Condensation Risk Assessment
Technical Overview
Condensation risk assessment evaluates the potential for moisture accumulation on surfaces or within building envelope assemblies when air reaches its dew point temperature. This analysis combines psychrometric principles, heat transfer calculations, and moisture transport modeling to predict condensation occurrence under various environmental conditions.
The assessment process identifies critical surfaces, calculates temperature factors, evaluates thermal resistance ratios, and applies moisture accumulation criteria to determine acceptability. Proper risk assessment prevents structural damage, mold growth, thermal performance degradation, and indoor air quality issues.
Fundamental Condensation Criteria
Dew Point Temperature Relationship
Condensation occurs when surface temperature drops below the dew point temperature of adjacent air:
T_surface ≤ T_dewpoint → Condensation occurs
Where:
- T_surface = Surface temperature (°F or °C)
- T_dewpoint = Dew point temperature of adjacent air (°F or °C)
The dew point temperature is determined from:
T_dp = T - [(100 - RH)/5] (Approximation in °C)
Or using psychrometric equations:
T_dp = 243.04 × [ln(RH/100) + (17.625×T)/(243.04+T)] / [17.625 - ln(RH/100) - (17.625×T)/(243.04+T)]
Where:
- T = Dry-bulb temperature (°C)
- RH = Relative humidity (%)
Critical Surface Temperature
The minimum surface temperature that prevents condensation:
T_critical = T_dewpoint + ΔT_safety
Where:
- ΔT_safety = Safety margin (typically 2-5°F or 1-3°C)
Temperature Factor (f-factor)
Definition and Calculation
The temperature factor quantifies how close a surface temperature approaches the indoor air temperature relative to the indoor-outdoor temperature difference:
f = (T_si - T_o) / (T_i - T_o)
Where:
- f = Temperature factor (dimensionless, 0 to 1)
- T_si = Interior surface temperature (°F or °C)
- T_i = Indoor air temperature (°F or °C)
- T_o = Outdoor air temperature (°F or °C)
Minimum Temperature Factor
The minimum temperature factor to prevent condensation:
f_min = (T_dp - T_o) / (T_i - T_o)
For acceptable performance:
f_actual ≥ f_min
Temperature Factor Requirements
Typical minimum temperature factors by climate zone:
| Climate Zone | Winter Design Temp | Indoor RH | Minimum f-factor |
|---|---|---|---|
| 1 (Warm) | 40°F | 40% | 0.30 |
| 2 | 30°F | 40% | 0.40 |
| 3 | 20°F | 35% | 0.45 |
| 4 | 10°F | 35% | 0.50 |
| 5 | 0°F | 30% | 0.55 |
| 6 | -10°F | 30% | 0.60 |
| 7 (Cold) | -20°F | 25% | 0.65 |
| 8 (Subarctic) | -30°F | 25% | 0.70 |
Thermal Resistance Ratio Method
Surface Temperature Calculation
Interior surface temperature from thermal resistance ratios:
T_si = T_i - [(T_i - T_o) × R_si] / R_total
Where:
- R_si = Interior surface film resistance (h·ft²·°F/Btu)
- R_total = Total assembly R-value (h·ft²·°F/Btu)
Total Assembly Resistance
R_total = R_si + R_1 + R_2 + ... + R_n + R_so
Where:
- R_1, R_2, R_n = Layer resistances
- R_so = Exterior surface film resistance
Critical Resistance Ratio
The ratio of interior thermal resistance to total resistance:
R_ratio = R_si / R_total
Lower ratios indicate warmer interior surfaces and reduced condensation risk.
Condensation Resistance Factor (CRF)
Definition
The Condensation Resistance Factor quantifies the assembly’s resistance to condensation formation:
CRF = (T_si - T_o) / (T_dp - T_o)
Performance criteria:
- CRF ≥ 1.0: No condensation expected
- CRF = 0.8-1.0: Marginal, monitor conditions
- CRF < 0.8: Condensation likely, redesign required
Modified CRF for Safety Margin
CRF_modified = (T_si - T_o) / (T_dp + ΔT_safety - T_o)
Design target: CRF_modified ≥ 1.1
ASHRAE Standard 160 Criteria
Scope and Application
ASHRAE Standard 160 “Criteria for Moisture-Control Design Analysis in Buildings” provides criteria for preventing mold growth, material degradation, and moisture-related problems.
Surface Moisture Index (SMI)
The 30-day running average surface relative humidity:
SMI = (1/30) × Σ(RH_surface,i) for i = 1 to 30 days
Acceptance criteria:
- SMI < 80%: Acceptable for most materials
- SMI ≥ 80%: Mold growth potential exists
Surface Relative Humidity Calculation
RH_surface = (P_sat(T_si) / P_sat(T_i)) × RH_i × 100%
Where:
- P_sat(T) = Saturation vapor pressure at temperature T
- RH_i = Indoor relative humidity (%)
Saturation Vapor Pressure
Using the Magnus-Tetens equation:
P_sat(T) = 610.78 × exp[(17.27 × T) / (T + 237.3)] (Pa, T in °C)
Or in English units:
P_sat(T) = 0.1171 × exp[(18.678 - T/234.5) × T / (257.14 + T)] (psi, T in °F)
Mold Growth Index
ASHRAE 160 references the VTT mold growth model:
M(t+Δt) = M(t) + max(0, (1/7) × k_1 × k_2 × Δt)
Where:
- M = Mold index (0-6 scale)
- k_1 = Intensity factor (function of RH and T)
- k_2 = Material susceptibility factor
- Δt = Time increment (weeks)
Acceptance: M < 3 (no visible growth)
Design Criteria Summary
| Parameter | Limit | Duration |
|---|---|---|
| Surface RH | < 80% | 30-day average |
| Surface RH | < 100% | Instantaneous |
| Mold Index | < 3 | Annual analysis |
| MC (wood) | < 16% | Monthly average |
Monthly Analysis Method
Overview
Monthly analysis evaluates condensation risk throughout the annual cycle using representative monthly conditions rather than worst-case hourly data.
Monthly Design Conditions
For each month, establish:
- Mean outdoor temperature (T_o,monthly)
- Mean indoor temperature (T_i,monthly)
- Mean outdoor relative humidity (RH_o,monthly)
- Design indoor relative humidity (RH_i,monthly)
- Indoor moisture generation rate (G)
Indoor Humidity Ratio Calculation
W_i = W_o + (G × 7000) / (ρ × Q)
Where:
- W_i = Indoor humidity ratio (lb_w/lb_da)
- W_o = Outdoor humidity ratio (lb_w/lb_da)
- G = Moisture generation rate (lb/h)
- ρ = Air density (lb/ft³)
- Q = Ventilation rate (cfm)
Monthly Surface Temperature
T_si,monthly = T_i,monthly - [(T_i,monthly - T_o,monthly) × R_si] / R_total
Monthly Condensation Hours
Estimate hours per month when T_si < T_dp:
H_condensation = N_hours × P(T_si < T_dp)
Where:
- N_hours = Hours in month (720, 744, etc.)
- P(T_si < T_dp) = Probability of condensation
Cumulative Moisture Accumulation
M_accumulated = Σ[h_fg × ρ_air × (W_dp - W_si) × v_air × H_condensation]
Where:
- h_fg = Latent heat of vaporization (1060 Btu/lb)
- ρ_air = Air density (0.075 lb/ft³)
- W_dp, W_si = Humidity ratios at dew point and surface
- v_air = Air velocity near surface (fpm)
Acceptance Criteria
Monthly analysis acceptance:
- No month exceeds 100 hours of condensation
- Total annual condensation < 500 hours
- Condensation periods allow complete drying
- No trapped moisture accumulation
Interstitial Condensation Analysis
Layer-by-Layer Temperature Distribution
Temperature at interface between layers m and m+1:
T_m = T_i - [(T_i - T_o) × Σ(R_1 to R_m)] / R_total
Vapor Pressure at Each Layer
P_v,m = P_v,i - [(P_v,i - P_v,o) × Σ(M_1 to M_m)] / M_total
Where:
- P_v = Vapor pressure (in. Hg or Pa)
- M = Vapor permeance (perm)
- M_total = Total assembly vapor permeance
Saturation Vapor Pressure Comparison
At each interface:
If P_v,m > P_sat(T_m): Condensation occurs at interface m
Condensation Rate Calculation
q_condensation = (P_v,m - P_sat(T_m)) / M_m (lb/h·ft² or g/h·m²)
Risk Classification System
Low Risk Conditions
- f-factor ≥ 0.70
- CRF ≥ 1.2
- Surface RH < 70% monthly average
- No interstitial condensation
- All months meet criteria
Moderate Risk Conditions
- f-factor = 0.60-0.70
- CRF = 1.0-1.2
- Surface RH = 70-80% monthly average
- Minor condensation (< 50 hours/month)
- Adequate drying potential
High Risk Conditions
- f-factor < 0.60
- CRF < 1.0
- Surface RH > 80% monthly average
- Frequent condensation (> 100 hours/month)
- Limited drying potential
- Interstitial condensation present
Unacceptable Risk
- f-factor < 0.50
- CRF < 0.8
- Surface RH > 90%
- Continuous condensation conditions
- No drying periods
- Structural damage potential
Design Considerations
Thermal Bridge Evaluation
Linear thermal bridging reduces local surface temperature:
ψ = Q / (ΔT × L)
Where:
- ψ = Linear thermal transmittance (Btu/h·°F·ft)
- Q = Additional heat loss through bridge (Btu/h)
- L = Length of bridge (ft)
Adjusted surface temperature:
T_si,bridge = T_i - [(T_i - T_o) × (R_si + ψ×L/A)] / R_total
Air Leakage Impact
Air leakage through envelope increases local condensation risk:
q_infiltration = ρ × c_p × Q_leak × (T_i - T_o)
Exfiltration deposits moisture within wall assembly.
Moisture Storage Capacity
Materials with high moisture storage capacity buffer condensation:
C_moisture = ∂M/∂RH × ∂RH/∂P_v
Where:
- C_moisture = Moisture capacitance (lb/psi)
- M = Moisture content (lb_w/lb_material)
Drying Potential Assessment
The drying time constant:
τ_dry = (M_stored × h_fg) / (ΔP_v / M_total)
Shorter time constants indicate better drying potential.
Best Practices and Recommendations
Assessment Protocol
- Identify critical surfaces and assemblies
- Establish design conditions (outdoor/indoor)
- Calculate thermal resistance distributions
- Determine surface temperatures at critical locations
- Evaluate dew point temperatures
- Calculate temperature factors and CRF values
- Perform monthly analysis over annual cycle
- Check interstitial condensation potential
- Evaluate thermal bridges and penetrations
- Assess drying potential between condensation periods
- Apply ASHRAE 160 mold growth criteria
- Classify risk level and recommend mitigation
Mitigation Strategies by Risk Level
Moderate Risk:
- Increase thermal resistance
- Relocate insulation outboard
- Improve air sealing
- Control indoor humidity
- Add vapor retarders if appropriate
High Risk:
- Redesign assembly thermal performance
- Add continuous exterior insulation
- Install ventilation or drainage cavities
- Implement active humidity control
- Consider alternative materials
Unacceptable Risk:
- Complete assembly redesign mandatory
- Increase R-value significantly
- Add thermal breaks at bridges
- Active dehumidification required
- Regular monitoring and maintenance protocol
Climate-Specific Considerations
Cold Climates:
- Focus on interior surface condensation
- Evaluate thermal bridges rigorously
- Control indoor humidity levels (< 35% RH in winter)
- Ensure adequate insulation R-values
- Use interior vapor retarders appropriately
Hot-Humid Climates:
- Assess exterior surface condensation in summer
- Evaluate reverse vapor drive potential
- Control air conditioning overcooling
- Consider vapor-permeable exterior layers
- Ensure adequate drainage and ventilation
Mixed Climates:
- Evaluate both heating and cooling seasons
- Use vapor semi-permeable assemblies
- Assess bi-directional drying potential
- Consider variable permeance membranes
- Monitor actual performance post-occupancy
Documentation Requirements
Complete assessment documentation includes:
- Design climate data sources
- Indoor condition assumptions and basis
- Thermal resistance calculations with layer details
- Surface temperature calculations at critical locations
- Temperature factor and CRF calculations
- Monthly analysis results table
- Interstitial condensation analysis
- ASHRAE 160 compliance demonstration
- Risk classification determination
- Mitigation measures if required
Code and Standard References
- ASHRAE Standard 160: Criteria for Moisture-Control Design Analysis in Buildings
- ASHRAE Handbook—Fundamentals, Chapter 25: Heat, Air, and Moisture Control in Building Assemblies
- ASHRAE Handbook—Fundamentals, Chapter 1: Psychrometrics
- ISO 13788: Hygrothermal Performance of Building Components and Building Elements
- NFRC 500: Procedure for Determining Fenestration Product Condensation Resistance Values
- WUFI and similar hygrothermal simulation tools
- International Energy Conservation Code (IECC)
- Local building codes and amendments