Vapor Retarders
Overview
Vapor retarders are materials or systems designed to reduce the rate of water vapor transmission through building envelope assemblies by vapor diffusion. The primary function is to limit moisture accumulation within wall, roof, and floor assemblies that could lead to condensation, material degradation, mold growth, or reduced thermal performance. Vapor retarder selection and placement depend on climate zone, assembly construction, interior moisture generation rates, and the relative vapor drive direction throughout the year.
The effectiveness of a vapor retarder is quantified by its water vapor permeance, which measures the rate of water vapor transmission through a material under specified conditions of temperature and humidity differential.
Fundamental Physics
Vapor Transmission Mechanisms
Water vapor moves through building materials by three primary mechanisms:
- Vapor diffusion: Molecular movement from high to low vapor pressure regions (governed by Fick’s law)
- Air leakage: Bulk moisture transport via air movement through gaps and penetrations (typically 100x more significant than diffusion)
- Capillary action: Liquid water movement through porous materials
Vapor retarders specifically address diffusion-driven moisture transport.
Driving Forces
The vapor pressure differential across an assembly drives diffusion:
ΔP = P_interior - P_exterior
Where:
- ΔP = vapor pressure differential (Pa or in. Hg)
- P_interior = interior vapor pressure (Pa)
- P_exterior = exterior vapor pressure (Pa)
The direction of vapor drive reverses seasonally in many climates:
- Winter: Interior to exterior (heating season)
- Summer: Exterior to interior in hot-humid climates with air conditioning
Permeance and Permeability
Permeance (M) measures vapor transmission rate through a specific material thickness:
M = m / (A × t × Δp)
Where:
- M = permeance (perm or ng/(Pa·s·m²))
- m = mass of water vapor transmitted (grains or ng)
- A = area (ft² or m²)
- t = time (hr or s)
- Δp = vapor pressure differential (in. Hg or Pa)
Unit conversions:
- 1 perm = 1 grain/(hr·ft²·in. Hg)
- 1 metric perm = 1 ng/(Pa·s·m²)
- 1 perm = 57.4 ng/(Pa·s·m²)
Permeability (μ) is a material property independent of thickness:
μ = M × thickness
For multi-layer assemblies, permeances combine in series:
1/M_total = 1/M₁ + 1/M₂ + 1/M₃ + … + 1/M_n
This relationship shows that the layer with the lowest permeance controls the overall assembly performance.
Vapor Retarder Classification
ASHRAE 90.1, the International Building Code (IBC), and International Energy Conservation Code (IECC) classify vapor retarders into three classes based on permeance:
| Class | Permeance Range | Description | Typical Applications |
|---|---|---|---|
| Class I | 0.1 perm or less | Vapor impermeable | Cold climates (Zones 5-8), interior side |
| Class II | 0.1 < perm ≤ 1.0 | Vapor semi-impermeable | Mixed climates (Zones 3-4) |
| Class III | 1.0 < perm ≤ 10 | Vapor semi-permeable | Warm climates (Zones 1-2), allows drying |
This classification system originates from ASTM E1745 “Standard Specification for Plastic Water Vapor Retarders Used in Contact with Soil or Granular Fill under Concrete Slabs.”
Testing Standards
Permeance values are determined per:
- ASTM E96: Standard Test Methods for Water Vapor Transmission of Materials
- Procedure A (Desiccant Method): Dry cup test, measures permeance at low humidity
- Procedure B (Water Method): Wet cup test, measures permeance at high humidity
- ASTM E154: Standard Test Methods for Water Vapor Retarders Used in Contact with Earth Under Concrete Slabs
- ASTM C1699: Standard Test Method for Moisture Retention Curves of Porous Building Materials Using Pressure Plates
Many materials exhibit different permeance values between wet cup and dry cup tests due to moisture-dependent transport properties.
Class I Vapor Retarders (≤0.1 Perm)
Material Types and Properties
| Material | Typical Permeance | Thickness | Applications |
|---|---|---|---|
| Polyethylene sheet | 0.06 perm | 6 mil (0.15 mm) | Walls, crawlspaces |
| Aluminum foil | 0.0 perm | 1 mil (0.025 mm) | Faced insulation |
| Rubberized asphalt | 0.05 perm | 40 mil (1 mm) | Below-grade walls |
| Sheet metal | 0.0 perm | Various | Ductwork vapor barrier |
| Glass | 0.0 perm | 1/8 in. (3 mm) | Essentially impermeable |
| Vapor retarder paint | 0.05-0.09 perm | Multiple coats | Retrofit applications |
Polyethylene Sheets
Continuous polyethylene (poly) sheeting remains the most common Class I vapor retarder for residential and light commercial construction in cold climates.
Specifications:
- Minimum thickness: 6 mil (0.15 mm) per most building codes
- Material: Low-density polyethylene (LDPE) or linear low-density polyethylene (LLDPE)
- Reinforcement: Available with fiber scrim for tear resistance
- Permeance: 0.06 perm for 6 mil thickness
- Standards: ASTM E1745 Type I
Installation requirements:
- Continuous installation with lapped seams (minimum 6 in. overlap)
- Sealed at all penetrations (electrical boxes, pipes, ducts)
- Sealed to framing at top and bottom
- Protected from UV exposure (degrades within weeks)
- Installed on warm-in-winter side of insulation
Advantages:
- Low cost per square foot
- Widely available
- Predictable performance
- Easy to verify installation
Disadvantages:
- Cannot dry if wetted during construction
- Vulnerable to construction damage
- Difficult to seal penetrations effectively
- May trap moisture in assemblies with dual vapor drives
Foil-Faced Materials
Aluminum foil provides essentially zero vapor transmission and often serves as a radiant barrier simultaneously.
Common applications:
- Kraft-foil-kraft facing on fiberglass batts
- Foil-faced rigid insulation boards
- Foil-faced bubble wrap insulation
- Radiant barrier sheathing
Permeance: <0.01 perm when foil is intact
Critical considerations:
- Any puncture creates a high permeance pathway
- Reflective surface must face air space (minimum 3/4 in.) to function as radiant barrier
- Conductive material requires careful electrical safety considerations
Vapor Retarder Paints
Specialized low-permeance coatings applied directly to interior gypsum board or plaster.
Performance characteristics:
- Permeance range: 0.05-0.09 perm (typically 2-3 coats)
- Application: Roller or spray to achieve required dry film thickness
- Dry film thickness: 3-5 mils minimum for rated permeance
- Coverage rate: 200-400 ft²/gallon per coat
Advantages:
- Retrofit-friendly (can be applied to existing walls)
- Self-sealing around penetrations
- No continuity gaps at studs
- Cost-effective for small areas
Disadvantages:
- Difficult to verify proper application thickness
- Performance depends on substrate condition
- May not meet code requirements in some jurisdictions
- Limited to Class I in specific formulations
Testing requirement: Project-specific testing per ASTM E96 recommended to verify permeance with actual substrate and application method.
Class II Vapor Retarders (0.1-1.0 Perm)
Class II materials provide moderate vapor diffusion resistance while allowing some drying potential. Appropriate for mixed climates and assemblies that may experience bidirectional vapor drives.
| Material | Permeance Range | Typical Use |
|---|---|---|
| Kraft-faced fiberglass batts | 0.4-1.0 perm | Walls in Zones 3-4 |
| Plywood (1/4 in.) | 0.7 perm | Sheathing |
| Bitumen-impregnated kraft | 0.3-0.5 perm | Wall membrane |
| Extruded polystyrene (1 in.) | 0.6-1.0 perm | Rigid insulation |
| Closed-cell spray foam (2 in.) | 0.8 perm | Cavity insulation |
Kraft-Faced Insulation
Asphalt-impregnated kraft paper laminated to fiberglass batts.
Performance:
- Permeance: 0.4-1.0 perm (varies by manufacturer)
- Test method: ASTM E96 Procedure A (dry cup)
- Installation: Paper flange stapled to stud faces
Design considerations:
- Permeance increases significantly when wet (up to 5-10 perm)
- Provides minimal air barrier function unless sealed
- Susceptible to mold growth if condensation occurs
- Not acceptable as sole vapor retarder in Climate Zones 5-8 per IECC
Closed-Cell Spray Foam
Medium-density closed-cell polyurethane foam applied as insulation that also functions as vapor retarder at sufficient thickness.
Vapor retarder thickness requirements:
- Class II: 2-3 inches (50-75 mm) depending on formulation
- Class I: 3-4+ inches (75-100+ mm)
Permeance relationship: Permeance inversely proportional to thickness:
M = k / t
Where:
- M = permeance (perm)
- k = material constant (perm-inch)
- t = thickness (inches)
Typical k-value for closed-cell SPF: 1.6-2.0 perm-inches
Verification: ASTM E2178 requires field samples to verify installed density and thickness, which determine vapor permeance.
Class III Vapor Retarders (1.0-10 Perm)
Semi-permeable materials that allow significant drying while still providing some vapor diffusion control.
| Material | Typical Permeance | Notes |
|---|---|---|
| Latex paint on gypsum | 2-3 perm | Single coat |
| Unfaced fiberglass batts | 50+ perm | Not a vapor retarder |
| Gypsum board (1/2 in.) | 20-50 perm | Depends on paint |
| Plywood (1/2 in.) | 0.5-1.5 perm | Thickness-dependent |
| OSB (1/2 in.) | 2-3 perm | Higher than plywood |
| Unpainted concrete block | 2-5 perm | Varies with density |
Latex Paint
Standard interior latex paint provides Class III vapor retardance.
Performance factors:
- Single coat: 5-10 perm
- Two coats: 2-5 perm
- Three coats: 1-3 perm (may approach Class II)
- Primer impact: Affects overall permeance
Application: Sufficient for Climate Zones 1-3 where code permits Class III vapor retarders on interior side of frame walls.
Vapor-Open Sheathing Membranes
Modern water-resistive barriers (WRB) designed for high vapor permeability to facilitate outward drying.
Permeance range: 10-50+ perm while maintaining liquid water resistance
Mechanism: Microporous or monolithic membrane technology blocks bulk water while passing water vapor.
Smart Vapor Retarders
Variable Permeability Membranes
Advanced materials that modify vapor permeance in response to ambient relative humidity conditions, providing low permeance during heating season (preventing inward diffusion) and high permeance during cooling season or after wetting events (enabling drying).
Operating Principle
Vapor permeance varies as a function of relative humidity:
M(RH) = M_dry + (M_wet - M_dry) × f(RH)
Typical performance curve:
| Relative Humidity | Permeance |
|---|---|
| 0-25% RH | 0.7 perm (Class II) |
| 50% RH | 2-5 perm (Class III) |
| 75% RH | 10-20 perm (vapor open) |
| 90%+ RH | 20-50 perm (highly permeable) |
Materials Technology
Polyamide films: Nylon-based membranes with humidity-responsive permeance
- Representative products: Certain European and North American brands
- Mechanism: Polymer chains expand with moisture absorption
- Permeance range: 0.7 to 40+ perm
Kraft-polymer hybrids: Multilayer systems combining traditional and responsive materials
Design Applications
Smart vapor retarders excel in:
- Mixed and marine climates with seasonal vapor drive reversals
- High-performance assemblies requiring drying capacity
- Retrofit applications where existing assemblies may trap moisture
- Cold climate applications with exterior continuous insulation (reduces condensation risk while allowing drying)
Installation Requirements
- Continuous installation with taped or sealed seams
- Membrane must be in direct contact with material subject to humidity variation (typically interior gypsum board)
- Cannot be encapsulated by impermeable layers
- Requires compatible tape and sealant systems
Performance Verification
Testing per ASTM E96 at multiple humidity conditions (typically 0%, 50%, and 90% RH) to establish full performance curve.
Vapor Retarder Placement
Climate-Based Guidelines
The fundamental principle: Install vapor retarders on the warm-in-winter side of the insulation to prevent warm, humid air from reaching cold surfaces where condensation can occur.
| Climate Zone | Heating Degree Days | Interior Vapor Retarder Requirement |
|---|---|---|
| Zone 1-2 | <3000 HDD65 | Not required, may be problematic |
| Zone 3 | 3000-4000 HDD65 | Class III acceptable |
| Zone 4 | 4000-5400 HDD65 | Class III or II recommended |
| Zone 5 | 5400-7200 HDD65 | Class II required (Class I traditional) |
| Zone 6 | 7200-9000 HDD65 | Class I or II required |
| Zone 7-8 | >9000 HDD65 | Class I required |
Marine climates (Zone 4C): Special consideration due to year-round moderate humidity and bidirectional vapor drives. Class III or smart vapor retarders preferred over Class I.
Code Requirements
International Residential Code (IRC) and International Building Code (IBC) via reference to IECC specify:
- Climate Zones 5, 6, 7, 8, and Marine 4: Class I, II, or III vapor retarder required on interior side of frame walls
- Climate Zones 1, 2, 3, 4 (except Marine): No interior vapor retarder required
Exceptions where interior vapor retarder not required:
- Vented cladding over minimum R-5 continuous insulation in Zones 5 and lower
- Continuous insulation R-values per climate zone on exterior
- Conditioned space sealed from wall cavity (spray foam assemblies)
Exterior Vapor Retarders
General rule: Avoid Class I vapor retarders on exterior side of assemblies in heating climates.
Rationale: Prevents interior-generated moisture from drying outward during heating season and traps construction moisture or bulk water intrusion.
Acceptable exterior materials:
- Class III vapor retarders (vapor semi-permeable)
- Vapor-open water-resistive barriers (>10 perm)
- Properly detailed drainage planes regardless of permeance
Exception: Climate Zones 1-2 with significant air conditioning loads may benefit from exterior vapor retarders to limit inward vapor drive, but only with vapor-open interior finishes.
Dual Vapor Retarders
Critical warning: Avoid installing vapor retarders on both sides of an insulated assembly.
Problem: Creates moisture trap with no drying pathway. Any moisture introduced by:
- Construction moisture in framing or insulation
- Bulk water leaks
- Air leakage condensation
- Diffusion from unanticipated direction
Cannot escape and accumulates until causing material damage, mold growth, or system failure.
Acceptable dual-layer assemblies:
- One Class I/II vapor retarder + one Class III or higher (enables drying to one side)
- Smart vapor retarder on one side + vapor-permeable material on other
- Both sides Class III or higher with proper air sealing (moisture can dry to both sides)
Installation Best Practices
Continuity Requirements
Vapor retarder effectiveness depends on continuous installation without gaps, tears, or unsealed penetrations. Air leakage through defects can transport 100 times more moisture than diffusion through intact vapor retarder.
Laps and seams:
- Minimum 6-inch overlap at all seams
- Tape or seal laps with compatible adhesive
- Lap seams over framing members when possible for mechanical support
- Shingled orientation: upper courses overlap lower courses
Penetrations:
- Seal around all electrical boxes with acoustical sealant, tape, or prefabricated boots
- Seal pipe and duct penetrations with compatible tape or sealant
- HVAC register boots sealed to vapor retarder
- Window and door rough openings sealed to vapor retarder membrane
Transitions:
- Seal to floor and ceiling systems
- Seal to partition walls
- Seal to foundation or slab
- Address inside and outside corners
Mechanical Protection
Vapor retarders require protection from physical damage:
- Install interior finish (gypsum board) promptly to protect membrane
- UV-sensitive materials (polyethylene) must be covered within days to weeks
- Minimize foot traffic during construction
- Patch tears and damage immediately with compatible tape or sealant
- Inspect before covering with finish materials
Sequencing Considerations
Wall assemblies:
- Install exterior sheathing and water-resistive barrier
- Install insulation (if cavity insulation)
- Install vapor retarder (if required)
- Install electrical and mechanical systems
- Seal penetrations
- Install interior finish
Roof assemblies:
- Install roof deck
- Install vapor retarder (if required, typically on deck in cold climates)
- Install insulation
- Install cover board
- Install roofing membrane
Below-grade applications:
- Prepare substrate (level, remove sharp objects)
- Install capillary break (gravel or sand layer)
- Install vapor retarder (polyethylene sheet)
- Protect with sand layer or pour slab directly
- Ensure continuity with wall vapor retarder
Material Compatibility
Sealant and Tape Selection
Vapor retarder tapes and sealants must be compatible with substrate materials and maintain adhesion under expected temperature and humidity conditions.
Polyethylene sealing:
- Acrylic-based construction tape (most common)
- Butyl-based tape (superior long-term adhesion)
- Acoustical sealant at complex details
Membrane sealing:
- Manufacturer-specified tape systems
- Primer may be required for porous substrates
- UV-resistant formulations for temporary exposure
Performance criteria:
- Adhesion testing: ASTM D3330 or AAMA 711
- Permeance: Sealed assembly should maintain vapor retarder class rating
- Durability: Maintain adhesion over design life (typically 50+ years)
Substrate Considerations
- Wood framing: Standard tapes and sealants adhere well to clean, dry wood
- Gypsum board: Primer or porous-surface tape formulations required
- Concrete: Requires moisture-tolerant adhesive or mechanical attachment
- Metal framing: Non-porous substrate requires specialized adhesive formulations
Hygrothermal Modeling and Analysis
Condensation Risk Assessment
Simplified steady-state analysis provides first-order condensation risk evaluation using the Glaser method:
- Calculate temperature profile through assembly using thermal resistances
- Determine dew point temperature at each layer interface
- Compare actual temperature to dew point at each interface
- Condensation risk exists where T < T_dew point
Limitations: Does not account for moisture storage, solar-driven diffusion, air leakage, or transient conditions.
WUFI and Advanced Modeling
Hygrothermal simulation software (WUFI, DELPHIN, MOISTURE-EXPERT) provides dynamic analysis including:
- Hourly climate data (temperature, RH, solar radiation, wind-driven rain)
- Material moisture storage functions
- Moisture-dependent material properties
- Two-dimensional moisture and heat flow
- Mold growth risk assessment
- Multiple-year simulations to assess moisture accumulation
Key outputs:
- Moisture content profiles over time
- Condensation quantity and location
- Drying rates and pathways
- Freeze-thaw risk in masonry
- Mold growth risk indices
Applications:
- Novel assembly designs without field performance history
- High-performance building envelopes
- Renovation projects with changed moisture conditions
- Conflict between energy efficiency and moisture safety
Validation
Models require validation against:
- Field monitoring data from existing buildings
- Laboratory test chamber measurements
- Established performance of conventional assemblies
Special Applications
Crawlspace Vapor Retarders
IRC requires minimum 6-mil polyethylene vapor retarder over exposed earth in crawlspaces.
Installation requirements:
- Extend up foundation walls minimum 6 inches
- Lap seams minimum 6 inches
- Hold in place with battens, rocks, or soil cover
- Seal or weight edges to prevent displacement
Performance enhancement: 10-mil or thicker cross-laminated polyethylene provides improved durability and puncture resistance.
Slab-on-Grade Applications
ASTM E1643 and IRC require vapor retarders under concrete slabs in buildings:
Specification: Minimum 10-mil thick Class A vapor retarder per ASTM E1745
Installation per ACI 302.1:
- Granular fill layer (minimum 4 inches compacted aggregate)
- Vapor retarder (10-15 mil polyethylene or reinforced membrane)
- Cushion layer (optional, protects membrane during concrete pour)
- Concrete slab
Critical details:
- Seal laps with compatible tape
- Seal penetrations (plumbing, electrical)
- Extend up grade beams and seal
- Protect from puncture during reinforcement and concrete placement
Note: Slabs receiving moisture-sensitive floor coverings may require lower permeance (<0.01 perm) to prevent flooring failure.
Cathedral Ceiling and Unvented Roof Assemblies
Unvented roof assemblies require specific vapor retarder strategies:
Option 1 - Rigid foam exterior: Sufficient exterior continuous insulation to maintain condensing surface above dew point (no interior vapor retarder required if ratios met per IRC Table R806.5)
Option 2 - Spray foam interior: Air-impermeable insulation (closed-cell spray foam) installed in contact with underside of roof deck acts as combined air barrier and vapor retarder
Option 3 - Vented assembly: Traditional vented cathedral ceiling with Class I or II vapor retarder on interior (warm) side
Cold Storage and Refrigerated Spaces
Refrigerated spaces require robust vapor retarder systems due to extreme vapor pressure differentials.
Design criteria:
- Class I vapor retarder on warm side (exterior of insulated envelope)
- Continuous, sealed installation with redundancy at joints
- Multiple layers at high-risk locations
- Thermal breaks at penetrations to prevent condensation on conductive elements
Common systems:
- Self-adhered rubberized asphalt membranes
- Heat-welded PVC or TPO membranes
- Multiple layers of mastic and reinforcing fabric
- Factory-fabricated insulated metal panels with integral vapor retarder
Common Mistakes and Failures
Improper Placement
Error: Installing Class I vapor retarder on cold side of insulation
Result: Traps moisture migrating from warm side, causing condensation at vapor retarder surface
Example: Polyethylene on exterior side of wall in heating climate
Discontinuities and Gaps
Error: Failing to seal seams, penetrations, or transitions
Result: Air leakage transports moisture at rates orders of magnitude higher than diffusion, condensation occurs at leak points
Common locations: Electrical boxes, HVAC penetrations, top and bottom plates, window/door rough openings
Dual Vapor Retarders
Error: Installing low-permeance materials on both sides of assembly
Result: Moisture trap with no drying pathway, progressive moisture accumulation
Example: Polyethylene interior + foil-faced exterior insulation in mixed climate
Inadequate Material Selection
Error: Using vapor-permeable material where code requires vapor retarder, or vice versa
Result: Either condensation damage or inability to dry
Example: Unfaced fiberglass batts in Climate Zone 6 (requires Class I, II, or III vapor retarder)
Inspection and Quality Assurance
Visual Inspection Criteria
- Continuous installation with no visible gaps or tears
- Proper lap width at seams (minimum 6 inches)
- Sealing tape or adhesive fully bonded with no edge lift
- Penetrations sealed with compatible material
- Transitions to other assemblies properly detailed and sealed
- Mechanical damage repaired before covering
Testing and Verification
Blower door testing: While primarily for air leakage, identifies major vapor retarder discontinuities through visual observation (membrane flexing) or infrared thermography during pressurization
Moisture monitoring: Install moisture sensors or hygropins in high-risk assemblies during construction to monitor performance over first heating seasons
Sample testing: Submit material samples for ASTM E96 testing to verify permeance ratings, particularly for:
- Vapor retarder paints (verify proper application)
- Multi-layer assemblies
- Novel or modified materials
References and Standards
ASHRAE Standards:
- ASHRAE 90.1: Energy Standard for Buildings Except Low-Rise Residential Buildings
- ASHRAE 160: Criteria for Moisture-Control Design Analysis in Buildings
- ASHRAE Handbook - Fundamentals, Chapter 26: Heat, Air, and Moisture Control in Building Assemblies
ASTM Standards:
- ASTM E96: Standard Test Methods for Water Vapor Transmission of Materials
- ASTM E1745: Standard Specification for Plastic Water Vapor Retarders
- ASTM E2178: Standard Test Method for Air Permeance of Building Materials
- ASTM D4397: Standard Specification for Polyethylene Sheeting for Construction, Industrial, and Agricultural Applications
Building Codes:
- International Building Code (IBC)
- International Residential Code (IRC)
- International Energy Conservation Code (IECC)
Other References:
- ACI 302.1R: Guide to Concrete Floor and Slab Construction
- ASTM E1643: Standard Practice for Installation of Water Vapor Retarders Used in Contact with Earth or Granular Fill Under Concrete Slabs
- Building Science Corporation: Information sheets on vapor retarders and diffusion
Conclusion
Vapor retarder selection, placement, and installation represent critical components of moisture-resistant building envelope design. Success requires understanding climate-specific moisture loading, assembly-specific condensation risk, and material-specific performance characteristics. The shift from prescriptive “always install polyethylene” approaches to performance-based strategies including smart vapor retarders and hygrothermal modeling reflects the increasing sophistication of building envelope design.
Proper vapor retarder design must be coordinated with air barrier continuity, drainage plane details, and thermal insulation strategy to achieve durable, energy-efficient building envelopes. In all cases, air sealing remains the first priority, as air leakage transports far more moisture than vapor diffusion through even highly permeable materials.