HVAC Systems Encyclopedia

A comprehensive encyclopedia of heating, ventilation, and air conditioning systems

Surface Condensation

Fundamentals of Surface Condensation

Surface condensation occurs when the temperature of a building surface falls below the dew point temperature of the adjacent air. This phenomenon represents a critical failure mode in building envelope design, leading to moisture accumulation, mold growth, material deterioration, and occupant health concerns.

The physical principle governing surface condensation:

Surface condensation occurs when: Tsurface ≤ Tdewpoint

Where:

  • Tsurface = actual surface temperature (°F or °C)
  • Tdewpoint = dew point temperature of adjacent air (°F or °C)

The dew point temperature represents the saturation temperature at which water vapor in air begins to condense. This temperature depends solely on the moisture content of the air and can be calculated from dry-bulb temperature and relative humidity.

Psychrometric Relationships

The dew point temperature is determined from psychrometric relationships:

Approximate dew point calculation (IP units):

Tdp = T - ((100 - RH) / 5)

More accurate Magnus-Tetens formula (SI units):

Tdp = (b × α(T, RH)) / (a - α(T, RH))

Where:

  • α(T, RH) = (a × T) / (b + T) + ln(RH/100)
  • a = 17.27 (dimensionless)
  • b = 237.7°C
  • T = dry-bulb temperature (°C)
  • RH = relative humidity (%)

Surface Temperature Calculation

The surface temperature of building envelope components is calculated using heat transfer principles and thermal resistance values.

Interior Surface Temperature

For a wall or envelope assembly exposed to interior and exterior conditions:

Tsi = Ti - q × Rsi

Where:

  • Tsi = interior surface temperature (°F or °C)
  • Ti = interior air temperature (°F or °C)
  • q = heat flux through assembly (Btu/h·ft² or W/m²)
  • Rsi = interior surface film resistance (h·ft²·°F/Btu or m²·K/W)

The heat flux through the assembly:

q = (Ti - To) / Rtotal

Where:

  • To = outdoor air temperature (°F or °C)
  • Rtotal = total thermal resistance of assembly (h·ft²·°F/Btu or m²·K/W)

Substituting and rearranging:

Tsi = Ti - [(Ti - To) / Rtotal] × Rsi

Alternative form:

Tsi = Ti - (Ti - To) × (Rsi / Rtotal)

This demonstrates that interior surface temperature depends on the ratio of interior surface resistance to total assembly resistance.

Temperature Index Method

The Temperature Index (TI) provides a normalized measure of surface temperature:

TI = (Tsi - To) / (Ti - To)

Temperature Index ranges from 0 to 1:

  • TI = 1.0: surface at interior air temperature (no heat loss)
  • TI = 0.0: surface at exterior air temperature (no insulation)
  • TI > 0.7: generally acceptable for condensation resistance

Relationship to thermal resistance:

TI = (Rtotal - Rsi) / Rtotal = 1 - (Rsi / Rtotal)

This equation shows that higher total R-values produce higher temperature indices and warmer interior surfaces.

Thermal Bridging Effects

Thermal bridges are localized areas of higher heat flow that create cold spots on interior surfaces, significantly increasing condensation risk.

Common Thermal Bridge Locations

Structural elements:

  • Steel studs in exterior walls
  • Concrete slab edges
  • Structural columns and beams penetrating envelope
  • Balcony connections

Envelope transitions:

  • Wall-to-roof junctions
  • Wall-to-floor interfaces
  • Foundation wall-to-wall connections
  • Window and door frames

Mechanical penetrations:

  • Pipe and duct penetrations
  • Electrical conduit runs
  • Recessed lighting fixtures

Linear Thermal Transmittance

Thermal bridges are characterized by linear thermal transmittance (ψ-value):

ψ = (L2D - ΣUj × lj)

Where:

  • ψ = linear thermal transmittance (W/m·K or Btu/h·ft·°F)
  • L2D = thermal coupling coefficient from 2D analysis (W/m·K)
  • Uj = U-factor of 1D element j (W/m²·K)
  • lj = length of 1D element j (m)

The additional heat loss due to thermal bridging:

Qbridge = ψ × L × ΔT

Where:

  • Qbridge = heat loss through thermal bridge (W or Btu/h)
  • L = length of thermal bridge (m or ft)
  • ΔT = temperature difference (K or °F)

Steel Stud Thermal Bridging

Steel studs create significant thermal bridging due to their high thermal conductivity (k ≈ 45 W/m·K vs. 0.04 W/m·K for insulation).

Effective R-value of steel-framed wall:

Reff = 1 / [(fs / Rstud path) + ((1 - fs) / Rcavity)]

Where:

  • Reff = effective R-value of assembly (h·ft²·°F/Btu)
  • fs = framing fraction (typically 0.15 to 0.25)
  • Rstud path = R-value through stud path (h·ft²·°F/Btu)
  • Rcavity = R-value through cavity path (h·ft²·°F/Btu)

Steel framing can reduce wall assembly R-value by 40-60% compared to clear-wall R-value.

Surface Film Coefficients

Surface film coefficients significantly impact surface temperature calculations.

Interior Surface Coefficients

ASHRAE provides standard interior surface film coefficients:

Surface Positionhi (Btu/h·ft²·°F)hi (W/m²·K)Rsi (h·ft²·°F/Btu)Rsi (m²·K/W)
Horizontal, heat flow up1.639.260.610.108
Vertical surface1.468.290.680.121
Horizontal, heat flow down1.086.130.920.163
45° slope, heat flow up1.609.090.620.110
45° slope, heat flow down1.327.500.760.134

Exterior Surface Coefficients

Exterior surface coefficients depend on wind speed and surface orientation:

Wind Speedho (Btu/h·ft²·°F)ho (W/m²·K)Rso (h·ft²·°F/Btu)Rso (m²·K/W)
7.5 mph (winter)6.0034.00.170.030
15 mph7.2040.90.140.024
Summer (natural)4.0022.70.250.044

Still Air Conditions

For enclosed air spaces and cavities:

Applicationh (Btu/h·ft²·°F)h (W/m²·K)R (h·ft²·°F/Btu)R (m²·K/W)
Non-reflective surface1.106.250.910.160
Single reflective surface0.593.351.700.299
Double reflective surface0.301.703.330.588

Window Condensation

Windows represent the most common location for surface condensation due to their lower thermal resistance compared to opaque walls.

Window Surface Temperature

For a simple window with single interior surface:

Twindow = Ti - (Ti - To) × (hi / (Uwindow))

Or equivalently:

Twindow = Ti - (Ti - To) × (Rsi / (1/Uwindow))

Where Uwindow is the center-of-glass U-factor.

Condensation Resistance Rating

The Condensation Resistance (CR) rating provides a standardized metric for window performance:

CR = 100 × [1 - (Uwindow × Rsi)]

Condensation Resistance ratings range from 0 to 100:

  • CR ≥ 50: Acceptable for most climates
  • CR ≥ 60: Good performance for cold climates
  • CR ≥ 70: Excellent performance for extreme climates

Window Performance Comparison

Glazing TypeU-Factor (Btu/h·ft²·°F)U-Factor (W/m²·K)CR RatingMin. To at 70°F, 40% RH
Single glazing1.045.912959°F (15°C)
Double, air fill0.492.786730°F (-1°C)
Double, argon fill0.422.397123°F (-5°C)
Triple, argon fill0.201.1486-1°F (-18°C)
Triple, krypton, low-e0.150.8590-14°F (-26°C)

Minimum outdoor temperature calculated for condensation at interior conditions of 70°F (21°C) and 40% RH (dew point 45°F or 7°C).

Edge-of-Glass and Frame Effects

The edge-of-glass region (within 2.5 inches of frame) exhibits higher heat loss due to:

  • Reduced insulating air space width
  • Spacer thermal bridging
  • Frame proximity effects

Edge-of-glass U-factors typically 10-30% higher than center-of-glass values.

Frame condensation risk zones:

Frame MaterialThermal ConductivityCondensation Risk
Aluminum, no breakk = 160 W/m·KExtremely high
Aluminum, thermal breakkeff = 5-10 W/m·KHigh
Vinyl, hollow chamberkeff = 0.15-0.20 W/m·KLow
Woodk = 0.10-0.15 W/m·KVery low
Fiberglassk = 0.25-0.35 W/m·KLow

Corner Conditions and Multidimensional Heat Flow

Building corners experience multidimensional heat flow, creating surface temperatures lower than one-dimensional calculations predict.

Corner Temperature Depression

At inside corners (two exterior walls meeting), heat flows in two directions, creating a localized cold zone.

Approximate corner temperature:

Tcorner ≈ Twall - [(Ti - To) × 0.1 to 0.2]

The temperature depression factor depends on:

  • Wall R-value
  • Corner geometry (90° vs. other angles)
  • Interior surface coefficient
  • Insulation continuity

Critical Corner Locations

Exterior corners (inside the building):

  • Wall-to-wall inside corners
  • Wall-to-ceiling corners
  • Wall-to-floor corners
  • Three-way intersections

Mitigation strategies:

  • Continuous insulation across corners
  • Increased insulation thickness at corners
  • Air sealing to prevent convective loops
  • Interior finish details to improve air circulation

Cold Surface Condensation Risk Assessment

Condensation Potential Index

The Condensation Potential Index (CPI) quantifies condensation risk:

CPI = (Tsurface - Tdewpoint) / (Ti - Tdewpoint)

Risk assessment criteria:

CPI ValueRisk LevelDesign Recommendation
CPI > 1.0No riskSurface above interior air temp (unusual)
0.2 < CPI < 1.0Low riskAcceptable for most applications
0.0 < CPI < 0.2Moderate riskEnhanced ventilation recommended
-0.2 < CPI < 0.0High riskRedesign required
CPI < -0.2Severe riskUnacceptable, guaranteed condensation

Surface Relative Humidity Prediction

The relative humidity at a surface can be calculated without explicit dew point:

RHsurface = RHinterior × exp[(-L × (Ti - Tsurface)) / (Tsurface + 273.15)²]

Where:

  • L = 5420 K (latent heat constant)
  • Tsurface in Kelvin for SI units
  • RH expressed as decimal (e.g., 0.50 for 50%)

Mold growth threshold: RHsurface > 80% for extended periods

Design Conditions for Condensation Analysis

ASHRAE Winter Design Conditions

Condensation analysis should use 99% or 99.6% winter design temperatures, not extreme minimums.

Common design interior conditions:

Building TypeTemperature (°F)Temperature (°C)Relative Humidity
Residential68-7220-2230-40%
Office70-7221-2230-40%
School68-7220-2230-50%
Hospital70-7521-2430-60%
Museum68-7220-2245-55%
Indoor pool75-8524-2950-60%

Climate-Specific Considerations

Cold climate (Climate Zones 6-8):

  • Use 99.6% design temperature
  • Assume 35% interior RH as upper limit for residential
  • Consider vapor retarders on interior side

Mixed-humid climate (Climate Zones 4A):

  • Analyze both winter and summer condensation
  • Consider vapor-open assemblies
  • Interior humidity may exceed 50% in summer

Hot-humid climate (Climate Zones 1-3):

  • Reverse condensation risk (exterior warm/humid, interior cool/dry)
  • Never use interior vapor barriers
  • Consider vapor retarders on exterior

Thermal Imaging Analysis

Infrared thermography provides direct measurement of surface temperatures for condensation risk assessment.

Thermographic Survey Procedures

Survey requirements:

  • Minimum 20°F (11°C) temperature difference across envelope
  • Performed during heating season for cold climate analysis
  • Interior surfaces surveyed from inside
  • Exterior surfaces surveyed from outside

Temperature measurement accuracy:

  • Emissivity setting: 0.90-0.95 for painted surfaces
  • Reflected temperature compensation required
  • Atmospheric correction for exterior surveys

Identifying Condensation Risk Zones

Thermal anomalies indicating high condensation risk:

Temperature DepressionRisk LevelLikely Cause
2-4°F (1-2°C) below adjacent surfaceLowNormal variation
5-8°F (3-4°C) below adjacent surfaceModerateMinor thermal bridge
9-15°F (5-8°C) below adjacent surfaceHighSignificant thermal bridge
>15°F (>8°C) below adjacent surfaceSevereMissing insulation or major defect

Quantitative Analysis

From thermal images, calculate condensation margin:

Condensation Margin = Tmeasured - Tdewpoint

Safety factor:

  • Margin ≥ 5°F (3°C): Acceptable
  • Margin = 2-5°F (1-3°C): Monitor during cold weather
  • Margin < 2°F (<1°C): High risk, mitigation required

Prevention Strategies and Best Practices

Envelope Design Measures

Increase thermal resistance:

  • Higher R-value insulation
  • Continuous insulation over framing
  • Thermal break in metal components
  • High-performance glazing systems

Minimize thermal bridging:

  • Advanced framing techniques
  • Structural thermal breaks at balconies
  • Insulated concrete forms (ICF)
  • Thermally broken window frames

Typical minimum R-values to prevent condensation at 70°F, 40% RH, -10°F outdoor:

Climate ZoneMin. Wall R-valueMin. Roof R-valueMin. Window U-factor
6R-20R-49U-0.35
7R-25R-60U-0.30
8R-30R-60U-0.25

Humidity Control Strategies

Source control:

  • Kitchen and bathroom exhaust ventilation
  • Clothes dryer vented to exterior
  • No unvented combustion appliances
  • Dehumidification in high-moisture areas

Ventilation requirements (ASHRAE 62.2):

  • Continuous mechanical ventilation in tight buildings
  • Minimum 7.5 cfm per occupant + 1 cfm per 100 ft² floor area
  • Balanced ventilation with heat recovery in cold climates

Target interior humidity levels:

Outdoor TemperatureMaximum Interior RH (%)
40°F (4°C)45%
20°F (-7°C)40%
0°F (-18°C)35%
-10°F (-23°C)30%
-20°F (-29°C)25%

Surface Temperature Enhancement

Interior surface measures:

  • Increase interior surface coefficient through air circulation
  • Avoid furniture blocking exterior walls
  • Ensure registers direct air across cold surfaces
  • Eliminate dead air zones at corners and behind furniture

Insulation placement:

  • Eliminate compression at corners and edges
  • Extend insulation fully into corners
  • Seal insulation to framing to eliminate air gaps
  • Use spray foam at difficult-to-insulate locations

Detail Design Considerations

Critical details requiring special attention:

  1. Foundation wall-to-frame wall transition

    • Continuous insulation across transition
    • Air barrier continuity maintained
    • No thermal short-circuit through rim joist
  2. Window rough opening

    • Sill pan for drainage
    • Continuous air barrier around frame
    • Insulation packed to frame (not compressed)
    • Interior return (if used) detailed to avoid cold surface
  3. Roof-to-wall connection

    • Raised heel truss or energy truss
    • Full-depth insulation extending over wall top plate
    • Ventilation baffles maintaining air space
  4. Pipe and duct penetrations

    • Seal penetrations with appropriate materials
    • Insulate penetrating elements
    • Maintain insulation continuity around penetrations

Performance Verification

Calculation Verification

Required analysis for critical projects:

  • 2D or 3D heat transfer modeling at thermal bridges
  • Hygrothermal simulation for moisture accumulation risk
  • Annual moisture balance calculations

Software tools:

  • THERM (2D heat transfer)
  • WUFI (hygrothermal analysis)
  • HEAT3 (3D heat transfer)

Field Verification Methods

During construction:

  • Infrared thermography of completed assemblies
  • Blower door testing for air leakage
  • Tracer gas testing for specific leak locations
  • Insulation depth verification

Post-occupancy:

  • Winter season thermographic survey
  • Surface temperature monitoring at critical locations
  • Indoor humidity monitoring
  • Occupant feedback on condensation occurrence

Acceptance Criteria

Performance metrics:

ParameterTargetAcceptableMarginalUnacceptable
Window CR rating≥70≥6050-59<50
Surface temp margin>5°F3-5°F1-3°F<1°F
Surface RH<70%70-75%75-80%>80%
Thermal bridge ψ-value<0.10.1-0.20.2-0.3>0.3 W/m·K

Code and Standard References

ASHRAE Standards:

  • ASHRAE 90.1: Energy Standard for Buildings Except Low-Rise Residential Buildings
  • ASHRAE 160: Criteria for Moisture-Control Design Analysis in Buildings
  • ASHRAE Handbook - Fundamentals, Chapter 25: Heat, Air, and Moisture Control

Building Codes:

  • International Energy Conservation Code (IECC)
  • International Residential Code (IRC), Chapter 11
  • International Building Code (IBC), Chapter 14

Related Standards:

  • NFRC 500: Procedure for Determining Fenestration Product Condensation Resistance
  • ISO 13788: Hygrothermal Performance of Building Components
  • ASTM C1363: Standard Test Method for Thermal Performance of Building Materials

Conclusion

Surface condensation analysis requires understanding of heat transfer, psychrometrics, building envelope construction, and climate conditions. Proper design considers thermal bridging, utilizes accurate surface temperature calculations, and verifies performance through analysis and field testing. Prevention strategies include enhanced thermal resistance, thermal bridge mitigation, humidity control, and careful detailing at critical locations. HVAC professionals must integrate envelope performance with mechanical system design to achieve condensation-free building envelopes throughout the service life.