Testing Methods
Air permeability testing quantifies airflow resistance through building materials under controlled pressure differentials. These standardized test methods provide essential data for moisture transport modeling, energy analysis, and building envelope design.
ASTM E2178: Air Permeability of Building Materials
ASTM E2178 establishes the laboratory procedure for measuring air permeability of porous building materials as an intrinsic material property independent of specimen thickness.
Test Principle
The method determines air permeability (ka) by measuring steady-state airflow through a material specimen under known pressure differential:
ka = (μ × q × L) / (A × ΔP)
Where:
- ka = air permeability coefficient (m²)
- μ = dynamic viscosity of air (Pa·s)
- q = volumetric airflow rate (m³/s)
- L = specimen thickness (m)
- A = specimen area (m²)
- ΔP = pressure differential (Pa)
Specimen Requirements
Geometry:
- Minimum specimen diameter: 100 mm (4 in)
- Preferred specimen thickness: 13-50 mm (0.5-2 in)
- Maximum thickness: limited by equipment capacity
- Edge sealing: required to prevent bypass leakage
Conditioning:
- Temperature: 23°C ± 2°C (73°F ± 4°F)
- Relative humidity: 50% ± 5%
- Equilibration time: minimum 24 hours
- Moisture content: record at test initiation
Test Apparatus Components
| Component | Function | Critical Requirements |
|---|---|---|
| Permeameter chamber | Specimen mounting | Rigid, leak-tight construction |
| Pressure transducer | ΔP measurement | ±1 Pa accuracy, 0-500 Pa range |
| Flow meter | Airflow measurement | ±2% accuracy, variable range |
| Air supply | Pressure source | Regulated, oil-free compressed air |
| Temperature sensor | Ambient monitoring | ±0.5°C accuracy |
| Barometric sensor | Atmospheric pressure | ±50 Pa accuracy |
Measurement Procedure
Pressure differential selection:
- Test at minimum three pressures
- Range: 10-200 Pa typical
- Points distributed logarithmically
- Avoid pressure-induced material deformation
Data collection sequence:
- Install and seal specimen in chamber
- Apply lowest pressure differential
- Allow flow stabilization (30-60 seconds)
- Record steady-state flow and pressure
- Repeat for increasing pressure levels
- Verify repeatability with descending pressures
Flow regime verification: Calculate Reynolds number (Re) for each test point:
Re = (ρ × v × L) / μ
For Darcy flow (laminar): Re < 10 For turbulent flow: Re > 100 Transition region: 10 < Re < 100
Data Analysis
Linear regression: Plot flow velocity versus pressure gradient. For laminar flow, the relationship is linear:
v = (ka / μ) × (ΔP / L)
Slope yields ka/μ ratio. Calculate ka using standard air viscosity at test temperature.
Permeance calculation: Air permeance (C) incorporates specimen thickness:
C = ka / L (units: m³/(Pa·s·m²) or m/s)
Convert to I-P units: m/s × 2.96×10⁷ = perms at 75°F
ASTM E283: Air Leakage Through Exterior Windows, Doors, and Curtain Walls
ASTM E283 measures air leakage rates through assembled building components under static pressure differentials, representing installed performance.
Test Configuration
Chamber setup:
- Component mounted in rigid test frame
- All edges sealed to frame
- Pressure chamber: positive or negative mode
- Metering chamber for flow measurement
Pressure application:
- Standard test pressure: 75 Pa (1.57 psf)
- Alternative pressures: 150, 300 Pa for high-performance applications
- Minimum stabilization time: 10 seconds
- Test duration: sufficient for stable readings
Air Leakage Measurement
Flow rate determination: Measure volumetric airflow required to maintain test pressure:
Q = volumetric leakage rate (cfm or L/s)
Normalization methods:
| Basis | Units | Application |
|---|---|---|
| Area | cfm/ft² (L/s·m²) | Wall systems, curtain walls |
| Perimeter length | cfm/ft (L/s·m) | Operable windows, doors |
| Total assembly | cfm (L/s) | Individual component rating |
Performance Classification
AAMA/WDMA/CSA 101/I.S.2/A440:
| Performance Grade | Maximum Air Leakage at 75 Pa |
|---|---|
| R (Residential) | 0.30 cfm/ft² (1.5 L/s·m²) |
| LC (Light Commercial) | 0.30 cfm/ft² (1.5 L/s·m²) |
| CW (Commercial) | 0.06 cfm/ft² (0.3 L/s·m²) |
| AW (Architectural) | 0.06 cfm/ft² (0.3 L/s·m²) |
Field Testing Methods
ASTM E1186: Air Leakage of Building Envelopes
Measures installed air leakage characteristics using pressurization and depressurization techniques.
Equipment requirements:
- Blower door assembly with calibrated fan
- Digital pressure gauge (±1 Pa resolution)
- Temperature measurement devices
- Data acquisition system
Test protocol:
- Seal intentional openings (HVAC registers, exhaust fans)
- Establish baseline pressure difference
- Operate fan at multiple speeds
- Measure building pressure and flow at each point
- Test both pressurization and depressurization
- Average results for final leakage curve
Data presentation: Flow coefficient and pressure exponent from power law:
Q = C × ΔPⁿ
Where:
- Q = airflow rate (m³/h or cfm)
- C = flow coefficient
- ΔP = pressure difference (Pa)
- n = flow exponent (0.5-1.0, typically 0.65)
ASTM E779: Small Chamber Method
Portable chamber technique for isolated component testing in field conditions.
Chamber specifications:
- Volume: 0.1-1.0 m³ typical
- Construction: rigid frame with flexible membrane
- Seal interface: adhesive or mechanical clamp
- Pressure capacity: up to 300 Pa
Applications:
- Window and door leakage
- Penetration sealing effectiveness
- Material joint performance
- Repair verification testing
Specialized Test Methods
ASTM E1677: Heat-Air-Moisture Transport Properties
Dynamic testing under combined thermal and moisture gradients using guarded hot box apparatus.
Measurement capabilities:
- Air permeability under thermal stress
- Temperature-dependent permeance
- Coupled heat and moisture transport
- Convective loop formation detection
ISO 9972: Air Permeability of Buildings
International standard for whole-building airtightness testing with normalized reporting.
Key metrics:
- Air change rate at 50 Pa (ACH₅₀)
- Equivalent leakage area (ELA)
- Normalized leakage (NL)
- Specific leakage rate (SLR)
Instrumentation and Calibration
Differential Pressure Measurement
Micromanometer specifications:
- Resolution: 0.1 Pa minimum
- Accuracy: ±1% of reading or ±1 Pa
- Range: 0-500 Pa for material testing
- Temperature compensation: automatic
- Zero drift: <0.5 Pa per month
Calibration requirements:
- Frequency: annual minimum
- Reference standard: NIST-traceable
- Multiple points across operating range
- Documentation of calibration coefficients
Flow Measurement Devices
| Device Type | Range | Accuracy | Application |
|---|---|---|---|
| Laminar flow element | 0.1-100 L/min | ±2% reading | Low-permeability materials |
| Rotameter | 1-1000 L/min | ±3% full scale | General materials |
| Mass flow meter | 0.01-500 L/min | ±1% reading | Precision measurements |
| Orifice plate | 10-10,000 cfm | ±5% reading | Large assemblies |
Environmental Monitoring
Required measurements:
- Ambient temperature: ±0.5°C accuracy
- Barometric pressure: ±50 Pa accuracy
- Relative humidity: ±3% accuracy
- Wind speed (field tests): ±0.5 m/s
Data correction factors: Normalize flow measurements to standard conditions (20°C, 101.325 kPa):
Qstd = Qmeas × (Pstd/Pmeas) × (Tmeas/Tstd)
Data Interpretation and Reporting
Uncertainty Analysis
Primary error sources:
| Source | Typical Magnitude | Mitigation Strategy |
|---|---|---|
| Pressure measurement | ±2-5% | High-quality transducers, calibration |
| Flow measurement | ±2-10% | Multiple flow ranges, calibration |
| Temperature variation | ±1-3% | Environmental chamber testing |
| Edge leakage | ±5-15% | Careful specimen sealing verification |
| Material inhomogeneity | ±10-30% | Multiple specimens, statistical analysis |
Combined uncertainty: Calculate using root-sum-square method:
U = √(u₁² + u₂² + … + uₙ²)
Report results with 95% confidence interval.
Statistical Analysis
Minimum specimen count:
- Homogeneous materials: 3 specimens
- Variable materials: 5-10 specimens
- Field verification: 3 replicates minimum
Reporting parameters:
- Mean permeability or permeance
- Standard deviation
- Coefficient of variation
- Minimum and maximum values
- Number of specimens tested
Quality Control Checks
Test validity criteria:
- Flow regime verification (laminar assumption)
- Linear regression R² > 0.95 for Darcy flow
- Repeatability within ±10% between runs
- Hysteresis < 5% between increasing/decreasing pressure
- Zero-pressure flow reading < 1% of lowest test flow
Reference material testing:
- Periodic testing of standard materials
- Control charts for equipment performance
- Interlaboratory comparison programs
- NIST traceable reference specimens
Practical Considerations
Material-Specific Challenges
Fibrous insulation:
- Compression sensitivity during mounting
- Edge sealing without material distortion
- Anisotropic permeability (directional testing)
- Density variation effects
Membranes and barriers:
- Pinholes and manufacturing defects
- Installation damage simulation
- Temperature-dependent properties
- Aging and degradation assessment
Composite assemblies:
- Interface resistance identification
- Layer-by-layer testing for model validation
- Joint and penetration effects
- Thermal bridge interaction with airflow
Field vs. Laboratory Correlation
Laboratory advantages:
- Controlled environmental conditions
- Intrinsic material properties
- Repeatable test conditions
- Elimination of installation variables
Field testing advantages:
- As-installed performance
- Workmanship effects included
- Real operating conditions
- Quality assurance verification
Typical correlation factors: Field air leakage often 2-5× higher than laboratory values due to:
- Installation imperfections
- Material damage during construction
- Joint and interface effects
- Settling and structural movement
Related Test Standards
Supporting Methods
| Standard | Title | Application |
|---|---|---|
| ASTM C522 | Airflow Resistance of Acoustical Materials | Sound-absorbing materials |
| ASTM D737 | Air Permeability of Textile Fabrics | Membrane and fabric materials |
| ISO 7730 | Moderate Thermal Environments | Draft risk assessment |
| EN 12114 | Thermal Performance - Air Permeability | European building materials |
| CGSB 149.10 | Air Leakage Characteristics | Canadian building envelope testing |
Performance Verification Standards
- ASTM E1424: Rating of Joints by Air Leakage
- ASTM E2357: Air Leakage of Building Envelope Joints
- AAMA 502: Voluntary Specification for Field Testing
- RESNET Standard 380: Whole Building Air Leakage Testing