Air Barrier Vs Vapor Retarder
Overview
Air barriers and vapor retarders serve distinct functions in building envelope moisture control, yet confusion between these two systems remains common in practice. An air barrier controls moisture transport via air leakage (convection), while a vapor retarder controls moisture transport via diffusion. Understanding the fundamental differences between these systems is critical because air leakage typically transports 10-100 times more moisture than vapor diffusion under equivalent driving forces.
The distinction becomes critical in climate-specific design. In heating climates, uncontrolled air leakage during winter can deposit moisture within wall cavities through exfiltration, leading to condensation on cold surfaces. In cooling climates, infiltration of humid outdoor air can cause similar problems on cooled interior surfaces. Vapor diffusion, while slower, operates continuously and must be managed through appropriate retarder placement.
Fundamental Differences
Transport Mechanisms
Air barriers control moisture movement by bulk air transport (convection), while vapor retarders control moisture movement by molecular diffusion. The moisture transport capacity of these mechanisms differs by orders of magnitude:
Moisture Transport by Air Leakage:
M_air = ρ_air × ω × Q_air
Where:
- M_air = Moisture transport rate by air leakage (kg/s)
- ρ_air = Air density (kg/m³)
- ω = Humidity ratio (kg water/kg dry air)
- Q_air = Air leakage rate (m³/s)
Moisture Transport by Vapor Diffusion:
M_diff = δ × A × Δp_v / d
Where:
- M_diff = Moisture transport rate by diffusion (kg/s)
- δ = Vapor permeability of material (kg/(s·m·Pa))
- A = Area (m²)
- Δp_v = Vapor pressure difference (Pa)
- d = Material thickness (m)
Quantitative Comparison
For a typical 1 m² wall section with indoor conditions at 21°C, 50% RH and outdoor conditions at 0°C, 80% RH:
| Transport Mode | Moisture Flow Rate | Relative Magnitude |
|---|---|---|
| Air leakage at 0.1 L/(s·m²) | ~0.08 g/h | 100× |
| Vapor diffusion through gypsum board | ~0.0008 g/h | 1× |
This 100:1 ratio demonstrates why air barrier performance typically dominates moisture control effectiveness.
Performance Criteria
Air Barrier Requirements
ASHRAE 90.1 and the International Energy Conservation Code (IECC) define air barrier performance based on maximum air leakage rates:
Assembly Air Leakage Limits:
| Assembly Type | Maximum Air Leakage (L/(s·m²) at 75 Pa) |
|---|---|
| Walls | 0.20 |
| Roofs | 0.20 |
| Floors | 0.20 |
Material Air Leakage Limits:
| Material Category | Maximum Air Leakage (L/(s·m²) at 75 Pa) |
|---|---|
| Rigid materials | 0.02 |
| Flexible membranes | 0.02 |
| Sealed joints | 0.20 |
Air Barrier Continuity:
The air barrier system must form a continuous plane around the building thermal envelope. Discontinuities at the following locations require specific detailing:
- Wall-to-roof transitions
- Wall-to-foundation transitions
- Penetrations (windows, doors, mechanical, electrical)
- Material transitions
- Construction joints
Vapor Retarder Requirements
The International Residential Code (IRC) and International Building Code (IBC) classify vapor retarders based on permeance:
Vapor Retarder Classes (Per IRC R702.7 and IBC 1405.3):
| Class | Permeance | Description | Example Materials |
|---|---|---|---|
| Class I | ≤0.1 perm | Vapor impermeable | Polyethylene sheet, aluminum foil, sheet metal, rubber membrane |
| Class II | >0.1 to ≤1.0 perm | Vapor semi-impermeable | Kraft-faced insulation, unfaced XPS (>1 inch), certain paints |
| Class III | >1.0 to ≤10 perm | Vapor semi-permeable | Latex paint, unfaced fiberglass batt, plywood, OSB |
| Not a vapor retarder | >10 perm | Vapor permeable | Unpainted gypsum board, unfaced mineral wool, open-cell spray foam |
Permeance Calculation:
Permeance (M) is defined as:
M = δ / d
Where:
- M = Permeance (kg/(Pa·s·m²)) or (perm)
- δ = Vapor permeability (kg/(s·m·Pa))
- d = Material thickness (m)
Unit Conversion:
- 1 perm (US) = 57.4 ng/(Pa·s·m²) = 5.74 × 10⁻¹¹ kg/(Pa·s·m²)
- 1 perm-inch = 1.46 × 10⁻¹² kg/(Pa·s·m)
Material Properties
Air Barrier Materials
Rigid Air Barriers:
| Material | Air Permeability (L/(s·m²) at 75 Pa) | Installation Notes |
|---|---|---|
| Gypsum board (sealed) | <0.02 | Requires sealed joints, penetrations |
| Exterior gypsum sheathing | <0.02 | Requires sealed joints, face-sealed fasteners |
| Cement board | <0.02 | Joints must be sealed with appropriate mastic |
| Structural sheathing (sealed) | <0.02 | OSB or plywood with sealed joints and penetrations |
| Cast-in-place concrete | <0.02 | Inherently air-tight, seal formwork penetrations |
| Precast concrete panels | <0.02 | Seal panel joints with appropriate sealant |
Flexible Air Barriers:
| Material | Air Permeability (L/(s·m²) at 75 Pa) | Installation Requirements |
|---|---|---|
| Self-adhered membranes | <0.02 | Continuous substrate, no voids, proper adhesion |
| Mechanically fastened membranes | <0.02 | Overlapped seams, sealed fastener penetrations |
| Fluid-applied membranes | <0.02 | Minimum dry film thickness, proper surface prep |
| House wraps (taped seams) | <0.02 | All seams taped, fastener penetrations sealed |
Air Barrier Coatings:
Spray-applied air barriers require proper surface preparation and minimum dry film thickness:
| Product Type | Typical Dry Film Thickness | Substrate Requirements |
|---|---|---|
| Water-based acrylic | 20-40 mils (0.5-1.0 mm) | Clean, dry, free of oils/dust |
| Vapor-permeable coating | 20-30 mils (0.5-0.75 mm) | Can accommodate substrate moisture |
| Vapor-impermeable coating | 30-60 mils (0.75-1.5 mm) | Dry substrate required |
Vapor Retarder Materials
Class I Vapor Retarders (≤0.1 perm):
| Material | Permeance (perm) | Application | Limitations |
|---|---|---|---|
| Polyethylene sheet (6 mil) | 0.06 | Interior in heating climates | Not recommended in mixed/cooling climates |
| Aluminum foil (1 mil) | 0.05 | Facing on insulation products | Corrosion potential in high humidity |
| Rubberized asphalt membrane | 0.05 | Below-grade waterproofing | High cost, temperature sensitive |
| Sheet metal | 0.00 | Mechanical equipment, ducts | Condensation potential |
| Self-adhered bituminous membrane | 0.05-0.08 | Foundation waterproofing | UV degradation if exposed |
Class II Vapor Retarders (>0.1 to ≤1.0 perm):
| Material | Permeance (perm) | Application | Benefits |
|---|---|---|---|
| Kraft facing on insulation | 0.3-0.5 | Interior vapor control, heating climates | Allows some drying |
| XPS foam (1.5 inch) | 0.6-0.8 | Continuous insulation | Provides both thermal and vapor control |
| Foil-faced polyisocyanurate | 0.05-0.1 | Roofing, continuous insulation | High R-value per inch |
| Vapor retarder paint (special) | 0.45-0.90 | Retrofit applications | Easy application |
Class III Vapor Retarders (>1.0 to ≤10 perm):
| Material | Permeance (perm) | Application | Benefits |
|---|---|---|---|
| Latex paint (2 coats) | 5-10 | Standard interior finish | Allows significant drying |
| Plywood (3/8 inch) | 0.5-1.5 | Structural sheathing | Structural and vapor control |
| OSB (7/16 inch) | 0.5-2.0 | Structural sheathing | Cost-effective |
| Closed-cell spray foam (2 inch) | 1.0-2.0 | Air and vapor control | Combined functions |
Performance Testing
Air Barrier Testing Methods
ASTM E2357 - Standard Test Method for Determining Air Leakage of Air Barrier Assemblies:
Test conditions:
- Pressure differential: 75 Pa (1.57 psf)
- Temperature: 24 ± 3°C (75 ± 5°F)
- Test specimen: Representative wall assembly
- Pass criterion: ≤0.20 L/(s·m²) at 75 Pa
ASTM E283 - Standard Test Method for Determining Rate of Air Leakage:
Used for testing windows, curtain walls, and other fenestration products:
- Test pressure: 75 Pa or 1.57 psf
- Results reported in L/(s·m²) or cfm/ft²
Field Testing - Blower Door:
Whole-building air leakage testing per ASTM E779:
ACH₅₀ = (Q₅₀ × 60) / V
Where:
- ACH₅₀ = Air changes per hour at 50 Pa
- Q₅₀ = Air flow rate at 50 Pa (m³/s)
- V = Building volume (m³)
Normalization for Climate:
ELA = Q₅₀ / (2√Δp)
Where:
- ELA = Equivalent leakage area (m²)
- Q₅₀ = Air flow rate at 50 Pa (m³/s)
- Δp = Pressure difference (50 Pa)
Target values from ASHRAE Standard 62.2:
- New construction: 3-5 ACH₅₀ (residential)
- Commercial buildings: <0.40 cfm/ft² at 75 Pa
Vapor Retarder Testing Methods
ASTM E96 - Standard Test Methods for Water Vapor Transmission:
Desiccant Method (Procedure A):
- Measures water vapor movement from high to low humidity
- Test conditions: 50% RH gradient
- Used for low permeance materials
Water Method (Procedure B):
- Measures water vapor movement from liquid water source
- Test conditions: 100% to 50% RH gradient
- Used for high permeance materials
Permeance Calculation:
M = (G / t) / (A × Δp_v)
Where:
- M = Permeance (kg/(Pa·s·m²))
- G = Mass of water vapor transmitted (kg)
- t = Time (s)
- A = Test area (m²)
- Δp_v = Vapor pressure difference (Pa)
ASTM C1512 - Standard Test Method for Characterizing the Moisture Vapor Permeance of Spray Applied Liquid Air Barriers:
Specific protocol for spray-applied products:
- Substrate: Concrete masonry unit (CMU) or gypsum board
- Minimum dry film thickness as specified by manufacturer
- Test per ASTM E96 after proper cure time
Climate-Specific Requirements
Vapor Retarder Placement by Climate Zone
IECC Climate Zone Requirements (Per IRC R702.7):
| Climate Zone | Description | Required Vapor Retarder Class | Placement |
|---|---|---|---|
| 1, 2, 3 | Hot-humid, Mixed | Not required, or Class III | Interior (if used) |
| 4 Marine | Marine | Not required, or Class III | Interior (if used) |
| 4 (except Marine) | Mixed-humid | Class III | Interior |
| 5 | Cold | Class II or III | Interior |
| 6, 7, 8 | Very cold/Subarctic | Class I, II, or III | Interior |
Exceptions and Special Cases:
Class I vapor retarders can be eliminated when one of the following is installed on the exterior side:
- Continuous insulation R-5 or greater (Zones 4C, Marine 4)
- Continuous insulation R-7.5 or greater (Zone 4 except Marine)
- Continuous insulation R-10 or greater (Zones 5, 6)
- Continuous insulation R-15 or greater (Zones 7, 8)
Air Barrier Requirements by Climate
Air barriers are required in all climate zones per ASHRAE 90.1 and IECC. Location options:
Exterior Air Barrier:
- Protects insulation from air washing
- Must be exterior to insulation or between insulation layers
- Common with cavity insulation + continuous insulation
Interior Air Barrier:
- Common in cold climates (reduces exfiltration)
- Often combined with vapor retarder function
- Must be continuous across structural framing
Mid-Wall Air Barrier:
- At structural sheathing plane
- Protected from weather
- Requires careful window/door integration
Design Strategies
Separate vs. Combined Systems
Separate Systems:
Advantages:
- Optimized performance for each function
- Allows independent material selection
- Better drying potential (air barrier can be vapor-permeable)
- Easier retrofit and repair
Typical assembly (cold climate):
- Interior: Painted gypsum board (Class III vapor retarder, 5-10 perm)
- Cavity: Fiberglass or mineral wool insulation
- Sheathing: OSB with sealed joints (air barrier, 0.5-2 perm)
- Exterior: Weather-resistive barrier
Combined Systems:
Advantages:
- Reduced complexity
- Fewer potential failure points
- Lower installed cost
- Simplified detailing
Materials that function as both air and vapor barrier:
- Self-adhered membranes (Class I vapor retarder + air barrier)
- Closed-cell spray foam (Class II vapor retarder + air barrier)
- Foil-faced rigid insulation (Class I vapor retarder + air barrier)
Design Considerations:
When combining air barrier and vapor retarder functions, verify:
- Material provides required air leakage resistance (<0.02 L/(s·m²) at 75 Pa)
- Material provides appropriate permeance for climate zone
- Continuity can be maintained at all transitions
- Assembly provides adequate drying potential
Continuity at Transitions
Foundation to Wall Transition:
Critical details:
- Sealant between sill plate and foundation
- Membrane transition from foundation waterproofing to wall air barrier
- Rim joist insulation and air sealing
- Penetration sealing (anchor bolts, utilities)
Wall to Roof Transition:
Methods:
- Extend wall air barrier to roof deck
- Transition membrane from wall to roof assembly
- Seal top plate penetrations
- Address thermal bridging at structural members
Window and Door Openings:
Integration requirements:
- Rough opening air sealing before unit installation
- Window/door unit sealed to air barrier system
- Use of compatible sealants and tapes
- Maintain continuity of air barrier plane
- Consider thermal expansion/contraction
Mechanical, Electrical, and Plumbing Penetrations:
Sealing strategies:
- Dedicated penetration sleeves with integrated sealing
- Expandable foam for grouped penetrations (non-shrinking formulation)
- Compression gaskets for through-wall penetrations
- Prefabricated boots for ductwork and piping
Common Design Errors
Error 1: Confusing Functions
Problem: Specifying polyethylene sheet as “air and vapor barrier” in cooling climates.
Issue: Polyethylene is a Class I vapor retarder (0.06 perm), which prevents inward drying during cooling season. If installed on interior of wall in mixed or cooling climate, summer moisture drive can trap moisture in wall assembly.
Solution: In cooling or mixed climates, use Class III vapor retarder (>1.0 perm) on interior to allow inward drying. Locate air barrier at sheathing plane with vapor-permeable air barrier material.
Error 2: Vapor Retarder on Both Sides
Problem: Installing vapor-impermeable materials on both interior and exterior of wall assembly.
Issue: Creates “vapor sandwich” with no drying potential. Any construction moisture or incidental water intrusion becomes trapped, leading to mold growth and material degradation.
Solution: Ensure one side of assembly allows drying. Typical approach: vapor-impermeable or semi-impermeable on climate-appropriate side, vapor-permeable on opposite side.
Error 3: Air Barrier Discontinuity
Problem: Air barrier transitions not detailed or executed at critical junctions.
Issue: Even small gaps dramatically reduce air barrier system performance. A 1% gap can reduce effectiveness by 30% or more.
Solution: Detail all transitions in construction documents. Common locations requiring attention:
- Window and door rough openings
- Foundation to wall connection
- Wall to roof connection
- Structural penetrations
- Service penetrations
Error 4: Inappropriate Climate Application
Problem: Using Class I vapor retarder in mixed or cooling climate based on heating climate prescriptive requirements.
Issue: Prevents inward drying during cooling season, trapping moisture from air conditioning condensation or summer moisture drive.
Solution: Reference IECC climate-specific requirements. In mixed climates (Zone 4 except Marine), maximum Class III interior vapor retarder recommended unless continuous exterior insulation is provided.
Installation Quality Control
Air Barrier Installation
Pre-Installation Verification:
- Substrate is clean, dry, and appropriate for selected material
- Ambient conditions meet manufacturer requirements
- Materials are stored per manufacturer specifications
- Installers are trained and experienced with system
During Installation:
- Continuous oversight of critical transitions
- Random adhesion testing of self-adhered membranes
- Wet film thickness measurement of fluid-applied products
- Joint and penetration sealing verification
- Photographic documentation of concealed elements
Post-Installation Testing:
- Localized blower door testing of individual floors or zones
- Infrared thermography during pressurization
- Smoke pencil testing at suspected leakage locations
- Whole-building blower door test
Performance Criteria:
Residential targets (ASHRAE 62.2):
- New construction: ≤5 ACH₅₀ (climate zones 1-2), ≤3 ACH₅₀ (climate zones 3-8)
- Energy-efficient construction: ≤1.5 ACH₅₀ (with ventilation system)
Commercial targets (ASHRAE 90.1):
- Maximum 0.40 cfm/ft² of envelope area at 75 Pa
- High-performance buildings: 0.25 cfm/ft² or less
Vapor Retarder Installation
Installation Requirements:
Class I vapor retarders:
- Continuous sheet installation
- Minimum 6-inch overlaps at seams
- Sealed penetrations with compatible tape or sealant
- Protection from mechanical damage during construction
Class II and III vapor retarders:
- Application per manufacturer instructions
- Proper surface preparation for coatings
- Sealed joints for kraft-faced products
- Fastener penetrations addressed per system requirements
Verification Methods:
- Visual inspection of all seams and penetrations
- Sample removal and laboratory testing of spray-applied products
- Wet film thickness measurement during application
- Documentation of ambient conditions during installation
Advanced Considerations
Hygrothermal Modeling
Computer simulation tools (WUFI, THERM, MOISTURE-EXPERT) allow analysis of:
- Coupled heat and moisture transport
- Transient conditions throughout annual cycle
- Material moisture content over time
- Condensation potential at interfaces
- Drying rates and directions
Key Simulation Parameters:
- Accurate material properties (permeability, sorption isotherms, thermal conductivity)
- Representative climate data (ASHRAE climate design conditions)
- Realistic interior conditions (temperature, relative humidity generation)
- Construction sequence and initial moisture content
Smart Vapor Retarders
Variable permeance materials adjust vapor permeability based on ambient relative humidity:
Performance Characteristics:
| Relative Humidity | Permeance (perm) | Classification |
|---|---|---|
| Low (<40% RH) | 0.5-1.0 | Class II |
| Medium (40-70% RH) | 3-5 | Class III |
| High (>70% RH) | 10-20 | Vapor open |
Applications:
- Mixed climates with seasonal moisture drive reversals
- Retrofit applications with unknown existing conditions
- High-performance enclosures requiring bidirectional drying
- Assemblies with moisture-sensitive materials
Mechanism: Nylon film expands at high humidity, increasing effective permeance by enlarging pore structure.
Airtight Drywall Approach (ADA)
Gypsum board interior finish serves as air barrier:
Requirements:
- Sealed top and bottom plates to framing
- Sealed electrical boxes (airtight-rated boxes or gaskets)
- Sealed drywall joints (compound and tape)
- Sealed penetrations (switches, outlets, fixtures)
- Sealed perimeter (gasket or sealant at base and ceiling)
Performance: Properly executed ADA can achieve:
- 0.6-1.2 ACH₅₀ in residential construction
- Equivalent to 0.02 L/(s·m²) at 75 Pa material requirement
Advantages:
- Uses standard construction materials
- Inspectable and testable
- Easy to repair
- Combines with interior vapor retarder function
Specification Guidance
Section 07 26 00 - Vapor Retarders
Part 1 - General:
- Reference standards: ASTM E96, ASTM C1512, IRC R702.7
- Climate zone designation
- Required vapor retarder class
- Submittals: product data, third-party test reports, installation instructions
Part 2 - Products:
- Material type and permeance classification
- Physical properties (thickness, tensile strength, UV resistance)
- Accessories (tapes, sealants, primers)
- Compatibility with adjacent materials
Part 3 - Execution:
- Surface preparation requirements
- Application method
- Lap and seam requirements
- Penetration sealing methods
- Protection during construction
- Quality control testing
Section 07 27 00 - Air Barriers
Part 1 - General:
- Reference standards: ASTM E2357, ASTM E283, ASTM E779
- Performance criteria: ≤0.20 L/(s·m²) at 75 Pa for assemblies
- Testing requirements: pre-construction mockup, field testing
- Installer qualifications
Part 2 - Products:
- Air barrier material type and air permeability
- Physical properties (tensile strength, elongation, water resistance)
- Accessories (transitions, terminations, primers, reinforcement)
- Compatibility with other envelope components
Part 3 - Execution:
- Substrate preparation and inspection
- Application method and coverage rates
- Continuity details at all transitions
- Penetration sealing methods
- Quality control inspections and testing
- Field air leakage testing protocol
References
ASHRAE Standards:
- ASHRAE Standard 90.1: Energy Standard for Buildings Except Low-Rise Residential Buildings
- ASHRAE Standard 62.2: Ventilation and Acceptable Indoor Air Quality in Residential Buildings
- ASHRAE Handbook - Fundamentals, Chapter 25: Heat, Air, and Moisture Control in Building Assemblies
ASTM Standards:
- ASTM E96: Standard Test Methods for Water Vapor Transmission of Materials
- ASTM E283: Standard Test Method for Determining Rate of Air Leakage Through Exterior Windows, Skylights, Curtain Walls, and Doors
- ASTM E779: Standard Test Method for Determining Air Leakage Rate by Fan Pressurization
- ASTM E2357: Standard Test Method for Determining Air Leakage of Air Barrier Assemblies
- ASTM C1512: Standard Test Method for Characterizing the Moisture Vapor Permeance of Spray Applied Liquid Air Barriers
Building Codes:
- International Energy Conservation Code (IECC)
- International Residential Code (IRC), Section R702.7
- International Building Code (IBC), Section 1405.3
Industry References:
- Air Barrier Association of America (ABAA): Air Barrier Specifications and Testing
- Building Science Corporation: Building Science Digests on Air Barriers and Vapor Control
- NIST Technical Note 1496: Review of Test Methods for Air Leakage