Operational Improvements
Operational improvements represent the lowest-cost approach to energy conservation, targeting system performance optimization without capital investment. These strategies focus on extracting maximum efficiency from existing equipment through better control, maintenance, and operating practices.
Scheduling Optimization
Operating equipment only when needed eliminates unnecessary energy consumption while maintaining comfort and functionality.
Occupancy-Based Scheduling
Time-based scheduling aligns system operation with building use patterns:
- Start/Stop Optimization: Calculate minimum lead time required to reach setpoint by occupancy time
- Optimal Start Algorithms: Use outdoor temperature, space temperature, and thermal mass characteristics
- Night Setback Recovery: Predict warmup/cooldown time based on ΔT and building thermal response
- Weekend/Holiday Scheduling: Reduce or eliminate operation during unoccupied periods
- Staged Equipment Start: Prevent demand peaks by sequencing equipment startup
Optimal start time calculation:
t_start = t_occupancy - (T_setpoint - T_current) / R_thermal
Where R_thermal represents building heating/cooling rate (°F/hr or °C/hr).
Zone-Level Scheduling
Independent scheduling for different building areas improves efficiency:
- Perimeter vs. Core: Different solar gain patterns require different schedules
- Multi-Tenant Coordination: Individual zone control for varied occupancy patterns
- After-Hours Overrides: Temporary occupancy accommodation with automatic reversion
- Cleaning Schedule Integration: Ventilation during custodial operations only
- Kitchen/Laboratory Exhaust: Match exhaust to actual use periods
Load Shedding Strategies
Strategic equipment cycling reduces peak demand without compromising comfort:
- Rotating Equipment Shutdown: Brief cycling of non-critical loads
- Pre-Cooling: Lower temperature before peak demand periods
- Thermal Mass Utilization: Leverage building thermal storage capacity
- Demand Response Integration: Automated response to utility signals
- Peak Demand Limiting: Real-time load monitoring with automated shedding
Setback and Setup Strategies
Temperature setback during unoccupied periods reduces heating and cooling loads significantly.
Night Setback Heating
Lower heating setpoint during unoccupied hours:
- Typical Setback: 55-60°F (13-16°C) for most commercial buildings
- Freeze Protection: Minimum 50°F (10°C) for piping protection
- Equipment Protection: Higher setpoints for sensitive equipment areas
- Humidity Considerations: Prevent condensation during setback periods
- Recovery Time: 1-3 hours typical for commercial construction
Energy savings equation:
Q_saved = UA × (T_normal - T_setback) × t_unoccupied
Cooling Setup
Raise cooling setpoint during unoccupied periods:
- Typical Setup: 80-85°F (27-29°C) for commercial spaces
- Humidity Limits: Maximum 60% RH to prevent moisture damage
- Computer Room Exceptions: Maintain tighter control for IT equipment
- Building Mass Impact: Heavy construction allows wider temperature swing
- Peak Load Consideration: Setup may increase peak cooling demand
Seasonal Adjustments
Optimize setpoints based on outdoor conditions:
- Shoulder Season: Wider acceptable temperature range (70-78°F vs. 72-76°F)
- Humidity-Based Limits: Tighter control during high humidity periods
- Occupant Adaptation: Gradual seasonal adjustment improves acceptance
- Clothing Factor: Consider seasonal dress code in setpoint selection
- Activity Level: Adjust for space function and metabolic heat generation
Economizer Operation
Free cooling using outdoor air when conditions permit reduces mechanical cooling energy substantially.
Economizer Control Strategies
Selection of appropriate control method affects energy savings:
| Control Type | Changeover Point | Advantages | Limitations |
|---|---|---|---|
| Dry Bulb | 55-65°F (13-18°C) | Simple, reliable | Ignores humidity |
| Enthalpy | 28 BTU/lb (65 kJ/kg) | Accounts for latent load | Requires humidity sensor |
| Differential Dry Bulb | Return air temperature | No fixed setpoint | May overcool |
| Differential Enthalpy | Return air enthalpy | Optimal savings | Complex control |
Economizer Optimization Techniques
Maximize free cooling benefit through proper operation:
- Integrated Control: Coordinate economizer with mechanical cooling
- Minimum Damper Position: Ensure adequate ventilation air at all times
- Damper Sequencing: Modulate outdoor air before mechanical cooling
- Morning Purge: Pre-cool building with cool outdoor air before occupancy
- Night Cooling: Flush building heat during mild evenings
- High-Limit Shutoff: Prevent economizer operation during unfavorable conditions
Common Economizer Problems
Typical failures that eliminate energy savings:
- Stuck Dampers: Mechanical failure prevents modulation
- Failed Sensors: Incorrect readings cause improper control
- Control Logic Errors: Programming mistakes prevent economizer operation
- Minimum Position Too High: Excessive outdoor air during mechanical cooling
- Relief Damper Issues: Improper building pressure affects economizer capacity
- Mixed Air Temperature: Below dewpoint causes coil condensation and freezing
Maintenance Impact on Energy Performance
Proper maintenance preserves equipment efficiency and prevents energy waste.
Filter Maintenance
Clean filters reduce fan energy and maintain airflow:
- Pressure Drop Monitoring: Replace at 1.0-2.0 in. w.g. (250-500 Pa) depending on filter type
- Energy Impact: Each 0.5 in. w.g. increases fan power by approximately 10-15%
- Filter Selection: Balance filtration efficiency with pressure drop
- Prefilters: Extend life of final filters, reduce overall pressure drop
- Differential Pressure Sensors: Automate filter change notifications
Fan power relationship to pressure:
BHP = (CFM × ΔP) / (6356 × η_fan)
Coil Maintenance
Clean heat exchanger surfaces maintain heat transfer efficiency:
- Fouling Impact: Dirty coils reduce capacity by 10-30%
- Airside Cleaning: Annual cleaning prevents biological growth
- Waterside Cleaning: Remove scale and biological deposits
- Fin Straightening: Restore airflow through damaged fins
- Condensate Drain: Clear blockages to prevent water damage and IAQ issues
Belt and Drive Maintenance
Proper belt tension and alignment reduce energy loss:
- Belt Tension: Loose belts slip, wasting 5-10% of motor power
- Belt Condition: Worn belts reduce transmission efficiency
- Sheave Alignment: Misalignment increases belt wear and energy loss
- Direct Drive Benefits: Eliminate belt losses (3-5% efficiency gain)
- VFD Integration: Variable speed operation reduces mechanical stress
Bearing Lubrication
Proper lubrication reduces friction losses and prevents failure:
- Lubrication Schedule: Follow manufacturer recommendations
- Bearing Temperature: Monitor for excessive heat indicating problems
- Vibration Analysis: Detect bearing wear before failure
- Motor Efficiency: Poor bearings increase motor current draw
- Seal Condition: Prevent lubricant loss and contamination
Monitoring-Based Commissioning
Continuous monitoring identifies operational problems and optimization opportunities.
Key Performance Indicators
Track critical parameters to identify problems:
- Energy Use Intensity (EUI): kBTU/sf/yr or kWh/m²/yr
- Cooling Efficiency: kW/ton or COP
- Heating Efficiency: Combustion efficiency percentage
- Fan Efficiency: CFM/W or pressure rise per unit power
- Pump Efficiency: GPM/W or head per unit power
- Delta-T: Supply-return temperature difference indicates distribution efficiency
Fault Detection and Diagnostics
Automated analysis identifies operational faults:
- Simultaneous Heating and Cooling: Wasteful operation requiring correction
- Excessive Outdoor Air: Above minimum ventilation requirements
- Temperature Sensor Errors: Unrealistic or unchanging readings
- Economizer Faults: Damper position inconsistent with control logic
- Equipment Cycling: Short cycling indicates oversizing or control problems
- Schedule Adherence: Equipment operating outside scheduled hours
Trending and Baselining
Establish normal operation patterns to identify deviations:
- Load Normalization: Adjust for weather using degree-days or regression
- Seasonal Patterns: Compare current year to previous year same period
- Day-Type Comparison: Weekdays vs. weekends, occupied vs. unoccupied
- Benchmark Comparison: Compare to similar buildings or industry standards
- CUSUM Analysis: Cumulative sum charts reveal performance drift
Alarm Management
Effective notification ensures timely response to problems:
- Alarm Prioritization: Critical vs. informational classifications
- Setpoint Tolerance: Dead bands prevent nuisance alarms
- Alarm Delays: Time delays filter transient conditions
- Escalation Procedures: Automatic notification hierarchy
- Alarm Analysis: Review patterns to identify systemic issues
Reset Strategies
Adjusting supply temperatures based on demand reduces energy consumption.
Supply Air Temperature Reset
Raise supply air temperature when cooling loads decrease:
- Outdoor Air Reset: Increase SAT as OAT decreases
- Warmest Zone Reset: SAT based on zone requiring most cooling
- Return Air Temperature Reset: Maintain target return air temperature
- Typical Range: 55-65°F (13-18°C) depending on load
- Humidity Constraints: Minimum SAT to maintain dehumidification
Chilled Water Temperature Reset
Increase chilled water supply temperature reduces chiller energy:
- Outdoor Air Reset: 42-50°F (6-10°C) range based on OAT
- Load-Based Reset: Increase temperature during low load periods
- Valve Position Reset: Monitor valve positions, reset when all valves <90% open
- Chiller Efficiency Impact: Each 1°F increase saves approximately 1-2% compressor energy
- Dehumidification Limit: Maintain adequate coil temperature for latent removal
Hot Water Temperature Reset
Lower hot water temperature reduces heat loss and boiler cycling:
- Outdoor Air Reset: 120-180°F (49-82°C) range based on OAT
- Linear Reset: ΔT_hw proportional to ΔT_outdoor
- Design Day Operation: Maximum temperature at design outdoor temperature
- Domestic Hot Water Priority: Separate DHW from space heating for better control
- Condensing Boiler Optimization: Lower return temperature maximizes efficiency
Reset schedule example:
| Outdoor Temp | Hot Water Supply |
|---|---|
| 70°F (21°C) | 120°F (49°C) |
| 50°F (10°C) | 140°F (60°C) |
| 30°F (-1°C) | 160°F (71°C) |
| 0°F (-18°C) | 180°F (82°C) |
Variable Speed Drive Optimization
VFD operation reduces fan and pump energy through affinity law relationships.
Fan Speed Optimization
Reduce airflow during low load conditions:
- VAV System Reset: Lower static pressure setpoint based on damper positions
- Trim and Respond: Incrementally adjust setpoint to maintain minimum damper position
- Diversity Factor: Account for zones requiring simultaneous maximum airflow
- Minimum Speed: Maintain minimum 30-40% speed for stable operation
- Duct Pressure Distribution: Ensure adequate pressure at furthest zones
Energy savings relationship:
P₂/P₁ = (RPM₂/RPM₁)³
Reducing fan speed to 80% of design reduces power to 51% of design.
Pump Speed Optimization
Variable flow reduces pumping energy substantially:
- Differential Pressure Reset: Lower setpoint when control valves open
- Temperature-Based Control: Modulate flow to maintain ΔT
- Minimum Flow Requirements: Maintain chiller/boiler minimum flow
- Distribution Efficiency: Ensure adequate flow at furthest loads
- Decoupling Applications: Primary-secondary pumping with variable secondary
Demand Controlled Ventilation
Modulate outdoor air based on actual occupancy reduces conditioning load.
CO₂-Based Control
Carbon dioxide concentration indicates occupancy level:
- Setpoint Selection: 800-1000 ppm typical target above outdoor ambient
- Sensor Placement: Return air or representative zone location
- Minimum Ventilation: Maintain code-required minimum at all times
- Transient Response: Account for sensor lag and space mixing time
- Sensor Calibration: Verify accuracy annually, replace as needed
Ventilation rate equation:
CFM_vent = (G × 10⁶) / [CS(CO₂_space - CO₂_outdoor)]
Where G = CO₂ generation rate (CFM), CS = steady-state constant.
Occupancy Sensor Integration
Direct occupancy detection enables faster response:
- PIR Sensors: Passive infrared detects motion
- Dual Technology: Combines PIR with ultrasonic for better accuracy
- CO₂ Backup: Use both methods for redundancy
- Zone Aggregation: Combine multiple zones for smoother control
- Time Delays: Prevent rapid cycling on occupancy changes
Components
- Preventive Maintenance Efficiency
- Control System Optimization
- System Balancing Commissioning
- Economizer Optimization
- Supply Air Temperature Reset
- Chilled Water Temperature Reset
- Hot Water Temperature Reset
- Demand Controlled Ventilation
- Variable Speed Drive Optimization