HVAC Systems Encyclopedia

A comprehensive encyclopedia of heating, ventilation, and air conditioning systems

Air Leakage Moisture Transport

Air leakage represents the dominant mechanism for moisture transport through building envelopes, typically moving 100 to 1,000 times more moisture than vapor diffusion alone. Understanding air leakage pathways, driving forces, and control strategies is critical for HVAC system design, humidity control, and prevention of moisture-related building failures.

Air Leakage vs. Vapor Diffusion

The relative importance of air leakage compared to vapor diffusion as a moisture transport mechanism:

Transport MechanismMoisture Transfer RateDriving ForceControl Strategy
Air leakage50-500 g/m²·day (typical)Pressure differentialAir barrier continuity
Vapor diffusion0.5-5 g/m²·day (typical)Vapor pressure gradientVapor retarder placement
Ratio (leakage/diffusion)100:1 to 1000:1Varies with conditionsAir barrier priority

Quantitative Comparison

For a typical wall assembly with a 1 mm crack per linear meter of wall:

Air leakage moisture transport:

  • Pressure differential: 4 Pa (0.016 in. w.c.)
  • Air velocity through crack: 2.5 m/s (492 fpm)
  • Airflow rate: 0.0025 m³/s per meter (5.3 cfm/ft)
  • Indoor conditions: 21°C (70°F), 40% RH, 7.4 g/kg moisture content
  • Outdoor conditions: -18°C (0°F), 60% RH, 0.6 g/kg moisture content
  • Moisture transport rate: 230 g/day per meter of crack

Vapor diffusion moisture transport:

  • Same wall assembly without air leakage
  • Same temperature and humidity conditions
  • Typical wall permeance: 50 ng/(Pa·s·m²)
  • Vapor pressure differential: 540 Pa
  • Moisture transport rate: 2.3 g/day per square meter

The air leakage through a 1 mm crack per meter of wall transports as much moisture as vapor diffusion through 100 m² of wall surface.

Driving Forces for Air Leakage

Three primary mechanisms create pressure differentials that drive air leakage through building envelope discontinuities:

Stack Effect

Stack effect pressure differential calculation:

ΔP_stack = C_s × h × ΔT

Where:

  • ΔP_stack = Stack pressure differential (Pa)
  • C_s = Stack coefficient = 0.0342 Pa/(m·K) at sea level
  • h = Height above neutral pressure plane (m)
  • ΔT = Indoor-outdoor temperature difference (K)

Example calculation for 20-story building:

  • Building height: 60 m (197 ft)
  • Indoor temperature: 21°C (70°F)
  • Outdoor temperature: -18°C (0°F)
  • ΔT = 39 K
  • Neutral pressure plane at mid-height: 30 m

Pressure at top of building: ΔP_top = 0.0342 × 30 × 39 = 40 Pa (0.16 in. w.c.) outward

Pressure at bottom of building: ΔP_bottom = -0.0342 × 30 × 39 = -40 Pa (0.16 in. w.c.) inward

Wind-Driven Infiltration

Wind pressure on building surfaces:

ΔP_wind = 0.5 × ρ × C_p × V²

Where:

  • ΔP_wind = Wind-induced pressure (Pa)
  • ρ = Air density (kg/m³), typically 1.2 kg/m³
  • C_p = Pressure coefficient (dimensionless), varies by surface orientation
  • V = Wind velocity (m/s)

Typical pressure coefficients:

Surface LocationC_p ValuePressure Character
Windward wall+0.6 to +0.8Positive (inward)
Leeward wall-0.3 to -0.5Negative (outward)
Side walls-0.6 to -0.7Negative (outward)
Roof center-0.7 to -0.9Negative (outward)
Roof corners/edges-1.2 to -2.0Strong negative (outward)

Example wind pressure calculation:

  • Wind velocity: 10 m/s (22 mph)
  • Windward wall: C_p = +0.7
  • ΔP_wind = 0.5 × 1.2 × 0.7 × 10² = 42 Pa (0.17 in. w.c.)

Mechanical System Pressurization

HVAC systems create building pressurization through imbalanced supply and exhaust airflows:

ΔP_mech = (Q_supply - Q_exhaust) / C_leak

Where:

  • ΔP_mech = Mechanical pressurization (Pa)
  • Q_supply = Total supply airflow (m³/s)
  • Q_exhaust = Total exhaust airflow (m³/s)
  • C_leak = Building leakage coefficient (m³/(s·Pa^n))

Typical intentional building pressurization targets:

Building TypePressurizationPurpose
Hospital patient rooms-2.5 Pa (-0.01 in. w.c.)Infection control
Hospital operating rooms+2.5 to +8 Pa (+0.01 to +0.03 in. w.c.)Contamination prevention
Laboratory chemical storage-12 to -25 Pa (-0.05 to -0.10 in. w.c.)Containment
Clean rooms (ISO 5-7)+5 to +15 Pa (+0.02 to +0.06 in. w.c.)Particle control
Commercial buildings+2.5 to +7.5 Pa (+0.01 to +0.03 in. w.c.)Infiltration control

Air Barrier Systems

An effective air barrier system requires continuity across all six surfaces of the building envelope with proper transitions at penetrations and intersections.

Air Barrier Continuity Requirements

Critical air barrier transition details:

  1. Wall-to-roof transitions

    • Continuous membrane or sealed joint
    • Accommodate differential movement
    • Typical gap before sealing: 6-25 mm (1/4 to 1 in.)
  2. Wall-to-foundation transitions

    • Below-grade waterproofing integration
    • Capillary break consideration
    • Thermal bridge mitigation
  3. Window and door perimeters

    • AAMA 711 sealant installation standards
    • Backer rod sizing: 1.25 × joint width
    • Sealant depth: 0.5 × joint width (minimum 6 mm)
  4. Mechanical, electrical, plumbing penetrations

    • Sleeve-to-air barrier sealing
    • Service core pressurization control
    • Expansion/contraction accommodation
  5. Building expansion joints

    • Flexible air barrier materials
    • Movement capacity: ±25% minimum
    • UV resistance for exposed locations

Air Barrier Material Performance Criteria

ASHRAE 90.1 air barrier assembly requirements:

Performance MetricMaximum ValueTest Standard
Air permeance0.02 L/(s·m²) at 75 PaASTM E2178
Air leakage (assemblies)0.20 L/(s·m²) at 75 PaASTM E2357, E1677, E283
Air leakage (whole building)2.0 L/(s·m²) at 75 PaASTM E779 (pressurization)

Conversion: 0.02 L/(s·m²) at 75 Pa = 0.004 cfm/ft² at 0.3 in. w.c.

Common air barrier material assemblies:

Assembly TypeAir PermeanceInstallation Considerations
Self-adhered membrane0.001-0.005 L/(s·m²)Temperature-dependent adhesion
Fluid-applied membrane0.002-0.008 L/(s·m²)Wet mil thickness critical
Mechanically fastened membrane0.005-0.015 L/(s·m²)Seam overlap and fastener sealing
Spray polyurethane foam (SPF)0.001-0.003 L/(s·m²)Minimum 25 mm (1 in.) thickness
Exterior gypsum sheathing + sealed joints0.01-0.02 L/(s·m²)Joint sealant longevity concern
CMU fully grouted + parged0.015-0.025 L/(s·m²)Block core verification required

Blower Door Testing

Blower door testing quantifies whole-building air leakage by measuring airflow required to maintain specific pressure differentials.

Test Procedure

Standard test protocol per ASTM E779:

  1. Building preparation:

    • Close all exterior doors and windows
    • Close all interior doors (single-zone test)
    • Close fireplace dampers
    • Disable HVAC systems or seal supply/return registers
    • Record indoor/outdoor temperature and barometric pressure
  2. Pressure testing sequence:

    • Establish baseline pressure (HVAC off)
    • Create pressure differentials: 10, 15, 20, 25, 30, 40, 50, 60, 75 Pa
    • Measure airflow at each pressure step
    • Perform both pressurization and depressurization tests
    • Average results to minimize wind effects
  3. Data analysis:

    • Plot airflow vs. pressure on log-log scale
    • Determine power law relationship: Q = C × ΔP^n
    • Calculate equivalent leakage area (ELA)
    • Normalize results to building envelope area

Air Changes Per Hour at 50 Pa (ACH50)

ACH50 = (Q_50 × 3600) / V_building

Where:

  • ACH50 = Air changes per hour at 50 Pa (h⁻¹)
  • Q_50 = Airflow rate at 50 Pa (m³/s)
  • V_building = Building volume (m³)
  • 3600 = Conversion factor (seconds per hour)

Typical ACH50 values by construction type:

Construction TypeACH50 RangeAir Leakage RateEnvelope Quality
Passive House0.3-0.60.05-0.10 cfm/ft² @ 50 PaExceptional
High-performance0.6-1.50.10-0.25 cfm/ft² @ 50 PaExcellent
Code-compliant new (2018+)1.5-3.00.25-0.50 cfm/ft² @ 50 PaGood
Standard new construction3.0-5.00.50-0.85 cfm/ft² @ 50 PaAverage
Existing buildings (pre-2000)5.0-15.00.85-2.50 cfm/ft² @ 50 PaPoor
Unrenovated historic15.0-30.0+2.50-5.00+ cfm/ft² @ 50 PaVery poor

Converting ACH50 to Natural Infiltration

Natural infiltration rate estimation from ACH50:

ACH_natural = ACH50 / N

Where N is the “LBL factor” or “N-factor”:

Climate/ShieldingN-FactorDescription
Tight, well-sealed house25-30Minimal stack effect, sheltered
Average construction18-22Moderate exposure
Leaky construction12-16High exposure, significant height
Very leaky, exposed8-12Multi-story, windy site

Example:

  • ACH50 = 3.0 (code-compliant construction)
  • N-factor = 20 (average conditions)
  • ACH_natural = 3.0 / 20 = 0.15 ACH (natural infiltration)

Moisture Load from Air Leakage

Calculating moisture load on HVAC systems from envelope air leakage:

m_moisture = ρ × Q_leak × Δω × 3600

Where:

  • m_moisture = Moisture load (kg/h)
  • ρ = Air density (kg/m³), typically 1.2 kg/m³
  • Q_leak = Leakage airflow rate (m³/s)
  • Δω = Humidity ratio difference (kg_water/kg_air)
  • 3600 = Conversion factor (seconds per hour)

Example moisture load calculation:

Building parameters:

  • Floor area: 5,000 m² (53,820 ft²)
  • Envelope area: 6,500 m² (69,965 ft²)
  • Volume: 15,000 m³ (529,720 ft³)
  • ACH50: 2.5 (good construction)
  • Estimated natural infiltration: 2.5 / 20 = 0.125 ACH

Winter conditions:

  • Indoor: 21°C, 40% RH, ω = 0.0062 kg/kg
  • Outdoor: -10°C, 70% RH, ω = 0.0013 kg/kg
  • Δω = 0.0049 kg/kg

Infiltration airflow: Q_leak = (0.125 × 15,000) / 3600 = 0.521 m³/s (1,103 cfm)

Moisture removal load: m_moisture = 1.2 × 0.521 × 0.0049 × 3600 = 11.0 kg/h (24.3 lb/h)

This moisture load must be added to internal moisture generation when sizing dehumidification capacity.

ASHRAE 90.1 Air Barrier Requirements

ASHRAE Standard 90.1 Energy Standard for Buildings establishes mandatory air barrier requirements for the building thermal envelope.

Continuous Air Barrier Requirement

Section 5.4.3.1 - Continuous Air Barrier:

Buildings in climate zones 4-8 (and marine climate zone 3) require a continuous air barrier for the building thermal envelope. The air barrier must be continuous across:

  • Building envelope assemblies (walls, roofs, floors)
  • Joints and assemblies
  • Penetrations of the building envelope
  • Transitions in materials, assemblies, and building elements

Performance Testing Requirements

Verification options (choose one):

  1. Materials approach: Use materials/assemblies tested per:

    • ASTM E2178 (materials): ≤0.02 L/(s·m²) at 75 Pa
    • ASTM E2357 (assemblies): ≤0.20 L/(s·m²) at 75 Pa
  2. Whole building approach: Test completed building per:

    • ASTM E779 or E1827: ≤2.0 L/(s·m²) at 75 Pa
    • Based on building envelope surface area

Climate Zone Requirements

Climate ZoneAir Barrier RequiredTypical Infiltration Target
1 (Very Hot)No (recommended)Not specified
2 (Hot)No (recommended)Not specified
3 (Warm)Marine only≤0.25 cfm/ft² @ 75 Pa
4 (Mixed)Yes≤0.25 cfm/ft² @ 75 Pa
5 (Cool)Yes≤0.20 cfm/ft² @ 75 Pa
6 (Cold)Yes≤0.20 cfm/ft² @ 75 Pa
7 (Very Cold)Yes≤0.15 cfm/ft² @ 75 Pa
8 (Subarctic)Yes≤0.15 cfm/ft² @ 75 Pa

Note: More stringent local codes may apply (e.g., IECC, California Title 24).

Common Air Leakage Pathways

Identifying and addressing typical leakage locations:

Leakage LocationTypical % of TotalMitigation Strategy
Window/door perimeters15-25%Continuous perimeter sealant, integrated flashing
Wall-to-roof intersection10-20%Sealed transition membrane, rigid blocking
Wall-to-foundation8-15%Sill gasket, spray foam, sealed membrane
Service penetrations (MEP)10-18%Sleeve sealing, penetration boots, fire-rated sealants
Electrical outlets/switches5-12%Air barrier gaskets, sealed boxes
HVAC duct penetrations8-15%Duct mastic at penetrations, sealed sleeves
Attic access hatches3-8%Weatherstripping, insulated covers
Recessed lighting5-10%IC-rated, airtight fixtures (ASTM E283)
Plumbing chases/soffits5-12%Chase sealing, compartmentalization
Building expansion joints3-8%Flexible air barrier assemblies

Sequential Air Sealing Priority

For maximum cost-effectiveness, address air leakage in this order:

  1. Large, accessible penetrations (duct/pipe penetrations)
  2. Wall-to-roof and wall-to-foundation transitions
  3. Window and door perimeters
  4. Service chases and plumbing penetrations
  5. Electrical penetrations
  6. Small distributed leaks (switches, outlets)

Impact on HVAC System Design

Air leakage significantly affects multiple HVAC design parameters:

Heating and Cooling Load Implications

Infiltration sensible load: Q_sensible = ρ × Q × c_p × ΔT / 1000

Where:

  • Q_sensible = Sensible heating/cooling load (kW)
  • ρ = Air density (1.2 kg/m³)
  • Q = Infiltration airflow rate (m³/s)
  • c_p = Specific heat of air (1.006 kJ/(kg·K))
  • ΔT = Temperature difference (K)

Infiltration latent load: Q_latent = ρ × Q × Δω × h_fg / 1000

Where:

  • Q_latent = Latent cooling load (kW)
  • Δω = Humidity ratio difference (kg/kg)
  • h_fg = Latent heat of vaporization (2,501 kJ/kg at 0°C)

Example load comparison (5,000 m² building):

Envelope TightnessACH_naturalInfiltration (m³/s)Winter Heating (kW)Summer Sensible (kW)Summer Latent (kW)
Passive House (0.4 ACH50)0.020.0833.11.80.9
Excellent (1.5 ACH50)0.0750.31311.66.93.4
Code minimum (3.0 ACH50)0.150.62523.113.86.8
Average existing (7.0 ACH50)0.351.45853.932.115.8

Assumptions: Winter ΔT = 35 K, Summer ΔT = 12 K, Summer Δω = 0.008 kg/kg

Humidity Control Challenges

High infiltration rates create humidity control difficulties:

Winter humidification requirements:

  • Tight building (0.15 ACH): 8-12 kg/h humidification capacity
  • Leaky building (0.35 ACH): 18-28 kg/h humidification capacity
  • Increased first cost and operating energy

Summer dehumidification challenges:

  • Latent load from infiltration can exceed internal gains
  • Requires proper equipment selection (low sensible heat ratio)
  • May necessitate dedicated dehumidification systems
  • Envelope improvement often more cost-effective than mechanical oversizing

Pressurization Control Strategies

For buildings requiring specific pressurization:

  1. Pressure-independent flow control: Use airflow measuring stations to maintain supply-exhaust differential regardless of envelope leakage

  2. Building pressure sensors: Direct pressure measurement with relief damper modulation for precision control (±1 Pa)

  3. Envelope tightening: Reduce C_leak to minimize airflow required for target pressurization, reducing energy consumption

  4. Vestibule design: Create pressure buffer zones at building entries to minimize pressure fluctuations during door operation

Reducing building air leakage from 5.0 ACH50 to 1.5 ACH50 can decrease pressurization airflow requirements by 60-70%, resulting in substantial fan energy savings and improved pressure control stability.

Sections

Dominance Over Diffusion

Quantitative analysis of air leakage moisture transport dominance over vapor diffusion in building envelopes, including transport mechanisms, comparative calculations, and design implications for moisture control

Air Barrier Systems

Comprehensive technical analysis of air barrier systems including continuity requirements, material properties, assembly design, testing protocols, and performance standards for controlling air leakage and moisture transport in building envelopes

Air Barrier Vs Vapor Retarder

Technical comparison of air barriers and vapor retarders including performance criteria, material specifications, permeance ratings, and integration strategies for building envelope moisture control