Calcium Chloride Brines
Calcium chloride (CaCl₂) brine solutions represent one of the most widely used secondary coolants in industrial refrigeration due to their low cost, availability, and ability to achieve temperatures as low as -51°C (-60°F) at eutectic concentration. Despite high corrosivity requiring robust inhibitor packages, CaCl₂ brines remain prevalent in ice rinks, cold storage facilities, and process cooling applications where economics and temperature requirements favor their use over less corrosive alternatives.
Chemical and Physical Characteristics
Molecular Properties
Calcium chloride exists in several hydrated forms with distinct characteristics:
| Form | Chemical Formula | Molecular Weight | Typical Use |
|---|---|---|---|
| Anhydrous | CaCl₂ | 110.98 g/mol | Desiccant, initial mixing |
| Dihydrate | CaCl₂·2H₂O | 147.01 g/mol | Common commercial form |
| Tetrahydrate | CaCl₂·4H₂O | 183.04 g/mol | Crystallization product |
| Hexahydrate | CaCl₂·6H₂O | 219.07 g/mol | Crystallization below 30°C |
Dissolution Chemistry:
The dissolution of calcium chloride is highly exothermic, releasing approximately 81.3 kJ/mol for the anhydrous form. This exothermic behavior necessitates controlled mixing procedures to prevent localized overheating and equipment damage.
CaCl₂(s) + H₂O(l) → Ca²⁺(aq) + 2Cl⁻(aq) + heat
The anhydrous form releases more heat upon dissolution than hydrated forms, making gradual addition with cooling essential for safe system charging.
Solution Behavior
Calcium chloride solutions exhibit non-ideal thermodynamic behavior due to strong ion-water interactions. The Ca²⁺ ion has a high charge density, leading to extensive hydration shells and significant deviation from ideal solution properties. This non-ideality affects all transport and thermodynamic properties.
Ionic Dissociation:
In dilute solutions, CaCl₂ dissociates almost completely:
α = 0.92 to 0.98 (depending on concentration)
At concentrations above 20% by mass, ion pairing and association complexes form, reducing effective ionic strength and modifying properties.
Freeze Point Depression and Concentration
Eutectic Point
The calcium chloride-water system exhibits a eutectic at approximately 29.9% CaCl₂ by mass, corresponding to a freeze point of -51.0°C (-59.8°F). This represents the lowest achievable temperature for CaCl₂ brine systems without solid phase formation.
Eutectic Composition:
- CaCl₂ concentration: 29.9% by mass
- Freeze point: -51.0°C (-59.8°F)
- Solid phases: Ice + CaCl₂·6H₂O
Concentration-Freeze Point Relationship
| CaCl₂ (% by mass) | Freeze Point (°C) | Freeze Point (°F) | Relative Density (20°C) |
|---|---|---|---|
| 0 | 0.0 | 32.0 | 1.000 |
| 5 | -3.0 | 26.6 | 1.043 |
| 10 | -7.0 | 19.4 | 1.087 |
| 15 | -12.5 | 9.5 | 1.134 |
| 20 | -19.0 | -2.2 | 1.183 |
| 23 | -24.0 | -11.2 | 1.213 |
| 25 | -28.0 | -18.4 | 1.232 |
| 27 | -36.0 | -32.8 | 1.252 |
| 29 | -45.0 | -49.0 | 1.273 |
| 29.9 | -51.0 | -59.8 | 1.280 |
| 31 | -47.0 | -52.6 | 1.287 |
Operating Concentration Guidelines:
Design practice maintains brine concentration 3-5% by mass above the concentration corresponding to the lowest expected system temperature. This safety margin prevents ice crystal formation during abnormal conditions.
For a system operating at -35°C (-31°F):
- Minimum freeze point required: -40°C (-40°F) with safety factor
- Required concentration: ~28% by mass
- Operating concentration: 28-29% by mass
Thermophysical Properties
Density
Density increases with concentration and decreases with temperature. The relationship follows approximately:
ρ(T,C) = ρ₀(C) × [1 - β(C) × (T - T₀)]
Where β is the thermal expansion coefficient, ranging from 4×10⁻⁴ to 6×10⁻⁴ K⁻¹ depending on concentration.
Density at 20°C:
| CaCl₂ (% by mass) | Density (kg/m³) | Density (lb/ft³) |
|---|---|---|
| 10 | 1087 | 67.9 |
| 15 | 1134 | 70.8 |
| 20 | 1183 | 73.9 |
| 25 | 1232 | 76.9 |
| 29.9 | 1280 | 79.9 |
Specific Heat
Specific heat decreases significantly with increasing concentration, directly impacting heat transfer capacity and system performance.
Specific Heat at 20°C:
| CaCl₂ (% by mass) | Specific Heat (kJ/kg·K) | Specific Heat (Btu/lb·°F) |
|---|---|---|
| 10 | 3.86 | 0.922 |
| 15 | 3.59 | 0.858 |
| 20 | 3.29 | 0.786 |
| 25 | 2.96 | 0.707 |
| 29.9 | 2.61 | 0.624 |
The reduced specific heat at eutectic concentration (38% lower than water) requires higher mass flow rates to achieve equivalent heat transfer, increasing pumping energy.
Temperature Dependence:
Specific heat shows weak temperature dependence (< 5% variation from -40°C to +20°C) compared to concentration effects.
Viscosity
Dynamic viscosity increases dramatically with both increasing concentration and decreasing temperature, significantly affecting pumping power requirements.
Dynamic Viscosity (mPa·s):
| CaCl₂ (% by mass) | -40°C | -30°C | -20°C | -10°C | 0°C | 10°C | 20°C |
|---|---|---|---|---|---|---|---|
| 10 | - | - | - | - | 2.42 | 1.87 | 1.50 |
| 15 | - | - | - | 4.52 | 3.15 | 2.35 | 1.82 |
| 20 | - | - | 9.24 | 6.10 | 4.18 | 3.02 | 2.28 |
| 25 | - | 28.5 | 15.8 | 9.65 | 6.21 | 4.26 | 3.08 |
| 29.9 | 88.2 | 42.7 | 22.4 | 12.9 | 7.98 | 5.26 | 3.65 |
Viscosity Impact on System Design:
At eutectic concentration and -40°C, viscosity increases by a factor of ~24 compared to 20°C conditions. This dramatic increase necessitates:
- Oversized piping to limit pressure drop
- Higher capacity pumps with appropriate motor sizing
- Increased electrical energy consumption during cold operation
- Consideration of pump minimum flow bypass requirements
Thermal Conductivity
Thermal conductivity decreases with increasing concentration but shows modest temperature dependence.
Thermal Conductivity at 20°C:
| CaCl₂ (% by mass) | Thermal Conductivity (W/m·K) | Thermal Conductivity (Btu/h·ft·°F) |
|---|---|---|
| 10 | 0.548 | 0.317 |
| 15 | 0.532 | 0.307 |
| 20 | 0.516 | 0.298 |
| 25 | 0.500 | 0.289 |
| 29.9 | 0.484 | 0.280 |
The reduction in thermal conductivity at high concentrations (12% lower than water) marginally reduces heat exchanger performance but is less significant than specific heat effects.
Prandtl Number
The Prandtl number characterizes the relative importance of momentum and thermal diffusion:
Pr = (μ × cₚ) / k
For CaCl₂ brines:
- Pr = 10 to 15 at 20°C (depending on concentration)
- Pr = 30 to 50 at -30°C for concentrated brines
Elevated Prandtl numbers at low temperatures indicate thicker thermal boundary layers and reduced convective heat transfer coefficients.
Corrosion Characteristics and Control
Inherent Corrosivity
Calcium chloride brines exhibit aggressive corrosion behavior toward ferrous and non-ferrous metals due to:
- High Chloride Ion Concentration: Cl⁻ ions disrupt passive oxide films on metal surfaces, enabling pitting and crevice corrosion
- Ionic Conductivity: High electrical conductivity (up to 15 S/m) facilitates electrochemical corrosion processes
- Oxygen Solubility: Dissolved oxygen acts as a cathodic depolarizer, accelerating corrosion rates
- pH Sensitivity: Solutions naturally drift toward acidic conditions (pH 5-6) in the presence of dissolved CO₂
Typical Uninhibited Corrosion Rates:
| Material | Corrosion Rate (mm/year) | Corrosion Rate (mpy) | Suitability |
|---|---|---|---|
| Carbon Steel | 0.5 - 2.0 | 20 - 80 | Unacceptable without inhibitors |
| Cast Iron | 0.3 - 1.5 | 12 - 60 | Unacceptable without inhibitors |
| Galvanized Steel | 0.2 - 0.8 | 8 - 30 | Poor, zinc rapidly consumed |
| Copper | 0.02 - 0.08 | 0.8 - 3.0 | Acceptable with inhibitors |
| Brass | 0.05 - 0.15 | 2.0 - 6.0 | Dezincification risk |
| Stainless Steel 304 | 0.01 - 0.05 | 0.4 - 2.0 | Pitting susceptible |
| Stainless Steel 316 | < 0.01 | < 0.4 | Good resistance |
Corrosion Inhibitor Systems
Effective corrosion control requires multi-component inhibitor packages addressing different corrosion mechanisms:
Chromate-Based Inhibitors (Traditional):
- Sodium chromate (Na₂CrO₄): 1500-3000 ppm
- Hexavalent chromium (Cr⁶⁺) forms passive oxide layers
- Environmental concerns and regulatory restrictions limit current use
- Highly effective but largely phased out due to toxicity
Modern Non-Chromate Inhibitors:
| Inhibitor Type | Typical Concentration | Function | Target Metals |
|---|---|---|---|
| Sodium nitrite (NaNO₂) | 2000-5000 ppm | Anodic passivation | Ferrous metals |
| Sodium molybdate (Na₂MoO₄) | 500-1500 ppm | Anodic inhibitor | Ferrous metals |
| Sodium tetraborate (Na₂B₄O₇) | 1000-3000 ppm | pH buffer, passivation | Ferrous metals |
| Tolyltriazole (TTA) | 50-200 ppm | Copper protection | Copper alloys |
| Benzotriazole (BTA) | 50-200 ppm | Copper protection | Copper alloys |
| Polyacrylates | 100-500 ppm | Scale control | All metals |
Inhibitor Package Design:
A comprehensive inhibitor package for CaCl₂ brine typically includes:
- Primary anodic inhibitor (nitrite or molybdate)
- pH buffer (borate or phosphate)
- Copper protector (triazole derivatives)
- Dispersant (polyacrylate)
- Antifoam agent
Inhibitor Depletion:
Inhibitors deplete through:
- Chemical reaction with metal surfaces
- Thermal degradation at elevated temperatures
- Oxidation by dissolved oxygen
- Biological consumption (rare but possible)
Regular monitoring and replenishment maintain effective concentrations:
- Monthly testing for critical systems
- Quarterly testing for standard applications
- Immediate testing after system repairs or fluid additions
pH Management
Maintaining pH in the range 7.5-9.0 optimizes inhibitor effectiveness and minimizes corrosion:
pH Control Strategies:
- Initial pH adjustment: sodium hydroxide (NaOH) to pH 8.0-8.5
- Buffer capacity: borate or phosphate inhibitors
- Monitoring frequency: monthly minimum
- Corrective action: pH < 7.0 requires investigation and inhibitor replenishment
pH Drift Mechanisms:
Acidification occurs through:
- CO₂ absorption from atmosphere: CO₂ + H₂O → H₂CO₃
- Corrosion product formation: Fe + 2H₂O → Fe(OH)₂ + H₂
- Microbial activity (rare in cold systems)
Oxygen Control
Dissolved oxygen accelerates corrosion rates exponentially. Oxygen management strategies include:
Closed System Design:
- Nitrogen blanket on expansion tanks
- Hermetically sealed systems
- Bladder-type expansion tanks
- Dissolved oxygen target: < 0.5 ppm
Deaeration:
- Vacuum deaeration during initial fill
- Chemical scavenging (sodium sulfite + catalyst)
- Membrane contactors for continuous removal
Chemical Oxygen Scavenging:
Sodium sulfite reaction: 2 Na₂SO₃ + O₂ → 2 Na₂SO₄
Typical dosage: 8 ppm Na₂SO₃ per 1 ppm O₂ (stoichiometric ratio with 50% excess)
Cobalt catalyst accelerates reaction kinetics, particularly at low temperatures.
System Design Considerations
Material Selection
Piping Systems:
| Application | Recommended Material | Alternatives | Not Recommended |
|---|---|---|---|
| Main distribution | Schedule 40 carbon steel with inhibitors | Schedule 80 steel | Galvanized steel |
| Rink floor coils | Steel pipe, 1/2" to 1" diameter | Polyethylene for low-temperature service | Copper in direct contact with concrete |
| Heat exchangers | 316 stainless steel plates or tubes | Titanium, cupronickel | 304 stainless, carbon steel |
| Pumps | Cast iron body with 316 SS impeller | All-316 SS construction | Bronze, brass components |
| Expansion tanks | Carbon steel with epoxy lining | 304 SS for small units | Unlined carbon steel |
Gasket and Seal Materials:
- EPDM (ethylene propylene diene monomer): excellent chemical resistance
- Viton (fluoroelastomer): high-temperature applications
- PTFE (polytetrafluoroethylene): universal chemical resistance
- Avoid: natural rubber, nitrile in high-concentration brines
Heat Transfer Equipment
Shell-and-Tube Heat Exchangers:
Design considerations specific to CaCl₂ brines:
- Tube-side brine flow preferred to facilitate inspection and cleaning
- Minimum flow velocity: 1.0 m/s (3.3 ft/s) to prevent stagnation corrosion
- Tube material: 316 stainless steel for long service life
- Fouling factor: 0.0002-0.0004 m²·K/W (0.001-0.002 h·ft²·°F/Btu)
Plate Heat Exchangers:
Advantages for brine service:
- Compact design with high heat transfer coefficients
- Easy disassembly for inspection and cleaning
- 316 SS plate construction standard
- Turbulent flow at low Reynolds numbers reduces fouling
Disadvantages:
- Gasket degradation potential
- Pressure drop concerns at high viscosity
- Flow distribution sensitivity
Performance Correction Factors:
Heat transfer coefficients for CaCl₂ brine are reduced compared to water due to lower thermal conductivity and higher viscosity. Approximate correction factors:
- 20% concentration: 0.85 × water coefficient
- 25% concentration: 0.75 × water coefficient
- 30% concentration: 0.65 × water coefficient at -30°C
Piping System Design
Velocity Limits:
| Service | Minimum Velocity | Maximum Velocity | Typical Design Velocity |
|---|---|---|---|
| Main distribution | 0.6 m/s (2 ft/s) | 2.4 m/s (8 ft/s) | 1.2-1.8 m/s (4-6 ft/s) |
| Rink floor coils | 0.3 m/s (1 ft/s) | 1.2 m/s (4 ft/s) | 0.6-0.9 m/s (2-3 ft/s) |
| Heat exchanger | 1.0 m/s (3.3 ft/s) | 3.0 m/s (10 ft/s) | 1.5-2.1 m/s (5-7 ft/s) |
Minimum velocity prevents stagnation corrosion and particulate settling. Maximum velocity limits erosion-corrosion and pressure drop.
Pressure Drop Calculation:
The Darcy-Weisbach equation applies with friction factor from Moody diagram:
ΔP = f × (L/D) × (ρv²/2)
At low temperatures, elevated viscosity substantially increases pressure drop. Design practice applies a safety factor of 1.3-1.5 to calculated pressure drop to account for temperature excursions and system aging.
Thermal Expansion:
Linear thermal expansion coefficient for steel pipe: α = 12×10⁻⁶ /°C
Temperature differential from ambient installation (20°C) to cold operation (-35°C) produces contraction:
ΔL = α × L × ΔT = 12×10⁻⁶ × L × 55 = 0.00066 × L
For a 30 m pipe run: ΔL = 20 mm contraction
Expansion loops, flexible connections, or expansion joints accommodate dimensional changes without inducing excessive stress.
Insulation Requirements
Insulation serves three critical functions:
- Minimize heat gain to reduce refrigeration load
- Prevent surface condensation
- Personnel protection from cold surfaces
Insulation Thickness Guidelines (Closed-cell elastomeric foam):
| Pipe Size | Operating Temp | Insulation Thickness | Surface Temp (20°C ambient, 70% RH) |
|---|---|---|---|
| 25-50 mm | -30 to -20°C | 40 mm | 15-17°C |
| 65-100 mm | -30 to -20°C | 50 mm | 15-17°C |
| 125-200 mm | -30 to -20°C | 65 mm | 15-17°C |
Thickness selected to maintain surface temperature above dew point (approximately 14°C at 20°C, 70% RH).
Vapor Barrier Integrity:
All insulation joints, seams, and penetrations require vapor-tight sealing with compatible mastic or tape. Moisture infiltration into insulation causes:
- Thermal performance degradation
- Ice formation within insulation matrix
- External corrosion under insulation (CUI)
- Insulation compression and failure
Ice Rink Applications
Rink Floor System Design
Ice rink applications represent the largest single use category for calcium chloride brine in HVAC systems.
Typical System Parameters:
| Parameter | Value | Notes |
|---|---|---|
| Ice surface temperature | -5 to -8°C (23-18°F) | Varies by use and ambient conditions |
| Brine supply temperature | -10 to -12°C (14-10°F) | 4-6°C below ice surface target |
| Brine return temperature | -8 to -10°C (18-14°F) | 2-3°C rise across floor |
| Brine concentration | 22-25% by mass | Adequate freeze protection with margin |
| Brine flow rate | 0.4-0.6 L/s per 100 m² ice surface | 6-9 gpm per 1000 ft² |
Floor Construction Layers:
- Ice surface: 25-38 mm (1-1.5 in) thick
- Concrete slab: 100-150 mm (4-6 in) with embedded brine pipes
- Sand or gravel base: 150-300 mm (6-12 in) with moisture barrier
- Sub-slab insulation: 50-100 mm (2-4 in) extruded polystyrene
- Subgrade: compacted, well-drained
Brine Pipe Spacing:
Typical spacing: 100 mm (4 in) on center Pipe size: 12.7-19 mm (1/2 to 3/4 in) nominal Material: Carbon steel schedule 40 with corrosion inhibitors
Closer spacing (75 mm) used in warm climates or for critical surface temperature uniformity.
Heat Removal Requirements:
Total refrigeration load for ice rink:
Q_total = Q_conduction + Q_radiation + Q_convection + Q_resurfacing + Q_occupant
Typical values per 100 m² ice surface:
- Conduction through slab: 5-8 kW
- Radiation from ceiling: 3-5 kW
- Convection from air: 2-4 kW
- Resurfacing water: 1-2 kW
- Occupants and lighting: 2-4 kW
- Total: 13-23 kW per 100 m² (4.1-7.3 tons per 1000 ft²)
Full-size NHL rink (60 m × 26 m = 1560 m²) requires 200-360 kW (60-100 tons) refrigeration capacity.
Brine Concentration Management
Freeze Protection Margin:
Operating concentration must prevent freezing at the coldest expected brine temperature with safety margin:
Minimum concentration: corresponding to freeze point 5°C below lowest operating temperature
Example:
- Lowest brine supply temperature: -12°C (10°F)
- Required freeze point: -17°C (1°F) minimum
- Required concentration: ~16% by mass minimum
- Typical operating concentration: 22-25% by mass
Concentration Verification:
Field measurement methods:
- Refractometry: rapid, correlates refractive index to concentration
- Hydrometry: measures specific gravity at known temperature
- Freeze point testing: direct measurement using calibrated freeze point apparatus
- Titration: laboratory method for precise concentration determination
Concentration decreases over time through:
- Leakage at pipe joints, valves, seals
- Intentional drainage during maintenance
- Dilution from melted ice or condensation infiltration
Regular monitoring and adjustment maintain design concentration.
Chemical Handling and Safety
Personnel Safety
Health Hazards:
Calcium chloride exhibits low acute toxicity but requires appropriate handling precautions:
- Eye contact: severe irritation, potential corneal damage
- Skin contact: irritation, desiccation, dermatitis with prolonged exposure
- Ingestion: gastrointestinal irritation, hypercalcemia at high doses
- Inhalation: dust exposure causes respiratory irritation
Personal Protective Equipment (PPE):
- Safety glasses or goggles with side shields
- Chemical-resistant gloves (nitrile or neoprene)
- Long sleeves and pants to prevent skin contact
- Dust mask or respirator when handling dry material
- Face shield for mixing concentrated solutions
Mixing and Charging Procedures
Initial System Charge:
- Calculation of required CaCl₂ mass:
m_CaCl₂ = V_system × ρ_water × C_target / (1 - C_target)
Where:
- V_system = system volume (m³)
- ρ_water = water density (kg/m³)
- C_target = target concentration (mass fraction)
Example for 10 m³ system at 25% concentration: m_CaCl₂ = 10 × 1000 × 0.25 / (1 - 0.25) = 3333 kg
- Gradual mixing procedure:
- Fill system 50% with water
- Start circulation pump
- Slowly add CaCl₂ in 10-15 kg batches
- Allow 5-10 minutes circulation between additions
- Monitor temperature (dissolution is highly exothermic)
- Maintain brine temperature < 40°C during mixing
- Complete filling to system volume after full dissolution
- Verify concentration by testing
- Inhibitor addition:
Add inhibitor package after CaCl₂ fully dissolved and brine cooled to < 30°C. Premix powdered inhibitors with water before addition to prevent clumping.
- System deaeration:
- Operate circulation pump with vents open
- Remove air from high points
- Consider vacuum deaeration for critical applications
- Target dissolved oxygen < 0.5 ppm
Spill Response:
- Contain liquid spills with absorbent material (vermiculite, sand)
- Neutralize with weak acid if pH elevated
- Flush residue with copious water
- Dispose according to local regulations (typically non-hazardous)
Maintenance and Monitoring
Routine Testing Schedule
Monthly Testing (minimum):
Concentration measurement
- Method: refractometry or hydrometry
- Target: within ±2% of design value
- Action: adjust concentration if outside range
pH measurement
- Method: calibrated pH meter
- Target: 7.5-9.0
- Action: pH < 7.0 requires inhibitor replenishment
Inhibitor concentration
- Method: test kits or laboratory analysis
- Target: maintain manufacturer-specified levels
- Action: replenish depleted inhibitors
Visual inspection
- Check for leaks, corrosion, deposits
- Inspect expansion tank level and condition
- Verify pump operation and unusual noise
Annual Testing:
Complete fluid analysis:
- All inhibitor components
- Dissolved metals (Fe, Cu, Ca) indicating corrosion
- Suspended solids
- Microbial contamination
System pressure test
Heat exchanger inspection and cleaning
Pump seal inspection and replacement as needed
Corrosion Monitoring
Corrosion Coupon Program:
Install pre-weighed metal coupons representing system materials:
- Carbon steel (primary indicator)
- Copper (if present in system)
- Exposure period: 90 days typical
- Weight loss measurement determines corrosion rate
- Target: < 0.05 mm/year (2 mpy) for ferrous metals
Electrochemical Monitoring:
Linear polarization resistance (LPR) probes provide real-time corrosion rate measurement:
- Continuous monitoring capability
- Early warning of inhibitor depletion
- Immediate response to system changes
Comparison with Alternative Secondary Coolants
CaCl₂ vs. Ethylene Glycol
| Property | CaCl₂ (25% mass) | Ethylene Glycol (35% volume) |
|---|---|---|
| Freeze point | -28°C (-18°F) | -28°C (-18°F) |
| Viscosity at -20°C | 15.8 mPa·s | 10.3 mPa·s |
| Specific heat at 0°C | 3.08 kJ/kg·K | 3.62 kJ/kg·K |
| Thermal conductivity | 0.50 W/m·K | 0.43 W/m·K |
| Relative cost | 1.0 | 3.5-4.5 |
| Corrosivity | High (requires inhibitors) | Moderate (inhibitors recommended) |
| Toxicity | Low | High (requires leak containment) |
CaCl₂ Advantages:
- Significantly lower cost (60-75% less than glycol)
- Non-flammable
- Lower toxicity
- Higher thermal conductivity
- Readily available
CaCl₂ Disadvantages:
- Higher corrosivity requiring more aggressive inhibition
- Higher viscosity at low temperatures
- Lower specific heat (requires higher flow rates)
- Requires regular maintenance and monitoring
Application Selection Criteria
CaCl₂ Brine Preferred:
- Industrial refrigeration with professional maintenance staff
- Ice rinks and skating facilities
- Large-scale cold storage
- Process cooling with robust monitoring
- Cost-sensitive applications
- Systems designed for brine service with appropriate materials
Glycol Solutions Preferred:
- Food processing requiring non-toxic fluids
- HVAC comfort cooling systems
- Smaller systems with limited maintenance capability
- Applications requiring extended service intervals
- Systems with mixed metallurgy requiring broad compatibility
ASHRAE and Code References
ASHRAE Handbook References
ASHRAE Handbook—Refrigeration (2022):
- Chapter 4: Secondary Coolants (Brines)
- Thermophysical property tables
- Corrosion and inhibitor recommendations
- System design guidance
ASHRAE Handbook—HVAC Systems and Equipment (2020):
- Chapter 48: Ice Rinks
- Brine system design for ice rinks
- Load calculations
- Refrigeration equipment
ASHRAE Handbook—Fundamentals (2021):
- Chapter 31: Physical Properties of Secondary Coolants
- Detailed property correlations
- Heat transfer considerations
Standards and Codes
IIAR (International Institute of Ammonia Refrigeration):
- IIAR Bulletin 114: Identification of Secondary Coolants Used with Ammonia Refrigeration Systems
- IIAR-2: Equipment, Design, and Installation of Closed-Circuit Ammonia Mechanical Refrigeration Systems (references brine systems)
ASHRAE Standards:
- ASHRAE Standard 15: Safety Standard for Refrigeration Systems
- Secondary coolant system requirements
- Leak detection and ventilation
- Pressure relief provisions
ASME (American Society of Mechanical Engineers):
- ASME B31.5: Refrigeration Piping and Heat Transfer Components
- Piping design, materials, and installation requirements
NFPA (National Fire Protection Association):
- NFPA 1: Fire Code
- Ice rink refrigeration systems
- Secondary coolant classification
Water Quality Standards
Initial water quality significantly affects long-term corrosion and scale formation. Recommended makeup water parameters:
| Parameter | Maximum Value | Preferred Value |
|---|---|---|
| Total dissolved solids (TDS) | 500 ppm | < 200 ppm |
| Chlorides | 50 ppm | < 25 ppm |
| Sulfates | 50 ppm | < 25 ppm |
| Hardness (as CaCO₃) | 150 ppm | < 100 ppm |
| pH | 8.5 | 7.0-8.0 |
| Iron | 0.3 ppm | < 0.1 ppm |
Water softening or deionization may be required for high-purity applications or systems with minimal corrosion tolerance.
Environmental and Disposal Considerations
Environmental Impact
Calcium chloride brines present minimal direct environmental toxicity:
- Not classified as hazardous waste under RCRA
- Low aquatic toxicity (LC₅₀ > 1000 mg/L for most species)
- High BOD/COD (negligible organic content)
Environmental concerns:
- Soil and water salinity if released to environment
- Vegetation damage from high salt concentration
- Groundwater contamination potential in sensitive areas
- Corrosive to soil-buried metal infrastructure
Disposal Methods
Small Volumes (< 200 L):
- Dilute with water (10:1 minimum ratio)
- Discharge to sanitary sewer where permitted
- Verify local discharge regulations and pH limits
- Neutralize high-pH inhibited brines before discharge
Large Volumes (> 200 L):
- Contact licensed waste hauler for removal
- Recycle or reclaim through chemical reprocessing
- Evaporative concentration and CaCl₂ recovery for high-volume users
- Land application to roadways for dust control or ice melting (winter)
Contaminated Brine:
- Heavy metal contamination: treat as hazardous waste
- High oil content: separate oil, dispose according to regulations
- Microbial contamination: biocide treatment or thermal pasteurization
Best Practices Summary
- Design concentration 3-5% above freeze point corresponding to minimum operating temperature
- Implement comprehensive inhibitor package with regular monitoring and replenishment
- Maintain pH 7.5-9.0 through buffer additives and periodic adjustment
- Control dissolved oxygen < 0.5 ppm using closed system design and chemical scavenging
- Select corrosion-resistant materials, particularly 316 SS for heat exchangers and wetted pump components
- Design for minimum flow velocity 0.6 m/s to prevent stagnation corrosion
- Provide adequate insulation with vapor-tight sealing to prevent condensation and external corrosion
- Establish routine testing schedule with monthly minimum for concentration, pH, and inhibitors
- Use proper mixing procedures with gradual CaCl₂ addition and temperature control during initial charge
- Implement corrosion coupon monitoring to verify inhibitor effectiveness and system integrity
Economic Considerations
Life-Cycle Cost Analysis
Total cost of ownership for CaCl₂ brine system over 20-year service life includes:
Initial Costs:
- CaCl₂ material: $1.50-2.50/kg ($0.70-1.15/lb) for dihydrate grade
- Inhibitor package: $5-15/kg ($2.25-7/lb)
- System charging labor: 8-16 hours for typical ice rink system
Operating Costs (Annual):
- Inhibitor replenishment: 10-20% of initial charge
- Concentration adjustment: 5-10% makeup for typical leakage
- Testing and analysis: $500-2000 depending on frequency and laboratory costs
- Pumping energy: 15-25% higher than glycol due to density and viscosity
Maintenance Costs:
- Heat exchanger cleaning: annual to biennial depending on water quality
- Pump seal replacement: 3-5 year intervals with proper maintenance
- Piping repairs: corrosion-related failures if inhibitor program inadequate
End-of-Life:
- Disposal costs: $0.50-2.00 per gallon depending on local requirements
- System flushing labor: 4-8 hours
Despite higher operating costs compared to glycol systems, the 60-75% lower initial fluid cost and high-volume economics favor CaCl₂ for large industrial systems with professional maintenance capability.
Conclusion
Calcium chloride brine remains a cost-effective secondary coolant for industrial refrigeration and ice rink applications despite corrosivity challenges. Successful long-term operation requires careful attention to concentration management, comprehensive corrosion inhibition, routine monitoring, and appropriate material selection. When properly designed and maintained, CaCl₂ brine systems provide reliable service at significantly lower cost than alternative secondary coolants, making them the economically optimal choice for many large-scale refrigeration applications.