Candy Manufacturing
Candy manufacturing refrigeration systems provide precise temperature and humidity control for multiple processing stages including cooking, cooling, tempering, and storage. Process cooling requirements vary significantly based on candy composition, with hard candies requiring rapid cooling to achieve glass transition, chocolate products demanding controlled crystallization, and gummy candies needing gradual temperature reduction to prevent surface defects.
Cooling Tunnel Design
Cooling tunnels remove heat from candy products following cooking or forming operations. Tunnel length, air velocity, and temperature profiles determine production throughput and product quality.
Tunnel Configuration
Continuous belt systems transport products through multiple cooling zones with independent temperature control. Belt speed ranges from 0.5 to 3.0 m/min depending on product mass and required cooling rate.
Multi-zone design allows progressive temperature reduction:
- Entry zone: Initial cooling with minimal temperature differential to prevent thermal shock
- Primary cooling: Maximum heat removal at controlled rates
- Tempering zone: Final temperature equilibration
- Exit conditioning: Surface temperature stabilization before packaging
Air distribution employs overhead supply with perforated ducts or nozzle arrays positioned 150-300 mm above product surface. Supply air velocity at product level ranges from 3-8 m/s for forced convection cooling.
Heat Transfer Analysis
Cooling rate calculation requires convective heat transfer coefficient determination:
h = Nu × k / L
Where:
- h = convective heat transfer coefficient, W/(m²·K)
- Nu = Nusselt number (dimensionless)
- k = air thermal conductivity, W/(m·K)
- L = characteristic length, m
For turbulent flow over flat candy surfaces:
Nu = 0.037 × Re^0.8 × Pr^0.33
Cooling load per meter of tunnel:
Q = ṁ × cp × ΔT
Where:
- Q = cooling load, W
- ṁ = product mass flow rate, kg/s
- cp = specific heat capacity, J/(kg·K)
- ΔT = temperature reduction, K
Temperature Control Requirements
Different candy types require specific cooling profiles to achieve desired texture, appearance, and shelf stability.
Hard Candy Cooling
Hard candies require rapid cooling from cooking temperature (150-165°C) to below glass transition temperature (Tg ≈ 30-50°C depending on moisture content and composition).
Cooling rate targets:
- Initial cooling: 20-40°C/min from cooking temperature to 80°C
- Secondary cooling: 10-20°C/min from 80°C to 40°C
- Final conditioning: 2-5°C/min from 40°C to packaging temperature
Supply air temperature progression:
- Zone 1: 10-15°C
- Zone 2: 5-10°C
- Zone 3: 15-20°C (tempering)
Excessive cooling rates cause surface stress cracking. Insufficient cooling results in product deformation and sticking.
Chocolate Tempering Integration
Chocolate enrobing lines require cooling tunnels following tempering units. Proper cocoa butter crystallization demands precise temperature control.
Target cooling profile for dark chocolate:
- Enrobing temperature: 31-32°C
- Initial cooling zone: 12-15°C supply air, 2-3 minutes
- Primary cooling: 8-12°C supply air, 3-5 minutes
- Final conditioning: 15-18°C supply air, 1-2 minutes
- Exit temperature: 18-20°C
Milk chocolate requires gentler cooling due to milk solids:
- Higher initial zone temperatures (15-18°C)
- Extended cooling time
- Exit temperature: 16-18°C
Gummy Candy Processing
Gummy candies contain 15-22% moisture and require controlled cooling to prevent surface condensation and uneven moisture distribution.
Cooling sequence:
- Demolding temperature: 55-70°C
- Initial air temperature: 20-25°C (small temperature differential prevents surface hardening)
- Primary cooling: 15-20°C, 50-60% RH
- Final temperature: 20-22°C before starch application or packaging
Relative humidity control prevents moisture loss from product surface while avoiding condensation on equipment surfaces.
Humidity Management
Humidity control prevents surface defects including sugar bloom on chocolate, moisture migration in hard candies, and surface tackiness in gummy products.
Dew Point Control
Equipment surfaces must remain above dew point temperature of process air to prevent condensation. Temperature differential between supply air and cooling coil surface determines moisture removal capacity.
For supply air at 10°C and 60% RH:
- Dew point temperature: 2.2°C
- Cooling coil surface temperature: -2 to 0°C
- Condensate removal rate depends on air circulation volume
Reheat capacity required:
Q_reheat = ṁ_air × cp,air × (T_supply - T_coil)
Where reheat raises discharge temperature from coil temperature to desired supply temperature while maintaining reduced absolute humidity.
Process Air Conditions
| Candy Type | Supply Air Temp (°C) | Relative Humidity (%) | Air Velocity (m/s) | Dew Point (°C) |
|---|---|---|---|---|
| Hard candy | 5-15 | 40-50 | 5-8 | -5 to 2 |
| Chocolate | 8-15 | 50-60 | 3-5 | 2 to 8 |
| Gummy candy | 15-22 | 50-60 | 2-4 | 8 to 14 |
| Caramel | 10-18 | 45-55 | 4-6 | 0 to 8 |
| Fondant | 12-20 | 55-65 | 3-5 | 5 to 12 |
Product-Specific Requirements
Hard Candy Systems
Cooling load calculation example:
Production rate: 500 kg/hr Inlet temperature: 160°C Exit temperature: 25°C Specific heat: 1.8 kJ/(kg·K)
Q = (500 kg/hr) × (1.8 kJ/kg·K) × (160-25 K) / 3600 s/hr Q = 33.75 kW sensible cooling load
Add safety factor of 1.15-1.25 for equipment heat gain and transient conditions: Design capacity: 39-42 kW
Chocolate Cooling Tunnels
Chocolate crystallization releases latent heat of fusion (approximately 120-150 kJ/kg). Total cooling load includes:
Q_total = Q_sensible + Q_latent
Q_sensible = ṁ × cp × ΔT Q_latent = ṁ × L_f × X
Where:
- L_f = latent heat of cocoa butter crystallization, kJ/kg
- X = cocoa butter mass fraction (0.30-0.35 for dark chocolate)
For 1000 kg/hr production:
- Sensible load: ṁ × 2.2 kJ/(kg·K) × (32-20 K) = 7.3 kW
- Latent load: ṁ × 0.33 × 135 kJ/kg = 12.4 kW
- Total: 19.7 kW, design capacity: 24 kW with safety factor
Aerated Candy Products
Marshmallow, nougat, and whipped confections contain entrained air (40-60% by volume) requiring gentle handling. Air distribution must avoid product surface disruption while providing adequate cooling.
Design parameters:
- Maximum air velocity: 2-3 m/s at product surface
- Supply air temperature: 15-20°C
- Cooling tunnel residence time: 8-15 minutes
- Final product temperature: 22-25°C
Condensation Prevention
Condensation on product surfaces causes sugar dissolution, surface defects, and microbial growth. Prevention requires maintaining all contact surfaces above dew point temperature.
Surface Temperature Control
Belt surface temperature monitoring prevents condensation accumulation:
- Continuous temperature monitoring with IR sensors
- Belt material selection (stainless steel mesh with minimal thermal mass)
- Insulated return path to maintain temperature above dew point
Minimum belt surface temperature:
T_belt,min = T_dp + 3°C safety margin
Where T_dp is dew point temperature of process air.
Equipment Design Features
Insulated tunnel enclosures prevent external moisture infiltration and maintain internal surface temperatures above condensation point. Insulation thickness calculated from:
Q = U × A × ΔT
Where U-value includes insulation resistance and surface resistances. Typical construction: 75-100 mm polyurethane or polyisocyanurate insulation achieving U ≤ 0.25 W/(m²·K).
Air curtains at tunnel openings minimize ambient air infiltration:
- Vertical laminar flow curtains
- Air velocity: 8-12 m/s
- Temperature matching adjacent zone ±2°C
Vapor barriers on cold surfaces prevent moisture transmission through insulation to cold surfaces where condensation would occur.
Refrigeration System Design
Capacity Requirements
Total refrigeration load includes:
- Product cooling load (sensible and latent heat removal)
- Air circulation load (fan motor heat)
- Infiltration load (ambient air entry)
- Transmission load (heat gain through enclosure)
- Lighting and equipment loads
Typical load distribution:
- Product cooling: 60-70%
- Infiltration: 15-20%
- Transmission: 8-12%
- Fan motors: 5-8%
- Other: 2-5%
System Configuration
Direct expansion (DX) systems provide temperature control for small to medium production lines (up to 100 kW cooling capacity). Evaporator coils installed in air handling units with precise temperature control through refrigerant flow modulation.
Chilled water systems serve multiple cooling tunnels from central plant. Supply water temperature: 2-6°C. Secondary refrigerant (glycol solutions) used when temperatures below 0°C required.
Cascade refrigeration for ultra-low temperature applications (below -40°C for specialized products like ice cream coatings).
Control Strategies
Multi-Zone Temperature Control
Independent zone control maintains optimal temperature profile:
- PID control loops for each zone
- Supply air temperature sensors (0.1°C accuracy)
- Product temperature monitoring via non-contact IR sensors
- Refrigerant valve modulation or variable speed fans for capacity control
Humidity Control Integration
Coupled temperature-humidity control:
- Cooling coil with reheat for dehumidification
- Desiccant systems for precise dew point control (critical for chocolate applications)
- Steam injection humidification for gummy candy conditioning
Control sequence:
- Measure supply air temperature and humidity
- Modulate cooling coil capacity to achieve temperature setpoint
- Adjust reheat to maintain humidity setpoint
- Monitor product and equipment surface temperatures
- Alarm conditions if surfaces approach dew point temperature
Production Integration
Cooling system coordination with upstream processes:
- Cooking temperature feedback adjusts cooling requirements
- Production rate changes modify air circulation and refrigeration capacity
- Product changeover sequences adjust all zone temperatures and humidity levels
- Sanitation mode raises all temperatures for cleaning operations
Energy Efficiency Considerations
Heat recovery from refrigeration condensers provides process heat:
- Warm water generation for cleaning operations
- Building heating during cold weather
- Tempering water for chocolate processing
Variable speed drives on circulation fans reduce energy consumption during reduced production or partial cooling requirements. Fan power varies with cube of speed, providing substantial savings at reduced airflow.
Night setback schedules for packaging areas while maintaining critical storage zones.
Sanitation Requirements
Cooling tunnel design must facilitate cleaning:
- Sloped floors with drains (minimum 1% slope)
- Removable belt sections
- Accessible coil surfaces
- Stainless steel construction in product contact zones
- CIP (clean-in-place) capability for coils and air distribution components
Sanitation cycle heating requirements:
- Raise air temperature to 60-80°C
- Maintain for sufficient time to achieve surface sanitization
- Control condensation during cooldown
- Return to production conditions without product quality impact
Sections
Hard Candy Production HVAC Systems
Environmental control systems for hard candy manufacturing including batch roller cooling, die forming temperature control, low humidity dehumidification (25-35% RH), and sticking prevention through precise climate management.
Caramel Production HVAC Systems
Comprehensive HVAC design for caramel manufacturing facilities including cooking area ventilation, cooling tunnel design, humidity control for crystallization prevention, and wrapping room environmental conditioning systems.
Humidity Control Candy Manufacturing
Advanced HVAC humidity control systems for candy manufacturing facilities including dehumidification strategies, hygroscopic sugar management, and packaging room environmental requirements for confectionery production.