HVAC Systems Encyclopedia

A comprehensive encyclopedia of heating, ventilation, and air conditioning systems

Heat Rejection

Heat Rejection Fundamentals

Heat rejection in refrigeration systems encompasses the total thermal energy discharged from the condenser to the ambient environment. This thermal load exceeds the evaporator capacity by the amount of compressor work input converted to heat.

Energy Balance

The condenser must reject the sum of:

  • Heat absorbed in the evaporator (Q_evap)
  • Heat of compression (W_comp)
  • Heat from auxiliary equipment (pumps, fans)
  • Superheat removed in the desuperheating zone
  • Latent heat removed during condensation
  • Subcooling heat removed below saturation temperature

Total heat rejection equation:

Q_cond = Q_evap + W_comp

Or expressed in terms of refrigerant mass flow:

Q_cond = ṁ × (h_2 - h_4)

Where:

  • Q_cond = condenser heat rejection rate (Btu/hr or kW)
  • Q_evap = evaporator capacity (Btu/hr or kW)
  • W_comp = compressor power input (Btu/hr or kW)
  • ṁ = refrigerant mass flow rate (lbm/hr or kg/s)
  • h_2 = enthalpy at compressor discharge (Btu/lbm or kJ/kg)
  • h_4 = enthalpy at condenser exit (Btu/lbm or kJ/kg)

Heat Rejection Ratio

The ratio of condenser heat rejection to evaporator capacity:

HRR = Q_cond / Q_evap = 1 + (W_comp / Q_evap) = 1 + (1 / COP)

Typical heat rejection ratios by application:

ApplicationEvaporating TempCondensing TempTypical HRR
Air Conditioning40°F to 50°F95°F to 115°F1.15 to 1.25
Medium Temp Refrigeration0°F to 20°F90°F to 105°F1.25 to 1.35
Low Temp Refrigeration-20°F to -10°F90°F to 100°F1.40 to 1.60
Ultra-Low Temp-40°F to -30°F85°F to 95°F1.70 to 2.00

Condenser Heat Load Calculations

Design Heat Load

Calculate condenser capacity based on compressor performance and operating conditions.

Step 1: Determine refrigerant state points

Using refrigerant properties at design conditions:

  • State 1: Evaporator outlet (superheated vapor)
  • State 2: Compressor discharge (superheated vapor)
  • State 3: Condenser mid-point (saturated vapor/liquid)
  • State 4: Condenser outlet (subcooled liquid)

Step 2: Calculate enthalpy changes

For R-410A at typical air conditioning conditions:

  • Evaporating: 45°F (h_1 = 162.5 Btu/lbm)
  • Condensing: 105°F (h_3 = 50.2 Btu/lbm)
  • Compressor discharge: 140°F (h_2 = 175.3 Btu/lbm)
  • Subcooling: 10°F (h_4 = 46.8 Btu/lbm)

Step 3: Apply energy balance

Q_cond = ṁ × (h_2 - h_4)
       = ṁ × (175.3 - 46.8)
       = ṁ × 128.5 Btu/lbm

Step 4: Determine mass flow rate

From evaporator capacity:

ṁ = Q_evap / (h_1 - h_4)

For 36,000 Btu/hr (3 ton) evaporator capacity:

ṁ = 36,000 / (162.5 - 46.8)
  = 311 lbm/hr

Step 5: Calculate condenser heat rejection

Q_cond = 311 × 128.5
       = 39,964 Btu/hr
       ≈ 40,000 Btu/hr (3.33 tons)

Heat rejection ratio: 40,000 / 36,000 = 1.11

Condenser Zone Heat Transfer

The condenser operates in three distinct zones with different heat transfer characteristics:

ZoneTemperature RangeHeat Transfer% of Total
DesuperheatingT_discharge to T_satSingle-phase vapor cooling10-20%
CondensingT_sat (constant)Phase change (latent heat)70-85%
SubcoolingT_sat to T_outletSingle-phase liquid cooling5-15%

Desuperheating heat removal:

Q_desup = ṁ × c_p,vapor × (T_2 - T_sat)

Condensing heat removal:

Q_cond_latent = ṁ × h_fg

Subcooling heat removal:

Q_subcool = ṁ × c_p,liquid × (T_sat - T_4)

Where:

  • c_p,vapor = specific heat of superheated vapor (Btu/lbm·°F)
  • c_p,liquid = specific heat of subcooled liquid (Btu/lbm·°F)
  • h_fg = latent heat of vaporization (Btu/lbm)
  • T_sat = saturation temperature at condensing pressure (°F)

COP Relationship to Condensing Temperature

System coefficient of performance directly correlates with condensing temperature. Lower condensing temperatures improve efficiency by reducing compression ratio.

Carnot COP Relationship

Theoretical maximum efficiency:

COP_Carnot = T_evap / (T_cond - T_evap)

Where temperatures are absolute (°R or K).

Example: Refrigeration system

  • T_evap = 20°F = 479.67°R
  • T_cond = 100°F = 559.67°R
COP_Carnot = 479.67 / (559.67 - 479.67)
          = 479.67 / 80
          = 6.0

Actual COP typically 40-60% of Carnot COP due to real-world inefficiencies.

Condensing Temperature Impact

Effect of condensing temperature on actual COP:

For R-404A refrigeration system at 0°F evaporating temperature:

Condensing Temp (°F)Compression RatioDischarge Temp (°F)COP% Change
803.21102.85baseline
903.71252.55-10.5%
1004.31402.28-20.0%
1104.91552.05-28.1%
1205.61701.85-35.1%

Key observation: Each 10°F increase in condensing temperature reduces COP by approximately 8-10%.

Energy Consumption Impact

Power consumption increases exponentially with condensing temperature:

W_comp ∝ (P_cond / P_evap)^((k-1)/k)

Where:

  • k = ratio of specific heats (≈1.13 for refrigerants)
  • P_cond = condensing pressure (absolute)
  • P_evap = evaporating pressure (absolute)

Practical impact on operating cost:

For 100 ton refrigeration system operating 6,000 hours annually:

  • Baseline: 95°F condensing, 150 kW
  • High condensing: 105°F condensing, 172 kW

Annual energy increase:

ΔE = (172 - 150) kW × 6,000 hr = 132,000 kWh

At $0.12/kWh: $15,840 additional annual cost

Optimization Strategy

Maintain lowest practical condensing temperature by:

  • Maximizing condenser airflow (fan speed control)
  • Ensuring adequate condenser surface area
  • Regular coil cleaning
  • Utilizing free cooling when available
  • Implementing head pressure control in cold weather

Air-Cooled vs Water-Cooled Comparison

Selection between air-cooled and water-cooled condensers involves trade-offs in performance, efficiency, cost, and site requirements.

Performance Characteristics

ParameterAir-CooledWater-CooledEvaporative
Condensing Temp (design)Ambient +20-25°FWater temp +10°FAmbient WB +15-20°F
Typical summer condensing115-125°F95-105°F85-95°F
Approach to ambient20-25°F DB10-15°F to water15-20°F WB
COP (relative)1.0 (baseline)1.15-1.251.20-1.35
Part-load efficiencyGoodExcellentVery good

Air-Cooled Condensers

Advantages:

  • No water consumption
  • Lower installation cost
  • Minimal maintenance
  • No freeze protection in water systems
  • No water treatment required
  • Suitable for water-scarce regions
  • No cooling tower or water-cooled equipment

Disadvantages:

  • Higher condensing temperatures
  • Lower efficiency (higher energy cost)
  • Large footprint and weight
  • Noise generation
  • Performance degradation in high ambient
  • Limited capacity in extreme heat
  • Reduced equipment life due to higher pressures

Heat transfer equation:

Q = U × A × LMTD

Where:

  • U = overall heat transfer coefficient: 8-15 Btu/hr·ft²·°F
  • A = heat transfer surface area (ft²)
  • LMTD = log mean temperature difference (°F)

Typical design parameters:

  • Face velocity: 400-600 fpm
  • Fin spacing: 10-16 fins per inch
  • Tube arrangement: Staggered or in-line
  • Refrigerant circuits: Multiple parallel paths
  • Material: Copper tubes with aluminum fins

Water-Cooled Condensers

Advantages:

  • Lower condensing temperatures
  • Higher COP (15-25% improvement)
  • Smaller physical size
  • Quieter operation
  • Better capacity control
  • Consistent performance
  • Extended equipment life

Disadvantages:

  • Water consumption (evaporation + blowdown)
  • Cooling tower required
  • Higher installation complexity
  • Water treatment necessary
  • Fouling potential
  • Freeze protection needed
  • Higher maintenance requirements
  • Susceptible to water quality issues

Shell-and-tube heat transfer:

Q = U × A × LMTD

LMTD = (ΔT₁ - ΔT₂) / ln(ΔT₁/ΔT₂)

Where:

  • U = 150-300 Btu/hr·ft²·°F (clean tubes)
  • ΔT₁ = T_cond - T_water,in
  • ΔT₂ = T_cond - T_water,out

Typical design parameters:

  • Water velocity: 3-10 fps (optimal: 6-8 fps)
  • Fouling factor: 0.00025-0.0005 hr·ft²·°F/Btu
  • Temperature rise: 10-20°F
  • Approach: 5-10°F
  • Flow rate: 2.5-3.0 gpm per ton

Water flow calculation:

GPM = (Q_cond × 12) / (500 × ΔT_water)

For 100 ton system (Q_cond = 1,500,000 Btu/hr, ΔT = 10°F):

GPM = (1,500,000 × 12) / (500 × 10)
    = 300 gpm

Evaporative Condensers

Operating principle: Combines water evaporation and air cooling for enhanced heat transfer.

Advantages:

  • Lowest condensing temperatures
  • Highest efficiency (20-35% better than air-cooled)
  • Smaller footprint than air-cooled
  • Less water use than cooling tower
  • Compact design
  • Good part-load performance

Disadvantages:

  • Water consumption (though less than tower)
  • Water treatment required
  • Freeze protection necessary
  • Plume potential
  • Higher maintenance than air-cooled
  • Legionella risk (requires protocols)
  • Local codes may restrict use

Heat transfer mechanisms:

  1. Evaporative cooling (dominant):
Q_evap = ṁ_water × h_fg,water
  1. Sensible cooling:
Q_sens = ṁ_air × c_p,air × ΔT

Typical performance:

  • Approach to wet bulb: 10-15°F
  • Water flow: 1.5-2.0 gpm per ton
  • Air velocity through media: 400-600 fpm
  • Evaporation rate: 3-5% of circulation rate

Economic Comparison

Life-cycle cost analysis (100 ton system, 20 years, 4,000 hr/yr):

Cost CategoryAir-CooledWater-CooledEvaporative
Equipment cost$45,000$65,000$55,000
Installation cost$8,000$25,000$12,000
Annual energy cost$28,800$24,000$22,500
Annual water cost$0$4,200$2,400
Annual maintenance$1,200$3,500$2,200
20-year LCC$653,000$721,000$565,000

Assumptions: $0.12/kWh, $8/1000 gal water, 3% discount rate

Ambient Temperature Effects

Ambient conditions significantly impact condenser performance, capacity, and efficiency across all condenser types.

Air-Cooled Condenser Response

Condensing temperature relationship:

T_cond = T_ambient,DB + ΔT_approach

Where ΔT_approach typically ranges 20-30°F depending on:

  • Condenser size (larger = smaller approach)
  • Airflow rate (higher = smaller approach)
  • Coil condition (fouling increases approach)

Capacity variation with ambient temperature:

For R-410A air conditioning system:

Ambient Temp (°F)Condensing Temp (°F)System CapacityCompressor PowerEER
75100107%93%11.5
85110103%97%10.6
95120100%100%10.0
10513096%106%9.1
11514091%113%8.1

Performance degradation in extreme heat:

  • Reduced cooling capacity when needed most
  • Increased energy consumption
  • Higher discharge temperatures
  • Potential high-pressure cutout
  • Accelerated oil breakdown
  • Shortened equipment life

Water-Cooled Condenser Response

Performance tied to cooling tower wet bulb temperature:

T_cond = T_WB + ΔT_tower_approach + ΔT_range + ΔT_condenser_approach

Typical values:

  • Tower approach: 7-10°F
  • Tower range: 10-15°F
  • Condenser approach: 5-8°F

Example at 78°F wet bulb:

T_cond = 78 + 8 + 12 + 6 = 104°F

Seasonal performance variation:

SeasonWet Bulb (°F)Tower Water (°F)Condensing (°F)COP Multiplier
Winter3545551.35
Spring5565751.20
Summer7585951.00
Fall6070801.15

Evaporative Condenser Response

Governed by wet bulb temperature with superior performance:

T_cond = T_WB + 10 to 20°F

Performance across ambient conditions:

Dry Bulb (°F)Wet Bulb (°F)Condensing (°F)Advantage vs Air-Cooled
95708530°F lower
100759030°F lower
105789332°F lower
110809535°F lower

High Ambient Operation Strategies

Design considerations for hot climates:

  1. Oversized condensers

    • 115-125% of standard capacity
    • Reduces approach temperature
    • Improves efficiency
    • Provides capacity margin
  2. Variable speed condenser fans

    • Modulate airflow to maintain target condensing pressure
    • Reduce energy at part load
    • Extend fan motor life
    • Reduce noise during cooler periods
  3. Precooling systems

    • Evaporative precoolers for air-cooled units
    • 10-20°F reduction in entering air temperature
    • Water consumption: 2-4 gpm per 100 tons
    • Effectiveness: 70-85%
  4. Adiabatic cooling

    • Intermittent water spray on coils
    • Lower water use than evaporative
    • Prevents scale buildup
    • 5-15°F temperature reduction

Precooler effectiveness:

Effectiveness = (T_DB,entering - T_DB,leaving) / (T_DB,entering - T_WB)

For 80% effectiveness at 105°F DB, 75°F WB:

T_leaving = 105 - 0.80 × (105 - 75) = 81°F

Condensing temperature reduction: 20-25°F

Low Ambient Operation

Cold weather presents challenges maintaining adequate head pressure.

Minimum condensing pressure requirements:

  • Ensure proper expansion valve operation
  • Maintain adequate subcooling
  • Prevent liquid flashing
  • Support oil return

Head pressure control methods:

  1. Fan cycling

    • Simple on/off control
    • Limited modulation
    • Pressure cycling
  2. Variable speed fans

    • Continuous modulation
    • Stable pressure control
    • Energy savings
  3. Dampers

    • Airflow restriction
    • Lower cost
    • Less efficient
  4. Flooded condenser

    • Reduces active surface area
    • Maintains pressure
    • Requires receiver capacity
  5. Hot gas bypass

    • Artificial loading
    • Energy penalty
    • Immediate response

Equipment Sizing

Proper condenser sizing ensures adequate heat rejection under all operating conditions while balancing first cost and operating efficiency.

Sizing Methodology

Step 1: Determine design heat rejection

Q_design = Q_evap × HRR × SF

Where:

  • Q_evap = design evaporator capacity
  • HRR = heat rejection ratio (1.15-1.50)
  • SF = safety factor (1.05-1.15)

Step 2: Establish design conditions

Air-cooled:

  • Ambient dry bulb: 95°F to 115°F (location-dependent)
  • Target condensing: Ambient +20-25°F

Water-cooled:

  • Entering water temp: 85°F (typical)
  • Water temperature rise: 10°F
  • Target condensing: 95-105°F

Evaporative:

  • Ambient wet bulb: 75-78°F
  • Target condensing: WB +15-20°F

Step 3: Calculate required heat transfer area

A = Q / (U × LMTD)

Step 4: Select equipment from manufacturer data

Match calculated capacity to available models considering:

  • Available space
  • Weight limitations
  • Sound requirements
  • Maintenance access
  • Future expansion

Air-Cooled Condenser Sizing

Example: 50 ton refrigeration system

Design parameters:

  • Evaporator capacity: 50 tons = 600,000 Btu/hr
  • HRR: 1.30 (medium temp application)
  • Safety factor: 1.10
  • Ambient design: 95°F
  • Target condensing: 105°F

Heat rejection calculation:

Q_cond = 600,000 × 1.30 × 1.10 = 858,000 Btu/hr

Surface area estimation:

Assuming:

  • U = 12 Btu/hr·ft²·°F
  • Refrigerant temp: 105°F
  • Air entering: 95°F
  • Air leaving: 102°F (estimate)
  • LMTD ≈ 6°F
A = 858,000 / (12 × 6) = 11,900 ft²

This is gross face area × rows deep.

Fan power:

Typical: 0.10-0.15 HP per ton of rejection

HP = 858,000 / 12,000 × 0.12 = 8.6 HP

Select (2) condenser units with 5 HP fans each.

Water-Cooled Condenser Sizing

Example: 100 ton chiller

Design parameters:

  • Chiller capacity: 100 tons = 1,200,000 Btu/hr
  • HRR: 1.20
  • Condensing temp: 105°F
  • Entering water: 85°F
  • Leaving water: 95°F

Heat rejection:

Q_cond = 1,200,000 × 1.20 = 1,440,000 Btu/hr

Water flow rate:

GPM = Q / (500 × ΔT) = 1,440,000 / (500 × 10) = 288 gpm

Use 300 gpm for safety margin.

Heat transfer area:

Shell-and-tube condenser:

  • U = 200 Btu/hr·ft²·°F (clean, includes fouling factor)
  • ΔT₁ = 105 - 85 = 20°F
  • ΔT₂ = 105 - 95 = 10°F
  • LMTD = (20 - 10) / ln(20/10) = 14.4°F
A = 1,440,000 / (200 × 14.4) = 500 ft²

Condenser pressure drop:

Target: 10-15 psi water side

  • Affects pump selection
  • Impacts operating cost
  • Consider fouling allowance

Oversizing Considerations

Benefits of larger condensers:

  • Lower condensing temperatures
  • Improved efficiency
  • Greater capacity in high ambient
  • Reduced compressor stress
  • Extended equipment life
  • Better part-load performance
  • Fouling tolerance

Economic analysis:

Incremental cost vs. energy savings:

Condenser SizeFirst CostCondensing TempAnnual EnergyNPV (20 yr)
100% (baseline)$15,000105°F$24,000$15,000
115%$17,250100°F$22,560$7,365
130%$19,50095°F$21,360$2,880
150%$22,50090°F$20,400-$3,960

Optimal sizing: 115-130% provides best life-cycle value

Practical limits:

  • Minimum head pressure control required when oversized
  • Diminishing returns beyond 130%
  • Space constraints
  • Weight considerations
  • Installation complexity

Energy Efficiency

Condenser optimization directly impacts system energy consumption and operating costs throughout equipment life.

Efficiency Metrics

Energy Efficiency Ratio (EER):

EER = Q_evap / W_total (Btu/W·hr)

Seasonal Energy Efficiency Ratio (SEER):

Weighted average accounting for varying conditions:

SEER = Total cooling (Btu) / Total energy (W·hr)

Coefficient of Performance (COP):

COP = Q_evap / W_comp

Integrated Energy Efficiency Ratio (IEER):

For commercial equipment:

IEER = 0.02A + 0.617B + 0.238C + 0.125D

Where A, B, C, D are EER values at 100%, 75%, 50%, 25% load.

Condenser Efficiency Factors

Heat transfer effectiveness:

ε = (T_ref,in - T_ref,out) / (T_ref,in - T_amb)

Higher effectiveness indicates better heat transfer.

Approach temperature:

Lower approach = higher efficiency

Air-cooled target: 15-20°F Water-cooled target: 5-10°F Evaporative target: 10-15°F to WB

Fouling impact:

Heat transfer degradation:

U_fouled = 1 / (1/U_clean + R_fouling)

Where R_fouling typical values:

  • Air-cooled: 0.0005-0.001 hr·ft²·°F/Btu
  • Water-cooled: 0.00025-0.0005 hr·ft²·°F/Btu

Fouling energy penalty:

20% reduction in U-value → 8-12% efficiency loss

Optimization Strategies

1. Condenser Temperature Reset

Reduce condensing temperature when ambient permits:

Reset schedule example:

Outdoor Temp (°F)Condensing Setpoint (°F)Energy Savings
95+105baseline
85-94956-8%
75-848512-15%
65-747518-22%
<656525-30%

2. Variable Speed Condenser Fans

Fan power varies with cube of speed:

P₂ = P₁ × (N₂/N₁)³

At 75% speed: P₂ = 0.75³ × P₁ = 0.42 × P₁ (58% savings)

Part-load fan energy reduction:

Load (%)Fixed SpeedVariable SpeedSavings
100100%100%0%
75100%56%44%
50100%25%75%
25100%8%92%

3. Free Cooling / Economizer

Utilize low ambient temperatures for direct heat rejection.

Water-side economizer:

When T_WB < 50-55°F, bypass chiller:

  • Cooling tower provides chilled water directly
  • Chiller remains off
  • 90-95% energy reduction
  • Requires plate-and-frame heat exchanger

Air-side economizer:

When T_DB < 55-60°F:

  • Outside air provides cooling directly
  • DX system remains off
  • 80-90% energy reduction
  • Common in data centers

4. Condenser Maintenance

Cleaning frequency and impact:

Maintenance LevelFouling FactorEfficiencyAnnual Cost Impact
Poor (yearly)0.00280%+25%
Fair (semi-annual)0.00190%+10%
Good (quarterly)0.000595%+5%
Excellent (monthly)0.000298%baseline

Cleaning methods:

  • High-pressure water
  • Chemical cleaning (water-cooled)
  • Brush cleaning (tube-side)
  • Fin combing (air-cooled)
  • Coil coatings (corrosion protection)

5. Subcooling Optimization

Increase subcooling for improved efficiency:

Subcooling benefits:

Subcooling (°F)Refrigerating EffectNet CapacityCOP Impact
0100%100%baseline
5103%102%+2%
10106%104%+4%
15109%106%+6%
20112%107%+7%

Diminishing returns beyond 15-20°F subcooling.

Mechanical subcooling methods:

  • Dedicated subcooler circuit
  • Subcooling heat exchanger
  • Suction-liquid heat exchanger

ASHRAE Guidelines

ASHRAE provides comprehensive standards for condenser design, installation, and operation.

Relevant Standards

ASHRAE Standard 15-2019: Safety Standard for Refrigeration Systems

  • Machinery room requirements
  • Ventilation for refrigerant leaks
  • Pressure relief sizing
  • Emergency procedures

ASHRAE Standard 34-2019: Designation and Safety Classification of Refrigerants

  • Refrigerant properties
  • Safety classifications (A1, A2L, etc.)
  • Exposure limits
  • Compatibility requirements

ASHRAE Standard 90.1-2019: Energy Standard for Buildings

  • Minimum efficiency requirements
  • Equipment performance tables
  • Economizer requirements
  • Control sequences

ASHRAE Handbook - Refrigeration (2022):

  • Chapter 3: Refrigerant and heat transfer
  • Chapter 4: Refrigeration system design
  • Chapter 13: Condensers

Design Conditions

ASHRAE cooling design conditions (Chapter 14, Climatic Design Information):

Selection criteria:

  • 0.4% design conditions: Extreme design
  • 1.0% design conditions: Standard design
  • 2.0% design conditions: Economical design

Example cities (1.0% cooling design):

LocationDry Bulb (°F)Wet Bulb (°F)Recommended Condensing
Phoenix, AZ10971130°F (air) / 85°F (evap)
Houston, TX9578115°F (air) / 95°F (evap)
Chicago, IL9175110°F (air) / 90°F (evap)
Miami, FL9179110°F (air) / 95°F (evap)
Denver, CO9363110°F (air) / 78°F (evap)

Efficiency Requirements

ASHRAE 90.1-2019 minimum efficiency (air-cooled condensing units):

Equipment TypeSize CategoryMinimum EER
Air conditioners<65,000 Btu/h11.0
Air conditioners≥65,000 and <135,000 Btu/h10.8
Air conditioners≥135,000 and <240,000 Btu/h10.0
Air conditioners≥240,000 and <760,000 Btu/h9.5

Water-cooled positive displacement chillers:

Size CategoryMinimum COP (Path A)Minimum IPLV
<75 tons4.205.05
≥75 and <150 tons4.455.20
≥150 and <300 tons4.905.60
≥300 tons5.506.15

Installation Requirements

Clearances (ASHRAE Standard 15):

Air-cooled condensers:

  • Service side: 36 inches minimum
  • Air inlet: 12 inches minimum
  • Air discharge: 60 inches minimum (no obstructions)
  • Between units: 12-24 inches

Water-cooled condensers:

  • Tube removal: 1 × tube length
  • Access for cleaning: 30 inches minimum
  • Pressure relief discharge: Per Section 9

Mounting:

  • Vibration isolation per ASHRAE Applications
  • Structural support for weight and seismic
  • Drainage for condensate (evaporative/air-cooled)
  • Electrical disconnects within sight

Maintenance Recommendations

ASHRAE Handbook - Refrigeration, Chapter 3:

Monthly:

  • Visual inspection
  • Check operating pressures
  • Verify fan operation
  • Monitor approach temperatures

Quarterly:

  • Clean coils (air-cooled)
  • Check water quality (water-cooled)
  • Inspect for leaks
  • Verify control sequences

Semi-annually:

  • Detailed coil cleaning
  • Water treatment analysis
  • Performance testing
  • Calibrate controls

Annually:

  • Tube cleaning (water-cooled)
  • Eddy current testing (tube integrity)
  • Fan motor service
  • Complete system analysis
  • Efficiency verification

Water Quality Standards

ASHRAE Guideline 12-2020: Minimizing the Risk of Legionellosis

Cooling tower water chemistry targets:

ParameterAcceptable RangeTarget
pH7.0-9.07.5-8.5
Conductivity<5,000 μS/cm1,000-3,000 μS/cm
Total Hardness<800 ppm as CaCO₃200-500 ppm
Alkalinity100-500 ppm150-300 ppm
Chlorides<500 ppm<250 ppm
Total Dissolved Solids<3,500 ppm1,500-2,500 ppm
Cycles of Concentration2-63-4

Condenser fouling factors (ASHRAE Handbook):

Water-cooled condensers:

  • City water: 0.00025 hr·ft²·°F/Btu
  • Cooling tower: 0.0005 hr·ft²·°F/Btu
  • Treated water: 0.0003 hr·ft²·°F/Btu
  • River water: 0.001-0.002 hr·ft²·°F/Btu

Conclusion

Heat rejection optimization represents one of the most effective strategies for improving refrigeration system efficiency and reducing operating costs. Understanding the fundamental relationships between condenser design, operating conditions, and system performance enables informed decisions regarding equipment selection, installation configuration, and operational control strategies.

Key principles:

  • Lower condensing temperature directly improves COP and reduces energy consumption
  • Each 10°F reduction in condensing temperature typically improves efficiency by 8-10%
  • Proper condenser sizing (115-130% of minimum) provides optimal life-cycle value
  • Regular maintenance preserves heat transfer effectiveness and prevents efficiency degradation
  • Ambient conditions dictate maximum achievable performance; design for local climate
  • Water-cooled and evaporative systems offer superior efficiency but require water management
  • Variable speed fan control and condensing temperature reset provide significant energy savings
  • ASHRAE standards establish minimum performance requirements and best practices

Comprehensive heat rejection analysis during design, combined with ongoing optimization during operation, maximizes system efficiency, reduces environmental impact, and minimizes life-cycle costs.