HVAC Systems Encyclopedia

A comprehensive encyclopedia of heating, ventilation, and air conditioning systems

Coaxial Evaporators

Coaxial evaporators employ a tube-in-tube (concentric tube) configuration where refrigerant and secondary fluid flow in separate passages with counterflow arrangement. This design provides compact heat exchange with high efficiency for liquid cooling applications, particularly in water chillers, heat pumps, and process cooling systems.

Construction and Geometry

Tube-in-Tube Configuration

The fundamental geometry consists of:

Inner Tube: Contains one fluid (typically refrigerant during evaporation)

  • Standard copper tube: 3/8", 1/2", 5/8" OD
  • Smooth or internally enhanced surface
  • Wall thickness per ASTM B88 Type L or K

Outer Tube: Contains the counterflowing fluid (typically water or glycol solution)

  • Larger diameter copper tube: 5/8", 7/8", 1-1/8" OD
  • Creates annular passage for secondary fluid flow
  • Maintains structural integrity and pressure containment

Annular Space Dimensions:

  • Hydraulic diameter of annulus: D_h = D_outer - D_inner
  • Typical annular gap: 1/8" to 3/8" radial clearance
  • Flow area affects velocity and heat transfer coefficient

Enhanced Surface Technologies

Internal Rifling (Inner Tube):

  • Helical grooves with spiral angles 18-30°
  • Groove depth: 0.008" to 0.015"
  • Increases internal surface area by 30-60%
  • Enhances refrigerant-side boiling coefficient

Microfin Tubes:

  • Fine helical fins with heights 0.008" to 0.012"
  • Fin density: 60-80 fins per circumference
  • Provides 80-100% surface area increase
  • Improves nucleate boiling and convective heat transfer

Corrugated Inner Surface:

  • Cross-corrugated or herringbone patterns
  • Creates turbulence and disrupts boundary layer
  • Effective for single-phase and two-phase flow

Assembly Methods

Brazed Construction:

  • Permanent joint using copper-phosphorus or silver alloy
  • High thermal conductivity at joint
  • Operating pressures to 600 psig
  • Temperature limit: 250°F continuous

Mechanical Swaging:

  • Expansion of inner tube into outer tube
  • Creates intimate contact for heat transfer
  • Allows field repair and tube replacement
  • Requires precise dimensional control

Triple-Wall Designs:

  • Intermediate barrier tube for double containment
  • Leak detection passage between primary barriers
  • Required for ammonia/water systems per codes
  • Safety consideration for toxic refrigerants

Heat Transfer Analysis

Overall Heat Transfer Coefficient

The thermal resistance network for coaxial geometry:

Resistance ComponentExpressionTypical Value
Refrigerant convection1/(h_i × A_i)h_i = 800-2500 Btu/hr-ft²-°F
Inner tube conductionln(r_o/r_i)/(2πkL)Negligible for copper
Annulus convection1/(h_o × A_o)h_o = 300-1200 Btu/hr-ft²-°F
Fouling (if applicable)R_f/AR_f = 0.0005-0.001 hr-ft²-°F/Btu

Overall Coefficient: U = 1 / [1/(h_i × A_i/A_o) + t_wall/(k_copper × A_log/A_o) + 1/h_o + R_f]

Typical overall U-values: 200-500 Btu/hr-ft²-°F for water cooling applications

Refrigerant-Side Heat Transfer

Nucleate Boiling Regime:

  • Dominant at low vapor qualities (x < 0.3)
  • Heat flux dependent: q" = C × ΔT_sat^n
  • Enhanced by surface roughness and nucleation sites
  • Correlations: Cooper, Gorenflo for pool boiling modified for flow

Convective Boiling Regime:

  • Increases importance at higher qualities (x > 0.4)
  • Flow pattern transitions: bubbly → slug → annular
  • Two-phase multiplier approach: h_tp = h_lo × F(x, properties)
  • Velocity effects become dominant

Enhancement Factor:

  • Rifled tubes: 1.5-2.5× smooth tube performance
  • Microfin tubes: 1.8-3.0× smooth tube performance
  • Quality dependent: maximum enhancement at x = 0.3-0.6
  • Pressure drop penalty: 1.3-1.8× smooth tube

Annulus-Side Heat Transfer

Turbulent Flow (Re > 4000):

  • Dittus-Boelter correlation: Nu = 0.023 Re^0.8 Pr^0.4
  • Hydraulic diameter: D_h = 4A_flow/P_wetted = D_outer - D_inner
  • Fully developed flow assumption after L/D_h > 10

Laminar Flow (Re < 2300):

  • Nusselt number depends on thermal boundary conditions
  • Constant heat flux: Nu = 4.36 (fully developed)
  • Constant wall temperature: Nu = 3.66 (fully developed)
  • Entrance effects significant for short coils

Velocity Optimization:

  • Higher velocity → higher h_o → better heat transfer
  • Pressure drop increases as ΔP ∝ V^2
  • Economic velocity range: 3-8 ft/s for water
  • Erosion concerns above 10 ft/s for copper

Counterflow Performance Advantages

Temperature Profiles

Effectiveness: ε = Q_actual / Q_max = (T_out - T_in)_water / (T_evap - T_in)_water

Counterflow provides:

  • Maximum temperature differential maintained throughout length
  • Higher LMTD compared to parallel flow: LMTD_counter > LMTD_parallel
  • Enables closer approach temperatures
  • Better thermodynamic efficiency

Log Mean Temperature Difference: LMTD = (ΔT_1 - ΔT_2) / ln(ΔT_1/ΔT_2)

Where:

  • ΔT_1 = T_evap - T_water,out (refrigerant inlet end)
  • ΔT_2 = T_evap - T_water,in (refrigerant outlet end)

Approach Temperature

Typical Values:

  • Water chillers: 3-5°F approach
  • Glycol systems: 5-8°F approach
  • Direct expansion: 2-4°F approach
  • Flooded evaporators: 1-3°F approach

Approach temperature impacts:

  • Evaporator size and cost
  • System efficiency (lower approach → higher suction pressure → higher COP)
  • Control stability
  • Part-load performance

Pressure Drop Considerations

Refrigerant-Side Pressure Drop

Components:

  1. Acceleration: ΔP_accel due to density change during evaporation
  2. Friction: ΔP_friction from wall shear stress
  3. Gravitational: ΔP_grav (orientation dependent)

Two-Phase Multiplier Method: ΔP_tp = ΔP_lo × Φ²_lo

Where:

  • ΔP_lo = pressure drop if total mass flowed as liquid
  • Φ²_lo = two-phase multiplier (function of quality, fluid properties)
  • Lockhart-Martinelli parameter X_tt characterizes flow regime

Typical Values:

  • Smooth tubes: 2-5 psi total evaporator drop
  • Enhanced tubes: 3-8 psi total evaporator drop
  • Design limit: < 2°F saturation temperature change

Water-Side Pressure Drop

Annular Passage: ΔP = (f × L/D_h × ρV²/2) / 144

Friction factor correlations:

  • Turbulent: f = 0.079/Re^0.25 (smooth pipe approximation)
  • Design range: 5-15 ft water per circuit
  • Pump power impact must be considered in efficiency analysis

Design Specifications

Performance Parameters

ParameterTypical RangeDesign Considerations
Capacity per circuit1-10 tonsModular assembly for larger loads
Tube length10-50 ftBalances pressure drop vs. size
Refrigerant velocity300-1500 fpmQuality dependent, exit velocity
Water velocity2-8 ft/sBalance heat transfer and ΔP
Heat flux3,000-12,000 Btu/hr-ft²Based on inner tube surface area
Mass flux (refrigerant)50,000-200,000 lb/hr-ft²Affects flow regime and h_i
Refrigerant charge0.5-2.0 lb/tonLow charge characteristic
Approach temperature2-8°FApplication specific

Dimensional Standards

Inner Tube ODOuter Tube ODAnnular GapTypical Capacity
3/8"5/8"1/8"1-2 tons
1/2"7/8"3/16"2-4 tons
5/8"1-1/8"1/4"4-7 tons
3/4"1-3/8"5/16"7-10 tons

Application Domains

Water Chillers

Residential and Light Commercial:

  • Heat pump water heaters (integrated or remote)
  • Capacity range: 1-5 tons
  • Compact footprint advantage
  • Low refrigerant charge (environmental benefit)
  • Brazed construction typical

Direct Expansion Systems:

  • Precise superheat control essential
  • Thermostatic expansion valve or electronic expansion valve
  • Exit superheat: 5-10°F typical
  • Liquid return risk mitigation

Heat Pump Applications

Water-Source Heat Pumps:

  • Evaporator mode during heating season
  • Reversing operation requires oil return considerations
  • Ground loop connections
  • Antifreeze solutions (glycol) common

Desuperheater Integration:

  • Upstream water heating before main condenser
  • Triple-wall design may be required
  • Pressure relief coordination
  • Thermal expansion provisions

Process Cooling

Advantages:

  • Direct refrigerant-to-process fluid heat exchange
  • Eliminates intermediate heat exchanger
  • Faster temperature response
  • Precise temperature control capability

Limitations:

  • Single process fluid circuit per refrigerant circuit
  • Pressure drop limits on long piping runs
  • Flow balancing in multiple parallel circuits
  • Not suitable for very high flow rates

Industrial Refrigeration

Liquid Overfeed Systems:

  • Coaxial evaporator as liquid cooling element
  • Recirculation ratio: 2:1 to 4:1
  • Separator vessel after evaporator
  • Lower refrigerant-side pressure drop
  • More stable operation

Cascade Systems:

  • Interstage heat exchanger between high and low stage
  • Counterflow maximizes efficiency
  • Typically larger industrial sizes
  • Ammonia low stage / CO₂ or HFC high stage common

Installation Requirements

Orientation Considerations

Horizontal Installation (Preferred):

  • Counterflow: water enters at refrigerant outlet end
  • Proper refrigerant distribution throughout length
  • Oil return to compressor maintained
  • Simplifies piping and support

Vertical Installation:

  • Upward refrigerant flow recommended (downward water flow)
  • Gravity assists oil entrainment and return
  • Higher pressure drop on refrigerant side
  • May require higher mass flux to ensure annular flow

Pitch Requirements:

  • Minimum 1/4" per 10 ft toward compressor
  • Facilitates oil return during operation
  • Prevents liquid trapping during shutdown
  • Vapor line pitch critical for reliability

Piping Connections

Refrigerant Side:

  • Distributor at inlet for uniform liquid feeding (DX mode)
  • Sight glass before evaporator to verify subcooled liquid
  • Superheat sensor at outlet (bulb location and insulation)
  • Suction accumulator consideration for systems with variable load

Water Side:

  • Isolation valves for service access
  • Pressure relief valve if isolation valves installed
  • Flow switch or sensor for freeze protection
  • Air vent at high point, drain at low point
  • Strainer before evaporator to prevent fouling

Thermal Expansion and Support

Linear Expansion: α = 9.5 × 10⁻⁶ in/in-°F for copper

For 20 ft coil with 60°F temperature swing: ΔL = 20 ft × 12 in/ft × 9.5×10⁻⁶ × 60°F = 0.137 inch

Support Spacing:

  • Horizontal runs: support every 6-10 ft
  • Avoid rigid clamping that constrains expansion
  • Allow axial movement at one end
  • Insulation support separate from tube support

Vibration Isolation:

  • Flexible connections at compressor discharge and suction
  • Avoid resonant frequencies with compressor operation
  • Secure mounting to prevent fatigue failure
  • Consider water hammer effects in liquid lines

Performance Monitoring

Key Indicators

Operating Temperatures:

  • Entering water temperature (EWT)
  • Leaving water temperature (LWT)
  • Refrigerant saturation temperature (via pressure measurement)
  • Superheat at evaporator outlet
  • Subcooling at evaporator inlet (for DX systems)

Temperature Metrics:

  • Approach: T_evap - T_water,out (expect 3-5°F for water)
  • ΔT across evaporator: T_in - T_out water side (capacity indication)
  • Superheat: T_suction - T_evap (control parameter, 5-10°F target)

Pressure Measurements:

  • Evaporator inlet pressure (saturated liquid in flooded/overfeed)
  • Evaporator outlet pressure (suction pressure)
  • Pressure drop across evaporator (diagnostic for fouling/restrictions)
  • Water-side pressure drop (pump performance and fouling indicator)

Degradation Mechanisms

Fouling:

  • Water-side scaling from hardness (calcium carbonate)
  • Biological fouling in open loop systems
  • Reduced U-value and capacity
  • Increased pressure drop on affected side
  • Maintenance: chemical cleaning or mechanical brushing (requires disassembly for coaxial)

Refrigerant-Side Issues:

  • Oil accumulation (reduces heat transfer surface)
  • Non-condensables (raise pressure, reduce capacity)
  • Moisture contamination (ice formation at expansion device)
  • Proper system design prevents: oil return velocity, filter-driers, evacuation

Mechanical Degradation:

  • Erosion at high velocity points (>10 ft/s water)
  • Corrosion from water chemistry (pH, chlorides, dissolved oxygen)
  • Stress corrosion cracking at brazed joints
  • Fatigue from thermal cycling and vibration

Advantages and Limitations

Advantages

Compact Footprint:

  • High heat transfer per unit volume
  • Minimal space requirements
  • Suitable for tight installations
  • Lower material costs for small capacities

Low Refrigerant Charge:

  • Environmental benefit (reduced GWP impact)
  • Safety consideration for flammable refrigerants (A2L, A3 classifications)
  • Regulatory compliance advantages
  • Lower refrigerant cost

High Efficiency:

  • Counterflow provides maximum thermodynamic effectiveness
  • Enhanced surfaces boost performance further
  • Close approach temperatures achievable
  • Good part-load performance

Direct Heat Exchange:

  • No intermediate fluid loops required
  • Faster response to load changes
  • Simpler system architecture
  • Reduced auxiliary energy consumption

Limitations

Capacity Constraints:

  • Practical limit ~10 tons per circuit
  • Multiple parallel circuits required for larger loads
  • Flow distribution challenges with parallel circuits
  • Individual circuit control complexity

Maintenance Access:

  • Brazed construction prevents internal cleaning
  • Must replace entire coaxial assembly if fouled
  • No access for tube-side inspection
  • External water treatment critical

Pressure Drop:

  • Annular passage limits water flow rate
  • Long lengths increase pressure drop
  • Pump energy consideration
  • May require larger sizes to reduce ΔP

Application Constraints:

  • Not suitable for very high water flow rates
  • Limited to clean water/glycol solutions
  • Single-pass design limits temperature change per circuit
  • Freeze risk in low-temperature applications requires glycol

Selection Methodology

Design Process

  1. Establish Requirements:

    • Cooling capacity (tons or Btu/hr)
    • Water flow rate and temperature range
    • Refrigerant type and operating conditions
    • Pressure drop limits (water and refrigerant)
    • Space constraints
  2. Initial Sizing:

    • Calculate heat duty: Q = m_water × cp × ΔT
    • Estimate overall U-value: 250-400 Btu/hr-ft²-°F typical starting point
    • Determine required surface area: A = Q / (U × LMTD)
    • Select tube diameters based on flow rates
  3. Detailed Analysis:

    • Calculate refrigerant-side heat transfer coefficient (h_i)
    • Calculate water-side heat transfer coefficient (h_o)
    • Compute overall U-value
    • Iterate on length and diameter if needed
  4. Pressure Drop Verification:

    • Check refrigerant-side pressure drop (< 2°F saturation change)
    • Check water-side pressure drop (< 15 ft head typical)
    • Adjust velocities if needed
  5. Performance Validation:

    • Verify approach temperature meets application needs
    • Check exit superheat for DX systems
    • Confirm capacity at off-design conditions
    • Ensure oil return velocity maintained

Selection Criteria

FactorCoaxial PreferredOther Type Preferred
Capacity< 10 tons per circuit> 20 tons total
SpaceVery limitedAmple
Refrigerant chargeMinimize (safety, cost)Not critical
Water qualityExcellent (low fouling)Poor (needs cleaning access)
ApplicationResidential, light commercialIndustrial, large commercial
ControlPrecise temperature controlBroad temperature range
MaintenanceReplacement acceptableRegular cleaning required

Future Developments

Enhanced Surfaces:

  • Advanced microstructures for higher boiling coefficients
  • Porous metallic coatings for nucleation control
  • Gradient structures optimized along tube length
  • Additive manufacturing for complex internal geometries

Alternative Materials:

  • Stainless steel for corrosive applications
  • Titanium for seawater and aggressive chemicals
  • Polymer-lined copper for water quality protection
  • Aluminum for weight reduction and specific refrigerants

Design Optimization:

  • Variable diameter along length to maintain optimal velocities
  • Hybrid smooth/enhanced sections tuned to quality profile
  • Integrated circuiting for multiple zones
  • CFD-optimized entrance regions

Low-GWP Refrigerants:

  • Adaptation to A2L refrigerants (R-32, R-454B, R-1234yf)
  • Pressure rating increases for high-pressure refrigerants
  • Material compatibility with HFO blends
  • Natural refrigerants (R-290 propane, R-744 CO₂) considerations