HVAC Systems Encyclopedia

A comprehensive encyclopedia of heating, ventilation, and air conditioning systems

Gravity Recirculation Systems

Thermosiphon Operation Principles

Gravity recirculation systems utilize natural circulation driven by density differences between liquid refrigerant in the supply line and two-phase refrigerant in the return riser. The system operates without mechanical pumps, relying entirely on thermosiphon action created by elevation differences and fluid density gradients.

Fundamental Operating Mechanism:

The driving force for circulation originates from the static pressure difference between the liquid column in the supply line and the lighter two-phase mixture in the suction riser. This pressure differential overcomes flow resistance in piping, evaporator coils, and control devices to maintain continuous refrigerant circulation.

Density-Driven Flow:

The system establishes circulation based on the hydrostatic pressure equation:

ΔP = ρ × g × H

Where:

  • ΔP = pressure difference (Pa)
  • ρ = fluid density (kg/m³)
  • g = gravitational acceleration (9.81 m/s²)
  • H = elevation difference (m)

The effective driving force equals the difference between liquid column pressure and two-phase column pressure:

ΔP_net = (ρ_liquid - ρ_mixture) × g × H

Natural Circulation Driving Force

The circulation rate in gravity systems depends on the balance between available static head and total system resistance. The relationship follows basic fluid mechanics principles for natural convection loops.

Pressure Balance Equation:

ΔP_static = ΔP_friction + ΔP_acceleration + ΔP_minor

Where:

  • ΔP_static = available static head from density difference
  • ΔP_friction = frictional losses in piping and evaporator
  • ΔP_acceleration = momentum changes in flow
  • ΔP_minor = losses through fittings, valves, and restrictions

Circulation Rate Determination:

The system self-regulates to establish a circulation rate where static head exactly equals total resistance. Higher elevation differences or greater density differences increase available driving force and circulation rates.

For a given evaporator heat load Q and refrigerant latent heat h_fg, the required circulation rate depends on the overfeed ratio N:

ṁ_circ = (Q / h_fg) × N

Typical overfeed ratios for gravity systems range from 2.0 to 4.0, lower than pumped systems due to limited available head.

Density Difference Effects

The density gradient between liquid and vapor phases provides the fundamental driving mechanism. For ammonia refrigeration at typical operating conditions:

TemperatureLiquid DensitySaturated Vapor DensityDensity Ratio
-40°F (-40°C)42.5 lb/ft³ (681 kg/m³)0.115 lb/ft³ (1.84 kg/m³)370:1
-20°F (-29°C)41.8 lb/ft³ (670 kg/m³)0.184 lb/ft³ (2.95 kg/m³)227:1
0°F (-18°C)41.0 lb/ft³ (657 kg/m³)0.287 lb/ft³ (4.60 kg/m³)143:1
20°F (-7°C)40.2 lb/ft³ (644 kg/m³)0.436 lb/ft³ (6.98 kg/m³)92:1
40°F (4°C)39.3 lb/ft³ (630 kg/m³)0.648 lb/ft³ (10.4 kg/m³)61:1

Two-Phase Mixture Density:

The effective density of the two-phase mixture in the return riser depends on void fraction, flow regime, and quality. For homogeneous flow assumption:

1/ρ_mixture = x/ρ_vapor + (1-x)/ρ_liquid

Where x represents the average quality in the return line.

For separated flow with slip between phases, void fraction α must be calculated using appropriate correlations (Lockhart-Martinelli, Chisholm, or drift-flux models).

Temperature Impact on Performance:

Lower evaporating temperatures increase density difference and available static head. Systems operating at -40°F have significantly greater driving force than those at 40°F, affecting minimum elevation requirements and maximum achievable circulation rates.

Static Head Requirements

Gravity recirculation systems require minimum elevation differences to overcome system resistance and maintain stable circulation. Insufficient static head results in inadequate circulation rates, incomplete evaporator wetting, and performance degradation.

Minimum Elevation Criteria:

Industry standards typically specify minimum vertical separation between receiver liquid level and evaporator inlet:

  • Low-temperature applications (-40°F to -20°F): 10-15 ft (3-4.5 m)
  • Medium-temperature applications (-20°F to 20°F): 15-20 ft (4.5-6 m)
  • High-temperature applications (20°F to 40°F): 20-30 ft (6-9 m)

Higher temperatures require greater elevation due to reduced density differences.

Available Static Head Calculation:

The usable static head accounts for liquid level variation in the receiver:

H_available = H_total - H_minimum_liquid - H_safety_margin

Where:

  • H_total = elevation from receiver bottom to evaporator inlet
  • H_minimum_liquid = minimum acceptable liquid level in receiver
  • H_safety_margin = safety factor for level fluctuations (typically 1-2 ft)

System Resistance Components:

Total pressure drop includes all flow resistances in the circulation loop:

ComponentTypical Pressure Drop
Liquid supply line0.5-1.5 psi (3.5-10 kPa)
Float chamber/control valve1-3 psi (7-21 kPa)
Evaporator distributor2-5 psi (14-35 kPa)
Evaporator coil (two-phase)3-8 psi (21-55 kPa)
Suction riser (two-phase)1-3 psi (7-21 kPa)
Total system ΔP8-20 psi (55-138 kPa)

The required static head must exceed total system resistance with adequate safety margin:

ΔP_static ≥ 1.5 × ΔP_total (recommended design factor)

Two-Phase Flow Considerations

The suction riser operates in two-phase flow regime, with complex flow patterns depending on velocity, quality, pipe diameter, and orientation. Proper riser design ensures stable operation and prevents liquid accumulation.

Flow Regime Identification:

Vertical upward flow in the suction riser transitions through several regimes as velocity increases:

  1. Bubbly flow: Discrete vapor bubbles in continuous liquid
  2. Slug flow: Large vapor slugs alternating with liquid slugs
  3. Churn flow: Chaotic, oscillatory flow pattern
  4. Annular flow: Liquid film on walls with vapor core
  5. Wispy-annular flow: Annular with liquid droplets entrained

Design for stable annular flow in risers to minimize pressure drop and prevent liquid accumulation.

Void Fraction Calculations:

The Lockhart-Martinelli correlation provides void fraction for two-phase vertical flow:

α = 1 / [1 + 0.28 × X^0.71]

Where X represents the Martinelli parameter:

X² = (dP/dz)_liquid / (dP/dz)_vapor

Minimum Riser Velocity:

To prevent liquid fallback and ensure stable upward flow, minimum vapor velocity must exceed:

V_min = 1000 / √ρ_vapor (ft/min, with ρ in lb/ft³)

Or in SI units:

V_min = 4.1 / √ρ_vapor (m/s, with ρ in kg/m³)

For ammonia at -20°F: V_min ≈ 2330 ft/min (11.8 m/s) For ammonia at 20°F: V_min ≈ 1515 ft/min (7.7 m/s)

Pressure Drop Correlations:

Two-phase frictional pressure gradient in vertical flow:

(dP/dz)_f = (dP/dz)_liquid × φ_L²

Where φ_L represents the two-phase friction multiplier from Lockhart-Martinelli charts or correlations.

System Design Criteria

Comprehensive design of gravity recirculation systems requires coordination of receiver placement, piping sizing, evaporator configuration, and control strategy to achieve reliable operation.

Design Sequence:

  1. Establish evaporator location and capacity requirements
  2. Determine required overfeed ratio (typically 2-4 for gravity systems)
  3. Calculate circulation rate: ṁ_circ = ṁ_evap × N
  4. Size liquid supply line for acceptable pressure drop
  5. Size suction riser for minimum velocity and pressure drop
  6. Calculate total system resistance
  7. Determine minimum static head requirement
  8. Verify available elevation exceeds minimum by safety factor
  9. Select receiver size and location
  10. Design control system and safety features

Liquid Supply Line Sizing:

Size for maximum velocity of 100-150 ft/min (0.5-0.75 m/s) to minimize pressure drop and prevent flashing. Use standard refrigeration pipe sizing tables with correction for overfeed flow rates.

For liquid line pressure drop:

ΔP_liquid = f × (L/D) × (ρV²/2)

Where f represents the Darcy friction factor from Moody diagram or Colebrook equation.

Suction Riser Sizing:

Size risers to maintain minimum velocity under all load conditions while limiting pressure drop. Use dedicated risers for each evaporator in multi-coil installations.

Riser DiameterMin CapacityMax CapacityVelocity Range
1-1/4 in (32 mm)2 tons8 tons1500-3000 ft/min
1-1/2 in (38 mm)3 tons12 tons1500-3000 ft/min
2-1/8 in (54 mm)5 tons20 tons1500-3000 ft/min
2-5/8 in (67 mm)8 tons30 tons1500-3000 ft/min
3-1/8 in (79 mm)12 tons45 tons1500-3000 ft/min

Values shown for ammonia at -20°F evaporating temperature.

Control Device Selection:

Gravity systems commonly employ:

  • Float-operated valves in surge drums or high-pressure receivers
  • Pilot-operated regulators maintaining liquid level
  • Electronic level controls with modulating valves

Avoid excessive restriction in control devices to preserve available static head.

Liquid Column Calculations

Accurate calculation of liquid column pressure requires accounting for refrigerant properties, temperature variations, and piping configuration.

Static Pressure from Liquid Column:

P_static = ρ_liquid × g × H / 144 (psi, with ρ in lb/ft³, H in ft)

P_static = ρ_liquid × g × H / 1000 (kPa, with ρ in kg/m³, H in m)

For ammonia at 90°F in receiver with 20 ft elevation to evaporator:

P_static = 38.2 × 20 / 2.31 = 8.6 psi (59.3 kPa)

Temperature Stratification Effects:

Liquid columns with temperature gradients require integration of density over height:

P_static = g × ∫[0 to H] ρ(z) dz

For linear temperature variation from T₁ to T₂:

ρ(z) = ρ₁ + (ρ₂ - ρ₁) × (z/H)

Subcooling Impact:

Subcooled liquid in the supply line provides additional margin against flashing. The subcooling amount affects system stability and capacity modulation range.

Degree of subcooling = T_sat(P_receiver) - T_liquid

Recommended minimum subcooling: 5-10°F (3-6 K) at evaporator inlet under design conditions.

Applications and Limitations

Gravity recirculation systems suit specific applications where building geometry and refrigeration requirements align with natural circulation capabilities.

Ideal Applications:

  • Industrial refrigeration with low-level machinery room
  • Cold storage with elevated product areas
  • Food processing with basement compressor rooms
  • Ice rinks with sub-floor equipment placement
  • Beverage cooling with rooftop condensers and ground-level serving areas
  • Multi-story facilities with vertical separation

Performance Advantages:

  • No recirculation pump power consumption
  • Reduced mechanical equipment maintenance
  • No pump seal leakage concerns
  • Lower first cost than pumped systems for suitable applications
  • Inherent simplicity and reliability
  • Reduced refrigerant charge compared to DX systems

System Limitations:

  • Requires substantial elevation difference (10-30 ft minimum)
  • Lower overfeed ratios than pumped systems (2-4 vs 3-6)
  • Limited capacity modulation range
  • Restricted horizontal piping runs from receiver to evaporator
  • Not suitable for rooftop evaporators with ground-level equipment
  • Sensitive to elevation changes and system modifications
  • Potential stability issues during load fluctuations

Capacity Constraints:

Maximum practical capacity per evaporator circuit typically limited to:

  • 50 tons (175 kW) for -40°F to -20°F applications
  • 30 tons (105 kW) for -20°F to 20°F applications
  • 20 tons (70 kW) for 20°F to 40°F applications

Larger systems require multiple parallel circuits with individual risers.

Equipment Specifications

Gravity recirculation systems incorporate specialized components designed for natural circulation operation.

Receiver Requirements:

  • Minimum volume: 3-5 minutes of system circulation capacity
  • Liquid level range: 30-70% to maintain adequate head variation
  • Connections: Liquid drain to evaporators, vapor equalization, refrigerant feed
  • Internal baffles to separate liquid from vapor
  • Level indication: Sight glass and/or electronic level sensor
  • Pressure rating: Match system high-side design pressure

Float Chamber Specifications:

Capacity RangeChamber SizeFloat SizeValve Connection
1-5 tons6 in diameter3-4 in3/4 in
5-15 tons8 in diameter4-6 in1 in
15-30 tons10 in diameter6-8 in1-1/4 in
30-50 tons12 in diameter8-10 in1-1/2 in

Float chambers must include:

  • Vapor equalization line to suction
  • Liquid drain to evaporator
  • Cleanout access
  • Pressure relief protection

Evaporator Configuration:

Design evaporators specifically for overfeed operation:

  • Top feed arrangement with overhead distributor
  • Bottom outlet for two-phase mixture
  • Internal baffles to promote uniform liquid distribution
  • Adequate refrigerant inventory capacity
  • Vertical orientation preferred for gravity drainage

Piping Accessories:

  • Manual shutoff valves: Ball or plug valves with full-port design
  • Strainers: 100-mesh screens before float valves
  • Sight glasses: Liquid line and float chamber
  • Thermometer wells: Monitor liquid and suction temperatures
  • Pressure gauges: Receiver, evaporator, and suction
  • Relief devices: Per code requirements

Comparison with Pumped Systems

Selection between gravity and pumped liquid overfeed systems depends on facility layout, capacity requirements, energy considerations, and operational preferences.

FeatureGravity SystemPumped System
Elevation requirement10-30 ft minimumNone
Overfeed ratio2-4 typical3-6 typical
Circulation reliabilityPassive, gravity-drivenActive, pump-dependent
First costLowerHigher
Operating costMinimalPump energy
MaintenanceMinimalPump maintenance
Capacity per circuit20-50 tons max100+ tons possible
Load modulationLimited rangeWide range
System complexitySimpleMore complex
Refrigerant chargeModerateHigher
Evaporator wettingGoodExcellent
Part-load performanceSensitive to load changesStable at all loads

Energy Comparison:

Gravity systems eliminate pump power but may have slightly higher pressure drops due to velocity limitations. For a 100-ton system at -20°F:

  • Pumped system pump power: 3-5 hp (2.2-3.7 kW)
  • Annual energy consumption: 18,000-30,000 kWh
  • Operating cost at $0.10/kWh: $1,800-$3,000/year

Gravity system saves this energy but requires careful design to achieve equivalent performance.

Reliability Considerations:

Gravity systems offer passive operation without mechanical failure modes associated with pumps. However, pumped systems provide more controllable circulation and better performance under varying loads.

Energy Efficiency

Gravity recirculation systems provide energy benefits through elimination of pump power while maintaining efficient refrigerant distribution to evaporators.

Energy Savings Components:

  1. No pump parasitic load: Eliminates 0.5-1.0 kW per 10 tons of refrigeration
  2. Reduced compressor work: Proper overfeed maintains high evaporator efficiency
  3. Lower refrigerant superheat: Complete evaporator wetting improves heat transfer
  4. Minimal throttling losses: Simple float control with low pressure drop

Coefficient of Performance Impact:

Well-designed gravity systems achieve COP values comparable to pumped systems:

COP_gravity ≈ COP_pumped × (1 + P_pump/P_compressor)

For typical industrial refrigeration at -20°F:

  • Compressor power: 0.8 kW/ton
  • Pump power (if used): 0.05 kW/ton
  • COP improvement: ~6%

Part-Load Efficiency:

Gravity systems maintain good efficiency at reduced loads provided:

  • Minimum riser velocity sustained
  • Adequate liquid level maintained in receiver
  • Subcooling preserved at evaporator inlet
  • Load reduction controlled to prevent circulation instability

Optimization Strategies:

  • Maximize static head within practical building constraints
  • Minimize liquid line length and fittings
  • Size risers for stable operation across load range
  • Employ variable-speed compressors for capacity modulation
  • Maintain optimal refrigerant charge for level control
  • Monitor performance and adjust overfeed ratio seasonally

Operating Cost Analysis:

Over 20-year system life, energy savings from eliminated pump power offset higher piping costs for most gravity-suitable applications. Total cost of ownership favors gravity systems when:

H_available > H_minimum + 50% Annual operating hours > 4,000 hours Energy cost > $0.08/kWh

System Stability and Control

Gravity recirculation systems require careful attention to stability under transient conditions and varying loads.

Stability Criteria:

The system achieves stable equilibrium when circulation rate self-regulates to match evaporator load. Instability manifests as:

  • Hunting in liquid level
  • Surging in suction pressure
  • Temperature oscillations
  • Intermittent liquid carryover

Critical Parameters for Stable Operation:

  • Receiver volume sufficient to buffer load changes (3-5 minute capacity)
  • Float chamber response time matched to load variation rate
  • Adequate subcooling margin (minimum 5°F) to prevent flashing
  • Proper riser sizing to maintain velocity at minimum load
  • Controlled load reduction rate to prevent vapor lock

Control System Requirements:

Implement basic monitoring and protection:

  • Low-level alarm on receiver
  • High-level alarm on float chamber
  • Suction superheat monitoring
  • Evaporator outlet temperature indication
  • Manual/automatic switchover capability

Advanced systems may incorporate:

  • Modulating liquid feed valves
  • Variable compressor capacity control
  • Automated refrigerant migration
  • Predictive load management

Startup and Shutdown Procedures:

Proper procedures ensure reliable operation:

Startup sequence:

  1. Verify receiver liquid level at 50-70%
  2. Confirm all manual valves in correct position
  3. Establish condenser operation
  4. Start compressor at minimum capacity
  5. Open liquid supply to evaporators gradually
  6. Monitor circulation establishment (5-15 minutes)
  7. Increase capacity to match load

Shutdown sequence:

  1. Reduce compressor capacity gradually
  2. Allow evaporators to pump down partially
  3. Close liquid supply valves
  4. Pump down remaining refrigerant to receiver
  5. Shut down compressor
  6. Close manual isolation valves

Troubleshooting Common Issues

Gravity system problems typically relate to inadequate circulation, liquid accumulation, or control malfunctions.

SymptomProbable CauseCorrective Action
Inadequate coolingInsufficient circulation rateVerify static head, check for restrictions
High superheatLow overfeed ratioIncrease liquid feed, check float operation
Liquid carryoverExcessive circulationReduce liquid feed, verify riser sizing
Unstable operationControl huntingAdjust float sensitivity, increase receiver volume
Pressure drop excessiveUndersized pipingReplace with larger diameter, reduce restrictions
Low receiver levelRefrigerant charge lossAdd charge, check for leaks
Evaporator floodingFloat valve stuck openClean/replace float valve, check for debris

Performance Verification:

Monitor key parameters to verify proper operation:

  • Suction superheat: 8-15°F (4-8 K) typical
  • Evaporator temperature drop: 3-8°F (2-4 K)
  • Receiver level: 40-60% normal operating range
  • Circulation ratio: Verify against design calculations

Regular inspection and maintenance preserve system performance and prevent degradation over time.