. Measure pressure differentials at design conditions
  2. Verify door opening forces at all egress points
  3. Confirm smoke detector activation response times
  4. Document fan performance (flow, pressure, power)
  5. Test manual override functions at fire command center
  6. Conduct system performance under simulated fire scenarios

Acceptance Criteria Verification

System ComponentPerformance MetricToleranceCorrective Action Threshold
Pressure differentialDesign ΔP±20%Adjust fan speed or relief damper
Airflow rateDesign cfm±10%Rebalance distribution system
Door opening force30 lbf maximum+0 lbfReduce pressure or add relief
Detector response30 seconds±5 secondsRelocate or adjust sensitivity
Fan start delay30 seconds±10 secondsReprogram control sequence

Documentation Requirements

Design Documentation

Submittal Documents

  • Smoke control system narrative and design basis
  • Pressure differential calculations with leakage assumptions
  • Smoke exhaust and makeup air sizing calculations
  • Fire damper schedule with ratings and locations
  • Duct smoke detector locations and wiring diagrams
  • Control sequence of operations for all fire modes

Operations and Maintenance

Required Information

  • System description and operational theory
  • Inspection and testing schedules (annual minimum for dampers)
  • Troubleshooting procedures and common failure modes
  • Replacement parts list with manufacturer contact information
  • As-built drawings showing final installation conditions
  • Commissioning test results and acceptance documentation

Fire safety engineering requires comprehensive integration between HVAC systems, fire protection systems, and building codes to ensure life safety objectives are achieved during fire events.

Sections

Smoke Control Systems

Components

  • Pressurization Systems
  • Mechanical Smoke Exhaust
  • Natural Smoke Venting
  • Atrium Smoke Control
  • Stairwell Pressurization
  • Elevator Shaft Pressurization
  • Smoke Control Sequence

Fire Damper Systems

Components

  • Fire Damper Rating Requirements
  • Combination Fire Smoke Dampers
  • Ceiling Radiation Dampers
  • Fusible Link Actuation
  • Electric Actuator Dampers
  • Fire Damper Inspection Requirements
  • Imc Nfpa Requirements

Fire Resistance Rated Assemblies

Components

  • Ul Rated Floor Ceiling
  • Ul Rated Wall Assemblies
  • Penetration Firestopping
  • Through Penetration Firestop Systems
  • Membrane Penetration Firestop