Global Cooling Efficiency Metrics and Standards

Global Cooling Efficiency Metrics and Standards

Cooling efficiency metrics vary significantly across global markets, reflecting different climate patterns, testing methodologies, and regulatory frameworks. Understanding these metrics enables accurate equipment comparison, proper system selection, and compliance with regional energy standards.

Fundamental Efficiency Metrics

Energy Efficiency Ratio (EER)

EER represents instantaneous cooling efficiency at specific test conditions:

EER = Q_cooling / W_input

Where:

  • Q_cooling = Cooling capacity (Btu/h or W)
  • W_input = Electrical power input (W or Wh)

Standard Test Conditions:

RegionIndoor ConditionsOutdoor ConditionsStandard
USA80°F DB / 67°F WB95°F DBAHRI 210/240
Europe27°C DB / 19°C WB35°C DBEN 14511
ISO27°C DB / 19°C WB35°C DBISO 5151
China27°C DB / 19.5°C WB35°C DBGB/T 7725

EER provides single-point efficiency but does not capture part-load or seasonal performance variations.

Coefficient of Performance (COP)

COP uses consistent units for both cooling output and power input:

COP = Q_cooling(W) / W_input(W)

Conversion Relationship:

EER(Btu/Wh) = COP × 3.412

COP is the international standard for efficiency expression, used in ISO standards and most global markets outside North America.

Seasonal Efficiency Metrics

Seasonal Energy Efficiency Ratio (SEER)

SEER accounts for varying load conditions throughout the cooling season:

SEER = ΣQ_cooling(i) / ΣW_input(i)

Where summation occurs across weighted temperature bins representing typical seasonal conditions.

SEER2 Calculation (2023 US Standard):

Uses outdoor temperatures from 65°F to 104°F in 5°F increments, weighted by frequency:

Temperature BinWeight FactorCompressor State
82°F0.214Cycling
87°F0.231Cycling/Continuous
92°F0.216Continuous
97°F0.161Continuous
102°F0.094Continuous

SEER2 (AHRI 210/240-2023) replaced SEER (2008 standard) with more realistic testing including external static pressure requirements.

European Seasonal Coefficient of Performance (SCOP)

SCOP for cooling (sometimes designated SEER_ON or ηs,c) follows EN 14825:

SCOP_cooling = Q_cooling,annual / E_annual

Calculation incorporates:

  • Four temperature bins: 20°C, 25°C, 30°C, 35°C
  • Part-load ratios: 100%, 74%, 47%, 21%
  • Standby and off-mode losses
  • Degradation coefficient for cycling

Climate Zones:

ZoneDesignationReference CityDesign Temp
AverageAStrasbourg35°C
WarmerWAthens35°C
ColderCHelsinki35°C

China Seasonal Performance Factor (CSPF)

CSPF applies to air conditioners under GB 21455:

CSPF = Total_cooling_output(Wh) / Total_energy_input(Wh)

Test Points:

Outdoor TempIndoor TempLoad %Weight
27°C27°C/19°C WB50%42%
32°C27°C/19°C WB75%27%
35°C27°C/19°C WB100%21%
40°C27°C/19°C WB125%10%

China’s testing methodology emphasizes high-temperature performance relevant to southern climate zones.

Indian Seasonal Energy Efficiency Ratio (ISEER)

ISEER under IS 1391 (Part 1):

ISEER = Total_annual_cooling / Total_annual_energy

Weighted Bins:

Based on 1600 hours annual operation:

  • 24°C outdoor: 45% weight
  • 28°C outdoor: 30% weight
  • 32°C outdoor: 20% weight
  • 37°C outdoor: 5% weight

Indoor conditions fixed at 27°C DB / 19°C WB.

Annual Energy Efficiency Ratio (AEER) - Japan

Japan’s JIS C 9612 defines AEER:

AEER = Annual_cooling_output(MJ) / Annual_power_consumption(kWh)

Uses regional climate data for Tokyo, with intermediate and minimum capacity operation weighted by occurrence frequency.

Global Standards Comparison

Testing Standard Frameworks

StandardRegionScopeKey Features
AHRI 210/240USA/CanadaUnitary AC & HPSEER2, EER2, external static pressure
EN 14511EuropeAC & chillersPart 1-4: terms, testing, marking, requirements
EN 14825EuropeHeat pumpsSeasonal calculation, climate zones
ISO 5151InternationalAC & HPReference standard, widely adopted
GB/T 7725ChinaRoom ACFixed and variable speed units
GB 21455ChinaMinimum efficiencyCSPF requirements, energy grades
JIS C 9612JapanRoom ACAPF (heating), AEER (cooling)
IS 1391IndiaRoom ACISEER, star rating program
AS/NZS 3823Australia/NZAC performanceEER, AEER for labeling

Efficiency Metric Conversion

Approximate conversions between seasonal metrics:

SEER2 ≈ SEER × 0.95

SCOP_cooling ≈ SEER ÷ 3.6

CSPF ≈ SEER × 1.05 (rough approximation)

Note: Direct conversion is imprecise due to different climate assumptions, test procedures, and weighting factors.

Minimum Efficiency Requirements

Regional Minimum Standards (2024)

RegionMetricMinimum Split ACEffective Date
USASEER213.4-14.3 (regional)Jan 2023
CanadaSEER13.0-14.0 (regional)Jan 2017
EUSCOPClass D minimumMar 2021
ChinaCSPF3.2 (Grade 3)Jul 2020
IndiaISEER3.1 (2-star)Jan 2018
JapanAPF5.8 (cooling 4.0kW)Apr 2027
AustraliaAEERVarious by capacityMultiple phases

Energy Labeling Programs

Label Format Comparison

USA - EnergyGuide: Yellow label showing estimated annual energy cost, SEER2 rating, and comparison range.

Europe - EU Energy Label: A-G scale (revised 2021), annual energy consumption in kWh, cooling capacity, sound power.

China - CEL: 5-grade scale (Grade 1 highest), CSPF value, cooling capacity, power input.

India - BEE Star Rating: 1-5 star scale, ISEER value, annual energy consumption estimate.

Japan - Unified Energy Label: Multi-year targets (up to 4 stars), annual energy consumption, market position indicator.

Physical Principles and Measurement

Seasonal metrics capture two critical thermodynamic realities:

Part-Load Degradation: Compressor cycling introduces losses from refrigerant migration, repeated startup transients, and control system inefficiencies. The degradation coefficient (C_D) quantifies efficiency reduction:

COP_cyclic = COP_steady × (1 - C_D × (1 - PLR))

Where PLR = part load ratio.

Temperature Dependence: Carnot efficiency establishes theoretical limits:

COP_Carnot = T_indoor / (T_outdoor - T_indoor)

Real systems achieve 40-60% of Carnot efficiency, with the ratio improving at lower lift conditions.

Testing Procedure Variations

Key procedural differences affecting measured efficiency:

Air Flow Measurement: Nozzle chamber (ISO 5151), pitot traverse (AHRI), or air enthalpy method (EN 14511).

Psychrometric Control: Indoor/outdoor chamber tolerances range from ±0.3°C (ISO) to ±0.5°F (AHRI).

Refrigerant Charge: Subcooling method, superheat method, or manufacturer specification.

Defrost Credit: European standards provide energy credit for reverse-cycle defrost losses; US standards do not.

System Selection Implications

Higher seasonal efficiency metrics indicate:

  • Superior part-load performance through variable-capacity compressors
  • Optimized refrigerant circuit design for varying conditions
  • Advanced controls minimizing cycling losses
  • Efficient fan and pump systems

When comparing equipment across regions, verify test standard alignment and climate suitability rather than relying solely on metric values.