HVAC Systems Encyclopedia

A comprehensive encyclopedia of heating, ventilation, and air conditioning systems

Juice Pasteurization

Juice pasteurization facilities require specialized HVAC and refrigeration systems to support thermal processing equipment, maintain product quality, and maximize energy recovery. The integration of pasteurization equipment with facility cooling systems presents unique opportunities for heat reclamation while managing substantial cooling loads.

Pasteurization Methods

Flash Pasteurization

Flash pasteurization heats juice rapidly to 90-95°C for 15-30 seconds, then cools immediately to prevent product degradation.

Process characteristics:

  • Heating rate: 15-25°C per second
  • Hold time: 15-30 seconds at target temperature
  • Cooling rate: 20-30°C per second
  • Product contact materials: stainless steel 316L
  • Heat transfer coefficient: 3000-5000 W/m²·K

HVAC implications:

The rapid heating and cooling cycles generate substantial heat rejection loads. A typical 5000 L/hr flash pasteurization line rejects 400-600 kW of heat during the cooling phase. This heat must be removed by process cooling water systems or refrigeration.

HTST Plate Heat Exchanger Systems

High Temperature Short Time (HTST) pasteurization uses plate heat exchangers to achieve efficient heat transfer and energy recovery.

System configuration:

  1. Regeneration section (product-to-product heat exchange)
  2. Heating section (hot water or steam)
  3. Holding tube (residence time)
  4. Cooling section (cooling water and chilled water)

Regeneration efficiency: 85-95% heat recovery Typical temperature profile:

Process StageTemperatureHeat Source/Sink
Raw juice inlet4-8°CRefrigerated storage
Pre-heating (regeneration)65-75°CHot pasteurized product
Final heating90-95°CHot water or steam
Hold tube90-95°CInsulated retention
Cooling (regeneration)25-35°CCold raw product
Final cooling4-8°CChilled water 0-2°C

Heat Recovery Systems

Regenerative Heat Exchange

Regenerative sections in HTST systems recover 85-95% of the heat energy, reducing both heating and cooling loads.

Performance factors:

  • Plate spacing: 2.5-5.0 mm
  • Flow velocity: 0.4-1.2 m/s
  • Pressure drop: 50-150 kPa per section
  • Fouling factor: 0.0001-0.0003 m²·K/W (clean juice)

For a 10,000 L/hr juice line:

  • Total heating requirement without regeneration: 1050 kW
  • Heating requirement with 90% regeneration: 105 kW
  • Cooling requirement without regeneration: 1050 kW
  • Cooling requirement with 90% regeneration: 105 kW

Heat Recovery Water Systems

Hot water from the pasteurizer heating section can be recovered for facility heating or Clean-In-Place (CIP) systems.

Recovery applications:

  • CIP pre-rinse water heating (40-60°C)
  • Process area space heating (winter operation)
  • Domestic hot water preheating
  • Bottle/container warming (hot-fill operations)

Heat recovery potential: 150-300 kW for a 10,000 L/hr line operating 16 hours per day.

Post-Pasteurization Cooling

Cooling Requirements

Post-pasteurization cooling prevents product degradation and prepares juice for cold storage or aseptic packaging.

Cooling specifications by packaging type:

Packaging MethodFinal TemperatureCooling TimeCooling Load
Aseptic (cold fill)4-8°C30-60 seconds280-320 kW per 10,000 L/hr
Hot fill85-90°CCooling in containerMinimal process cooling
Refrigerated (pasteurized)2-4°C45-90 seconds300-350 kW per 10,000 L/hr

Two-Stage Cooling

Most juice pasteurization lines employ two-stage cooling to optimize energy efficiency.

Stage 1: Cooling water (10-15°C)

  • Cools product from 35°C to 18-22°C
  • Heat rejection: 180-220 kW per 10,000 L/hr
  • Uses cooling tower water or well water
  • Lower operating cost than mechanical refrigeration

Stage 2: Chilled water (0-2°C)

  • Cools product from 18-22°C to final temperature 4-8°C
  • Refrigeration load: 100-130 kW per 10,000 L/hr
  • Requires mechanical refrigeration
  • Glycol or direct expansion cooling

Cooling Water Systems

Process Cooling Water Loop

Process cooling water serves the first-stage cooling in pasteurizers and various auxiliary cooling loads.

System parameters:

  • Supply temperature: 10-15°C
  • Return temperature: 25-35°C
  • Temperature differential: 15-20°C
  • Flow rate: 50-80 L/min per 1000 L/hr juice production
  • Pump head: 200-350 kPa
  • Piping: stainless steel or PVC Schedule 80

Heat rejection:

Heat is rejected via cooling towers, typically induced-draft or forced-draft designs rated for food processing environments.

Cooling tower specifications (10,000 L/hr line):

  • Heat rejection capacity: 250-350 kW
  • Water flow rate: 800-1000 L/min
  • Approach temperature: 3-5°C
  • Range: 15-20°C
  • Fan power: 5-10 kW

Chilled Water Systems

Chilled water provides final product cooling and maintains cold storage areas.

System design:

  • Supply temperature: 0-2°C
  • Return temperature: 8-12°C
  • Glycol addition: 15-25% propylene glycol (food grade)
  • Freezing point: -8 to -12°C
  • Refrigeration capacity: 120-180 kW per 10,000 L/hr line

Refrigeration plant configuration:

Multiple pasteurization lines are served by central refrigeration plants using ammonia, R-134a, or R-513A. Screw or scroll compressors with flooded shell-and-tube chillers provide optimal performance.

RefrigerantEvaporator TempCondenser TempCOP
Ammonia (R-717)-5°C35°C3.2-3.6
R-134a-5°C35°C2.8-3.2
R-513A-5°C35°C2.9-3.3

Pasteurization Process Controls

Temperature Control

Precise temperature control ensures food safety while maintaining product quality.

Control parameters:

  • Heating section: ±0.5°C of setpoint
  • Hold tube: ±0.3°C of setpoint (critical control point)
  • Cooling section: ±1.0°C of setpoint
  • RTD sensors: Class A (±0.15°C at 0°C)
  • Control valve response time: 2-5 seconds

Safety interlocks:

Flow diversion valve activates if pasteurization temperature falls below minimum threshold, routing product back to raw tank for reprocessing.

Flow Control

Maintaining constant flow rate ensures proper residence time in the hold tube.

  • Flow measurement: magnetic flowmeters (±0.5% accuracy)
  • Flow control: variable frequency drives on product pumps
  • Minimum flow velocity: 0.3 m/s (prevents settling)
  • Maximum flow velocity: 1.5 m/s (limits pressure drop)

Enzyme Inactivation

Pasteurization must inactivate enzymes that cause quality degradation in stored juice.

Target enzymes:

EnzymeFunctionInactivation TempImpact if Active
PectinaseDegrades pectin85-90°C, 30 secCloud loss, clarity
Polyphenol oxidaseOxidizes phenols90-95°C, 15 secBrowning, off-flavors
PeroxidaseOxidation reactions88-92°C, 30 secColor loss, off-flavors
LipoxygenaseLipid oxidation80-85°C, 60 secRancidity in pulpy juice

Heat-resistant peroxidase serves as an indicator enzyme. If peroxidase is inactivated, other enzymes are also inactivated.

Microbial Destruction

Pasteurization eliminates pathogenic microorganisms and extends shelf life.

Target organisms:

  • Pathogenic bacteria: E. coli O157:H7, Salmonella spp.
  • Spoilage organisms: yeasts, molds, lactic acid bacteria
  • Spores: not destroyed (require aseptic processing or hot fill)

Lethality calculations:

The cumulative lethality (F-value) must meet regulatory requirements.

For E. coli O157:H7 in apple juice:

  • Required 5-log reduction
  • D-value at 71.7°C: 0.35 minutes
  • F₇₁.₇ requirement: 1.75 minutes
  • Z-value: 5.6°C

At 90°C pasteurization:

  • Actual lethality: >10 minutes equivalent
  • Safety margin: >5x regulatory requirement

Facility HVAC Integration

Processing Room Conditions

Pasteurization areas require controlled environmental conditions.

Design conditions:

  • Temperature: 18-22°C
  • Relative humidity: 50-60%
  • Air changes: 15-20 ACH
  • Filtration: MERV 13 minimum
  • Positive pressure: +12.5 Pa relative to adjacent areas

Heat gain sources:

  • Pasteurization equipment surface losses: 15-25 kW per line
  • Motor heat gains: 8-12 kW per line
  • Personnel: 4-8 people × 150 W sensible = 0.6-1.2 kW
  • Lighting: 15-20 W/m²

Total cooling load: 35-50 kW per pasteurization line plus standard building loads.

Ventilation Requirements

Steam, hot water, and product vapors require adequate exhaust ventilation.

  • General exhaust: 10-15 ACH
  • Local exhaust at fill points: 200-300 m³/hr per hood
  • Make-up air: 100% of exhaust (conditioned)
  • Steam condensate collection and drainage

Energy Efficiency Optimization

Heat Recovery Maximization

Optimize regeneration section effectiveness:

  • Increase plate area (reduces approach temperature)
  • Maintain clean heat transfer surfaces (CIP frequency)
  • Balance flow rates (equal heat capacity rates)
  • Insulate piping between sections (minimize heat loss)

Increasing regeneration from 85% to 92% reduces heating and cooling loads by 40%.

Variable Flow Control

Implement variable flow in cooling water systems:

  • VFD-controlled cooling water pumps
  • Temperature-based flow modulation
  • Energy savings: 30-50% pump energy during partial load

Free Cooling

During cold weather, cooling towers can provide chilled water directly:

  • Water-side economizer operation
  • Supply temperature: 4-8°C (when ambient wet bulb <0°C)
  • Potential refrigeration energy savings: 60-100% during economizer hours

Aseptic Packaging Integration

Aseptic cold-fill packaging requires sterile product at 4-8°C.

System requirements:

  • Ultra-clean environment (Class 100,000 or better)
  • Positive pressure: +25 Pa
  • HEPA filtration: 99.97% at 0.3 μm
  • Temperature: 18-20°C, humidity: 45-55%
  • Sterile air supply to filling zone

Cooling capacity must maintain product temperature ±1°C through filling operation.

Hot Fill Operations

Hot-fill packaging uses high product temperature to sterilize containers.

Process sequence:

  1. Pasteurization to 90-95°C
  2. Hold at 85-90°C during filling
  3. Container inversion or tunnel treatment
  4. Cooling in containers to 30-35°C
  5. Final cooling to ambient (20-25°C)

HVAC considerations:

  • Minimal process cooling load (cooling in package)
  • High space cooling load from hot containers: 80-120 kW
  • Humidity control (condensation prevention)
  • Ventilation for steam and product vapors

This comprehensive approach to pasteurization facility HVAC design ensures food safety, product quality, and energy efficiency while managing the substantial thermal loads inherent in juice processing operations.