Density Temperature Effects
Physical Principles
The density of secondary coolants varies with temperature according to fundamental thermodynamic relationships governing molecular spacing and thermal expansion. Understanding these effects is critical for proper system design, expansion tank sizing, pump selection, and fluid charge calculations.
Fundamental Density-Temperature Relationship
Density decreases with increasing temperature due to thermal expansion of the liquid phase. For most secondary coolants, this relationship follows:
General Density Equation:
ρ(T) = ρ₀ / [1 + β(T - T₀)]
Where:
- ρ(T) = density at temperature T (lb/ft³ or kg/m³)
- ρ₀ = reference density at T₀ (lb/ft³ or kg/m³)
- β = volumetric thermal expansion coefficient (1/°F or 1/°C)
- T = operating temperature (°F or °C)
- T₀ = reference temperature (°F or °C)
Thermal Expansion Coefficient
The volumetric thermal expansion coefficient quantifies the fractional change in volume per degree temperature change:
Volumetric Expansion:
β = (1/V)(∂V/∂T)ₚ = -(1/ρ)(∂ρ/∂T)ₚ
Where measurements occur at constant pressure.
Relationship to Linear Expansion:
For isotropic materials: β ≈ 3α
Where α is the linear coefficient of thermal expansion.
Glycol Solution Density Properties
Ethylene Glycol Density Data
Ethylene glycol solutions exhibit concentration and temperature-dependent density variations critical for system calculations.
Density at 68°F (20°C) by Concentration:
| Concentration (% by weight) | Density (lb/ft³) | Density (kg/m³) | Specific Gravity |
|---|---|---|---|
| 0 (Pure Water) | 62.30 | 998.2 | 0.998 |
| 10 | 63.15 | 1011.8 | 1.013 |
| 20 | 63.95 | 1024.6 | 1.026 |
| 30 | 64.70 | 1036.6 | 1.038 |
| 40 | 65.40 | 1047.8 | 1.049 |
| 50 | 66.05 | 1058.2 | 1.060 |
| 60 | 66.60 | 1067.0 | 1.069 |
| 70 | 67.10 | 1075.0 | 1.077 |
| 80 | 67.50 | 1081.4 | 1.083 |
| 90 | 67.85 | 1087.0 | 1.089 |
| 100 (Pure EG) | 68.15 | 1091.6 | 1.093 |
Temperature Correction Factors:
Density at temperature T: ρ(T) = ρ₂₀°C × f(T)
| Temperature (°F) | Temperature (°C) | Correction Factor f(T) |
|---|---|---|
| -40 | -40 | 1.055 |
| -20 | -29 | 1.045 |
| 0 | -18 | 1.035 |
| 20 | -7 | 1.025 |
| 32 | 0 | 1.020 |
| 40 | 4 | 1.015 |
| 60 | 16 | 1.005 |
| 68 | 20 | 1.000 |
| 80 | 27 | 0.995 |
| 100 | 38 | 0.985 |
| 120 | 49 | 0.975 |
| 140 | 60 | 0.965 |
| 160 | 71 | 0.955 |
| 180 | 82 | 0.945 |
| 200 | 93 | 0.935 |
Propylene Glycol Density Data
Propylene glycol exhibits slightly different density characteristics than ethylene glycol.
Density at 68°F (20°C) by Concentration:
| Concentration (% by weight) | Density (lb/ft³) | Density (kg/m³) | Specific Gravity |
|---|---|---|---|
| 0 (Pure Water) | 62.30 | 998.2 | 0.998 |
| 10 | 63.10 | 1010.9 | 1.012 |
| 20 | 63.85 | 1023.0 | 1.025 |
| 30 | 64.55 | 1034.2 | 1.036 |
| 40 | 65.20 | 1044.6 | 1.046 |
| 50 | 65.80 | 1054.2 | 1.056 |
| 60 | 66.35 | 1063.0 | 1.065 |
| 70 | 66.85 | 1071.0 | 1.073 |
| 80 | 67.30 | 1078.2 | 1.080 |
| 90 | 67.70 | 1084.6 | 1.086 |
| 100 (Pure PG) | 68.05 | 1090.0 | 1.092 |
Thermal Expansion Coefficients (Propylene Glycol):
| Concentration (% by weight) | β at 68°F (10⁻⁴/°F) | β at 20°C (10⁻⁴/°C) |
|---|---|---|
| 0 (Pure Water) | 1.17 | 2.07 |
| 25 | 3.00 | 5.40 |
| 50 | 3.50 | 6.30 |
| 75 | 4.00 | 7.20 |
| 100 (Pure PG) | 4.40 | 7.92 |
Brine Solution Density Properties
Calcium Chloride Brine
Calcium chloride solutions provide freeze protection for low-temperature applications.
Density at 68°F (20°C):
| Concentration (% by weight) | Density (lb/ft³) | Density (kg/m³) | Specific Gravity |
|---|---|---|---|
| 0 | 62.30 | 998.2 | 0.998 |
| 5 | 63.50 | 1017.4 | 1.019 |
| 10 | 64.75 | 1037.4 | 1.039 |
| 15 | 66.05 | 1058.2 | 1.060 |
| 20 | 67.40 | 1079.8 | 1.082 |
| 25 | 68.80 | 1102.2 | 1.104 |
| 30 | 70.25 | 1125.4 | 1.127 |
Thermal Expansion Coefficient:
For CaCl₂ solutions: β ≈ 2.5 × 10⁻⁴ to 3.5 × 10⁻⁴ /°F (4.5 × 10⁻⁴ to 6.3 × 10⁻⁴ /°C)
Sodium Chloride Brine
Sodium chloride provides economical freeze protection with moderate temperature range.
Density at 68°F (20°C):
| Concentration (% by weight) | Density (lb/ft³) | Density (kg/m³) | Specific Gravity |
|---|---|---|---|
| 0 | 62.30 | 998.2 | 0.998 |
| 5 | 63.35 | 1015.0 | 1.017 |
| 10 | 64.45 | 1032.6 | 1.034 |
| 15 | 65.55 | 1050.2 | 1.052 |
| 20 | 66.70 | 1068.6 | 1.070 |
| 23.3 (Eutectic) | 67.35 | 1079.0 | 1.081 |
System Design Calculations
Volume Change with Temperature
The total volume change in a closed system between temperatures T₁ and T₂:
Volume Expansion Equation:
ΔV = V₁ × β × (T₂ - T₁)
Where:
- ΔV = volume change (gal or L)
- V₁ = initial system volume (gal or L)
- β = volumetric expansion coefficient (1/°F or 1/°C)
- T₂ - T₁ = temperature change (°F or °C)
Percent Volume Change:
% Volume Change = β × ΔT × 100
Expansion Tank Sizing
Proper expansion tank sizing accommodates fluid volume changes while maintaining system pressure.
Minimum Expansion Tank Volume:
For Diaphragm Tanks:
V_t = (V_s × ΔV_f × [(P_m + 14.7)/(P_m - P_f + 14.7)]) / (1 - P_a/P_m)
Where:
- V_t = minimum tank volume (gal)
- V_s = system fluid volume (gal)
- ΔV_f = volumetric expansion factor (dimensionless)
- P_m = maximum system pressure (psig)
- P_f = fill pressure (psig)
- P_a = atmospheric pressure = 14.7 psia
Simplified Expansion Tank Formula:
V_t = V_s × [β × ΔT / (1 - (P_f + 14.7)/(P_m + 14.7))]
Volumetric Expansion Factors (ΔV_f):
| Fluid | Temp Range (°F) | ΔV_f | Temp Range (°C) | ΔV_f |
|---|---|---|---|---|
| Water | 40 to 200 | 0.0359 | 4 to 93 | 0.0359 |
| 30% EG | 0 to 200 | 0.0480 | -18 to 93 | 0.0480 |
| 50% EG | -20 to 200 | 0.0540 | -29 to 93 | 0.0540 |
| 30% PG | 0 to 200 | 0.0495 | -18 to 93 | 0.0495 |
| 50% PG | -20 to 200 | 0.0560 | -29 to 93 | 0.0560 |
System Fill Volume Calculations
Determining proper system charge requires accounting for density at fill temperature.
Mass-Based Fill Calculation:
m = ρ_fill × V_system
Where:
- m = total fluid mass (lb or kg)
- ρ_fill = density at fill temperature (lb/ft³ or kg/m³)
- V_system = total system volume (ft³ or m³)
Volume Conversion:
V_gal = V_ft³ × 7.48052
V_L = V_m³ × 1000
Pumping Head Corrections
Density variations affect static head calculations in vertical systems.
Static Head Pressure:
P_static = ρ × g × h / 144
Where:
- P_static = static pressure (psi)
- ρ = fluid density (lb/ft³)
- g = gravitational acceleration = 32.174 ft/s²
- h = vertical height (ft)
- 144 = conversion factor (in²/ft²)
Static Head per Foot of Elevation:
For water at 68°F: 0.433 psi/ft For 30% ethylene glycol at 68°F: 0.446 psi/ft For 50% ethylene glycol at 68°F: 0.455 psi/ft
Density Correction Factor:
P_glycol = P_water × (ρ_glycol / ρ_water)
ASHRAE References
Design values and calculation methods derived from:
ASHRAE Handbook - Fundamentals:
- Chapter 31: Physical Properties of Secondary Coolants (Brines)
- Table 3: Thermophysical Properties of Ethylene Glycol Solutions
- Table 4: Thermophysical Properties of Propylene Glycol Solutions
- Table 7: Properties of Aqueous Solutions of Calcium Chloride
- Table 8: Properties of Aqueous Solutions of Sodium Chloride
ASHRAE Handbook - HVAC Systems and Equipment:
- Chapter 13: Hydronic Heating and Cooling System Design
- Section on Secondary Coolants and Freeze Protection
Engineering Design Considerations
System Volume Calculations
Accurate total system volume determination is essential for expansion tank sizing and fluid charge calculations.
System Volume Components:
Piping Volume:
- V_pipe = (π/4) × D² × L × n
- Account for all supply, return, and branch piping
Equipment Volume:
- Heat exchangers: manufacturer data
- Air handling units: coil manufacturer data
- Buffer tanks: calculated or manufacturer volume
- Chiller evaporator: manufacturer data
Fitting and Valve Allowance:
- Add 5-10% for fittings, valves, and miscellaneous
Total System Volume:
V_total = V_piping + V_equipment + V_fittings
Temperature Range Considerations
Design for the full temperature swing the system will experience.
Critical Temperature Points:
Minimum Fill Temperature:
- Typically outdoor ambient during installation
- May be 40-50°F in cold climates
Maximum Operating Temperature:
- Design supply or return temperature
- Consider upset conditions and safety factors
Design Temperature Differential:
- ΔT_design = T_max - T_fill
- Use for expansion calculations
Concentration Effects on Density
Glycol concentration must be considered in density calculations.
Concentration Selection Criteria:
Freeze Protection:
- Determine lowest ambient or process temperature
- Add 10-15°F safety margin
- Select minimum concentration from freeze point data
Density Impact:
- Higher concentrations increase density
- Affects pump head and system static pressure
- Influences expansion tank sizing
Performance Optimization:
- Use minimum concentration for required protection
- Reduces viscosity and improves heat transfer
- Minimizes pumping energy
Expansion Accommodation Methods
Systems must accommodate thermal expansion through various means.
Open Systems:
- Vented to atmosphere
- Free expansion into open tank
- No pressurization concerns
- Limited to low-temperature applications
Closed Systems - Compression Tank:
- Air cushion compresses with expansion
- Requires periodic air charging
- Air absorption over time reduces capacity
- Mostly obsolete for new construction
Closed Systems - Diaphragm Tank:
- Membrane separates fluid from air charge
- Prevents air absorption
- Factory-pressurized air side
- Standard for modern hydronic systems
- Requires proper sizing calculation
Closed Systems - Bladder Tank:
- Replaceable bladder isolates fluid
- Similar function to diaphragm
- Serviceable bladder element
- Higher initial cost
Pressure Relief Considerations
Thermal expansion creates pressure rise that must be safely relieved.
Pressure Relief Valve Sizing:
Required capacity based on thermal expansion rate and valve response time. Per ASME Section IV:
Relief Capacity:
Q = (V_s × β × ΔT × ρ × C_p × ΔT_max) / (t × 3600)
Where:
- Q = relief capacity (Btu/hr)
- t = time to relieve (hours)
- C_p = specific heat (Btu/lb·°F)
Standard Practice:
- Provide pressure relief valve on systems >15 psig
- Set relief pressure below maximum equipment rating
- Typical settings: 30-50 psig for standard systems
- Pipe relief discharge to visible location
Instrumentation Requirements
Monitor density-related parameters for proper system operation.
Key Monitoring Points:
System Pressure:
- Expansion tank connection point
- High point in system
- Pump suction (NPSH verification)
Temperature:
- Supply and return temperatures
- Expansion tank location temperature
- Fill temperature during charging
Fluid Level/Volume:
- Visual level gauge on compression tanks
- Pressure indication on diaphragm tanks
- Makeup water metering
Concentration Verification:
- Refractometer testing
- Specific gravity measurement
- Freeze point testing
Seasonal Effects
Annual temperature cycles create expansion and contraction patterns.
Annual Cycle Considerations:
Summer Expansion:
- Warmest fill condition
- Maximum system pressure
- Potential relief valve operation
Winter Contraction:
- Coldest system condition
- Minimum system pressure
- Potential for air ingestion if pressure too low
Fill Pressure Selection:
- Must prevent cavitation at pump suction year-round
- Maintain minimum positive pressure at all points
- Typical fill: 12-15 psig for systems <50 ft height
High-Rise Building Applications
Vertical height creates significant static pressure variations.
Static Pressure Gradient:
ΔP_static = (ρ × g × h) / 144
For 100 ft elevation change:
- Water: 43.3 psi
- 30% EG: 44.6 psi
- 50% EG: 45.5 psi
Design Implications:
Pressure Zoning:
- Separate systems for pressure zones
- Typically zone every 300-400 ft
- Intermediate heat exchangers between zones
Expansion Tank Location:
- Place at point of no pressure change
- Typically on pump suction
- Account for elevation head to all points
Fill Pressure Calculation:
- Must overcome static head to highest point
- Add NPSH requirement
- Add safety margin (5-10 psi)
Practical Application Examples
Example 1: Expansion Tank Sizing
Given:
- System volume: 500 gallons
- Fluid: 30% propylene glycol
- Fill temperature: 50°F
- Maximum temperature: 180°F
- Fill pressure: 15 psig
- Maximum pressure: 50 psig
Solution:
Temperature change: ΔT = 180 - 50 = 130°F
Expansion coefficient for 30% PG: β = 3.0 × 10⁻⁴ /°F
Volumetric expansion: ΔV_f = β × ΔT = 3.0 × 10⁻⁴ × 130 = 0.039
Tank volume: V_t = 500 × [0.039 / (1 - (15+14.7)/(50+14.7))] V_t = 500 × [0.039 / (1 - 0.459)] V_t = 500 × 0.072 = 36 gallons
Select: 40-gallon diaphragm expansion tank (next standard size)
Example 2: System Fill Calculation
Given:
- Total system volume: 300 ft³
- Fluid: 40% ethylene glycol
- Fill temperature: 60°F
Solution:
Density at 60°F for 40% EG:
- Base density at 68°F: 65.40 lb/ft³
- Correction factor at 60°F: ≈ 1.003
- ρ = 65.40 × 1.003 = 65.60 lb/ft³
Total mass required: m = 65.60 lb/ft³ × 300 ft³ = 19,680 lb
Volume in gallons: V = 300 ft³ × 7.48052 gal/ft³ = 2,244 gallons
Example 3: Pump Head Correction
Given:
- Vertical elevation: 80 ft
- Fluid: 50% propylene glycol at 40°F
- Water-based pump curve provided
Solution:
Density of 50% PG at 40°F:
- Base density at 68°F: 65.80 lb/ft³
- Correction factor at 40°F: ≈ 1.015
- ρ_PG = 65.80 × 1.015 = 66.79 lb/ft³
Density of water at 40°F: ρ_water = 62.42 lb/ft³
Static head correction:
- Water equivalent: 80 ft × (62.42/62.42) = 80 ft
- PG actual: 80 ft × (66.79/62.42) = 85.6 ft
Additional head required: 85.6 - 80 = 5.6 ft
Pump must overcome additional 5.6 ft head due to higher density
Maintenance and Operations
Periodic Testing
Regular verification ensures system maintains design parameters.
Testing Schedule:
Annual:
- Freeze point testing
- Specific gravity measurement
- pH testing
- Inhibitor concentration
Semi-Annual:
- System pressure verification
- Expansion tank pressure check
- Visual inspection for leaks
As Needed:
- After makeup water addition
- Following system modifications
- Post-leak repairs
Makeup and Recharge Procedures
Maintain proper concentration and volume throughout system life.
Makeup Requirements:
Concentration Matching:
- Match existing system concentration
- Pre-mix makeup solution
- Verify with refractometer
Volume Calculation:
- Determine volume loss
- Account for density at makeup temperature
- Add through fill connection
Documentation:
- Record makeup volume and date
- Track concentration changes
- Monitor for excessive makeup (leak indication)
Related Topics:
- Specific Heat Capacity
- Viscosity Temperature Effects
- Thermal Conductivity Properties
- Freeze Point Depression
- Corrosion Inhibitors