HVAC Systems Encyclopedia

A comprehensive encyclopedia of heating, ventilation, and air conditioning systems

Vented Attic Assemblies

Overview

Vented attic assemblies represent the most common roof-building assembly interface in residential and light commercial construction. This approach positions the thermal boundary at the attic floor (ceiling plane) rather than at the roof deck, creating an unconditioned buffer zone that relies on exterior ventilation to control temperature and moisture accumulation.

The fundamental premise of vented attic design: moisture generated within the conditioned space that migrates through the ceiling assembly into the attic space must be removed through continuous air exchange with exterior air before condensation occurs on cold surfaces.

Ventilation Physics and Airflow Mechanisms

Natural Ventilation Driving Forces

Vented attics rely primarily on natural ventilation driven by two physical phenomena:

Stack Effect (Thermal Buoyancy):

ΔP = Cₐ × ρₒ × g × H × (Tᵢ - Tₒ) / Tᵢ

Where:

  • ΔP = Pressure difference (Pa)
  • Cₐ = Flow coefficient (dimensionless, typically 0.65)
  • ρₒ = Outdoor air density (kg/m³)
  • g = Gravitational acceleration (9.81 m/s²)
  • H = Vertical distance between inlet and outlet (m)
  • Tᵢ = Attic air temperature (K)
  • Tₒ = Outdoor air temperature (K)

Wind-Induced Pressure:

ΔP = 0.5 × Cₚ × ρ × V²

Where:

  • Cₚ = Pressure coefficient (varies with location on roof, typically -0.6 to +0.8)
  • ρ = Air density (kg/m³)
  • V = Wind velocity (m/s)

Ventilation Airflow Rate

The actual airflow through attic vents depends on net free vent area and driving pressures:

Q = Cᵈ × A × √(2 × ΔP / ρ)

Where:

  • Q = Volumetric airflow rate (m³/s)
  • Cᵈ = Discharge coefficient (0.6-0.7 for typical vents)
  • A = Net free vent area (m²)
  • ΔP = Pressure difference across vent (Pa)
  • ρ = Air density (kg/m³)

Net Free Vent Area Requirements

Minimum Code Requirements

Standard Ratio (IRC R806.2, IBC 1203.2):

  • 1:150 ratio (net free ventilating area to attic floor area)
  • Example: 2,000 ft² attic requires 13.33 ft² net free vent area

Reduced Ratio (1:300): Permitted when ALL of the following conditions are met:

  • Vapor retarder (≤ 1.0 perm) installed on warm-in-winter side of ceiling insulation
  • At least 40% and not more than 50% of required ventilation provided in upper portion (near ridge)
  • Remaining 50% to 60% provided in lower portion (soffit/eave)

Net Free Area vs. Gross Vent Area

Net free area accounts for obstructions:

A_net = A_gross × (% open area)

Typical % Open Area by Vent Type:

Vent Type% Open AreaConversion Factor
Louvers with screen25-30%Multiply gross by 0.25-0.30
Continuous soffit strip (¼" × 1")9%Multiply gross by 0.09
Continuous soffit strip (⅜" × 1½")16%Multiply gross by 0.16
Slant-back ridge vent with baffle12-18%Multiply gross by 0.12-0.18
Roof louver vents40-60%Multiply gross by 0.40-0.60
Gable vents with screen60-70%Multiply gross by 0.60-0.70
Turbine vents50%Multiply gross by 0.50

Balanced Intake and Exhaust Strategy

Ventilation Distribution Principles

Effective attic ventilation requires balanced air pathway from intake to exhaust:

Intake Vents (50-60% of total net free area):

  • Located at soffit or eave
  • Continuous perforated soffit preferred over individual vents
  • Must not be blocked by insulation at eaves
  • Requires insulation baffles/chutes to maintain air channel

Exhaust Vents (40-50% of total net free area):

  • Located at or near ridge
  • Continuous ridge vent provides uniform extraction
  • Alternative: roof-mounted static vents, gable vents, or turbine vents
  • Higher placement increases stack effect driving force

Ventilation System Configurations

Configuration Effectiveness Ranking:

ConfigurationEffectivenessNotes
Continuous soffit + ridge ventExcellentMost uniform airflow pattern
Soffit + roof louvers (upper ⅓)GoodEnsure adequate spacing
Soffit + gable ventsFairCreates diagonal flow, potential dead zones
Gable vents onlyPoorLimited airflow, large dead zones
Roof louvers onlyPoorNo intake at eave, short-circuits

Common Ventilation Errors

Insufficient Intake Area:

  • Restricts total system airflow regardless of exhaust capacity
  • Creates negative pressure, can pull moisture from conditioned space
  • Results: Inadequate air exchange, persistent moisture accumulation

Mixed Exhaust Systems:

  • Combining ridge vents with gable vents or powered fans
  • Upper exhaust vents short-circuit airflow, drawing from other exhaust vents rather than soffit intake
  • Results: Dead zones in attic, reduced overall effectiveness

Thermal Boundary at Ceiling Plane

Insulation Requirements and Placement

The thermal boundary occurs at the attic floor (ceiling of conditioned space below). Insulation R-values must meet or exceed code minimums for climate zone.

IECC Climate Zone Requirements (2021):

Climate ZoneMinimum Ceiling R-Value
1, 2R-30
3R-30 to R-38
4 except MarineR-38
4 Marine, 5, 6R-49
7, 8R-49 to R-60

Insulation Installation Considerations

Depth Requirements:

For fiberglass batts (R-3.2 per inch):

  • R-30: 9.4 inches
  • R-38: 11.9 inches
  • R-49: 15.3 inches

For blown cellulose (R-3.6 per inch settled):

  • R-30: 8.3 inches
  • R-38: 10.6 inches
  • R-49: 13.6 inches

For blown fiberglass (R-2.5 per inch settled):

  • R-30: 12.0 inches
  • R-38: 15.2 inches
  • R-49: 19.6 inches

Critical Installation Details:

  1. Eave Protection: Install baffles/chutes to prevent insulation from blocking soffit vents. Maintain minimum 2-inch air channel from soffit to attic space.

  2. Uniform Coverage: Avoid gaps, compression, or voids. Insulation effectiveness degrades exponentially with coverage gaps.

  3. Penetration Sealing: Insulation does NOT stop air leakage. All penetrations must be air-sealed before insulation installation.

  4. Depth Markers: Install gauge markers at multiple locations to verify settled insulation depth during inspections.

Air Sealing the Ceiling Plane

Air sealing represents the most critical moisture control measure in vented attic assemblies. Air leakage transports 30-100 times more moisture into the attic than vapor diffusion alone.

Air Leakage vs. Vapor Diffusion

Moisture Transport Comparison:

Moisture flux by air leakage: M_air = ρₐᵢᵣ × ω × Q

Where:

  • M_air = Moisture transport rate (kg/s)
  • ρₐᵢᵣ = Air density (1.2 kg/m³)
  • ω = Humidity ratio (kg water/kg dry air)
  • Q = Air leakage rate (m³/s)

Moisture flux by vapor diffusion: M_diff = δₚ × A × Δpᵥ / d

Where:

  • M_diff = Moisture transport rate (kg/s)
  • δₚ = Vapor permeability of material (kg/Pa·s·m)
  • A = Surface area (m²)
  • Δpᵥ = Vapor pressure difference (Pa)
  • d = Material thickness (m)

For a 1 mm opening with 10 Pa pressure difference and typical winter conditions (20°C interior, 40% RH):

  • Air leakage transports approximately 0.4 g/hour of moisture
  • Diffusion through 100 ft² of 1-perm material transports approximately 0.006 g/hour

Ratio: Air leakage transports 60× more moisture than diffusion for this scenario.

Critical Air Sealing Locations

Top Priority Leakage Sites:

  1. Recessed Lighting Fixtures:

    • Use IC-rated, airtight (ICAT) fixtures
    • Seal non-IC fixtures with approved cover boxes
    • LED fixtures minimize heat, enable closer insulation contact
  2. Attic Access Openings:

    • Weatherstrip hatch perimeter with compression gasket
    • Insulate hatch to same R-value as ceiling
    • Spring-loaded latches to maintain compression
  3. Plumbing Penetrations:

    • Seal around pipes with fire-rated foam or caulk
    • Address both ceiling drywall and top plate penetrations
    • Larger openings: rigid material sealed with caulk/foam
  4. HVAC Penetrations:

    • Seal around ductwork boots at ceiling
    • Seal electrical supply to air handlers
    • Address combustion air supply (if applicable)
  5. Wall-to-Ceiling Intersections:

    • Top plates of interior partition walls
    • Often continuous open pathway to attic
    • Seal with caulk, foam, or blocking material
  6. Chimney/Flue Chases:

    • Fire-rated material required (sheet metal, fire caulk)
    • Maintain code clearances to combustibles
    • Sheet metal closure with high-temp caulk
  7. Dropped Soffits and Bulkheads:

    • Often built as open boxes to attic
    • Cap with rigid air barrier material
    • Seal all seams and penetrations
  8. Electrical Boxes:

    • Use foam gaskets behind cover plates
    • Seal wire penetrations into box with putty
    • Airtight-rated boxes preferred for new construction

Air Sealing Materials and Methods

ApplicationMaterial OptionsInstallation Notes
Small gaps (< ¼")Acrylic/latex caulk, elastomeric sealantClean surfaces, gun-grade preferred
Medium gaps (¼" - 3")Low-expansion polyurethane foamNon-expanding near electrical
Large openings (> 3")Rigid material + sealantPlywood, drywall, foam board sealed at edges
Wire/pipe penetrationsFire-rated caulk or foamVerify fire rating requirements
Around chimneysSheet metal + high-temp caulkMaintain 2" clearance minimum
Attic hatchCompression weatherstripAdhesive-backed foam with high compression

Attic Temperature Profiles

Summer Conditions

Well-ventilated attics typically reach temperatures 20-40°F above ambient outdoor conditions due to solar radiation absorbed by roofing:

T_attic ≈ T_outdoor + (I × α × R_roof) / h_conv

Where:

  • I = Solar irradiance (W/m²), peak ~800-1000 W/m²
  • α = Solar absorptance of roofing (0.05 for white to 0.95 for black)
  • R_roof = Thermal resistance of roof deck (minimal)
  • h_conv = Convective heat transfer coefficient (~10 W/m²·K for natural convection)

Typical Peak Attic Temperatures:

Roof SurfaceOutdoor Temp 95°FAttic Temp
White/reflective95°F110-115°F
Light colors95°F120-130°F
Medium colors95°F130-140°F
Dark colors/black95°F140-160°F

High attic temperatures increase cooling loads for the conditioned space below and accelerate shingle aging. Adequate ventilation (not exceeding code minimums) typically reduces attic temperature 10-15°F compared to unvented attics.

Winter Conditions

During heating season, attic temperature falls between indoor and outdoor temperatures, determined by:

  • Insulation R-value at ceiling
  • Air leakage from conditioned space
  • Solar gain through roof
  • Ventilation rate

T_attic = T_outdoor + (Q_leak × c_p × ρ × ΔT + Q_solar) / (h_conv × A_roof + m_vent × c_p)

Warmer attic temperatures increase risk of:

  • Condensation on cold roof sheathing
  • Ice dam formation at eaves
  • Premature snowmelt

Moisture Control and Condensation Prevention

Dew Point Analysis

Condensation occurs when surface temperature drops below the dew point temperature of the attic air. Dew point is determined by attic air temperature and relative humidity.

Dew Point Approximation (Magnus Formula):

T_dp = (b × α(T, RH)) / (a - α(T, RH))

Where: α(T, RH) = (a × T)/(b + T) + ln(RH/100) a = 17.27 b = 237.7°C T = Air temperature (°C) RH = Relative humidity (%)

Winter Condensation Risk

Condensation Potential Assessment:

  1. Calculate indoor air dew point (based on indoor T and RH)
  2. Determine likely roof sheathing temperature (near outdoor temperature)
  3. Assess moisture load entering attic (from air leakage)
  4. Evaluate ventilation adequacy to dilute moisture

Critical Factors:

  • Indoor humidity: Higher humidity increases moisture drive
  • Air leakage rate: More leakage transports more moisture
  • Ventilation effectiveness: Must dilute moisture faster than introduction
  • Sheathing temperature: Colder climates = higher condensation risk

Ventilation’s Role in Moisture Control

Ventilation dilutes moisture-laden air from interior with drier exterior air (winter) or prevents excessive accumulation (summer).

Required ventilation rate (simplified):

ACH = (M_gen × 3600) / (ρ × V × Δω)

Where:

  • ACH = Air changes per hour
  • M_gen = Moisture generation rate (kg/s)
  • ρ = Air density (kg/m³)
  • V = Attic volume (m³)
  • Δω = Humidity ratio difference between attic and outdoor air (kg/kg)

Typical residential attic ventilation provides 2-6 ACH under normal wind/temperature conditions, adequate for moderate moisture loads. However, significant air leakage from conditioned space can overwhelm ventilation capacity.

Key Principle: Air sealing always takes priority over ventilation. Ventilation cannot compensate for excessive air leakage.

Ice Dam Prevention

Ice dams form when heat loss through the ceiling melts snow on the roof surface. Meltwater runs down to the cold eave overhang where it refreezes, creating an ice barrier that backs up subsequent meltwater under shingles.

Ice Dam Formation Physics

Ice dam formation requires three conditions:

  1. Snow accumulation on roof
  2. Roof surface temperature above 32°F (melting occurs)
  3. Eave temperature below 32°F (refreezing occurs)

Heat flux through ceiling into attic: q = U × (T_indoor - T_attic)

Where:

  • q = Heat flux (W/m²)
  • U = Overall heat transfer coefficient = 1/R_total (W/m²·K)
  • T_indoor = Indoor temperature (K)
  • T_attic = Attic temperature (K)

This heat warms the roof sheathing from below, melting snow.

Ice Dam Prevention Strategies

Primary Defense - Thermal Boundary:

  • Maximize ceiling insulation (R-49 to R-60 in cold climates)
  • Eliminate thermal bypasses and air leakage
  • Maintain uniform insulation depth, especially at eaves

Secondary Defense - Ventilation:

  • Maintain code-minimum ventilation
  • Ensure intake at soffit not blocked by insulation
  • Cold attic air counteracts heat loss from below

Supplemental Measures:

  • Ice and water shield membrane at eaves (code requirement in many jurisdictions)
  • Extended 3-6 feet from eave edge
  • Metal drip edge properly integrated with membrane

Engineering Control (retrofit situations):

  • Heat cable at eaves (treats symptom, not cause)
  • Increased ventilation (limited effectiveness)
  • Mechanical ventilation/cooling of attic (energy penalty)

Ice Dam Risk Assessment

Low Risk:

  • R-49+ ceiling insulation, minimal air leakage
  • Well-ventilated attic with balanced intake/exhaust
  • Cold climate design practices followed

Moderate Risk:

  • R-30 to R-38 insulation
  • Some air leakage present
  • Limited eave protection

High Risk:

  • Cathedral ceiling or low-slope roof without adequate insulation
  • Significant air leakage into attic
  • Complex roof geometry with valleys
  • Insufficient ventilation at eaves

Design Considerations and Best Practices

Climate-Specific Recommendations

Cold Climates (Zones 6-8):

  • Maximum ceiling insulation (R-49 to R-60)
  • Aggressive air sealing (verified with blower door testing)
  • Balanced ventilation with continuous soffit and ridge vents
  • Interior vapor retarder (poly sheet or vapor-retarder paint)
  • Ice and water shield extended to 6 feet from eave

Mixed/Moderate Climates (Zones 3-5):

  • Code-minimum insulation (R-38 to R-49)
  • Comprehensive air sealing
  • Balanced ventilation
  • Vapor retarder optional (may be beneficial in Zone 5)

Hot-Humid Climates (Zones 1-2):

  • R-30 to R-38 insulation (cooling-dominated)
  • Air sealing prevents humid outdoor air infiltration
  • Radiant barriers on underside of roof deck can reduce cooling loads
  • NO interior vapor retarder (would trap inward vapor drive)

Radiant Barriers in Hot Climates

Radiant barriers (low-emittance surfaces) reduce radiant heat transfer from hot roof deck to attic floor:

q_radiant = σ × ε_eff × (T₁⁴ - T₂⁴)

Where:

  • σ = Stefan-Boltzmann constant (5.67 × 10⁻⁸ W/m²·K⁴)
  • ε_eff = Effective emittance (function of both surface emittances)
  • T₁, T₂ = Surface temperatures (K)

Effective emittance with radiant barrier: ε_eff = 1 / (1/ε₁ + 1/ε₂ - 1)

With aluminum radiant barrier (ε = 0.05) facing air gap:

  • Typical reduction: 40-50% of radiant component
  • Overall cooling load reduction: 5-10% (savings vary significantly)
  • Most effective in hot climates with high cooling loads

Installation Requirements:

  • Minimum ¾" air space facing low-e surface
  • Must be installed with low-e surface facing down (collects dust on top surface)
  • Proper ventilation still required

Equipment Located in Vented Attics

HVAC Equipment and Ductwork:

Placing HVAC equipment and ductwork in vented attics creates several problems:

  • Extreme temperature exposure (140°F+ summer, near-outdoor winter)
  • Duct leakage introduces/removes unconditioned air
  • Conductive/convective losses through duct walls
  • Reduced equipment efficiency at temperature extremes

Energy Penalty Quantification:

For supply duct in 130°F attic delivering 55°F air: q_loss = U × A × (T_attic - T_supply)

With R-6 insulated duct, 100 ft² surface area: q_loss = (1/6) × 100 × (130 - 55) = 1,250 BTU/hr

This represents direct sensible cooling load increase. Duct leakage penalties are typically much larger.

Best Practices When Equipment Must Be Located in Attic:

  1. Ductwork:

    • Minimum R-8 insulation (R-6 code minimum inadequate)
    • Seal all joints with mastic (not duct tape)
    • Verify duct leakage testing (< 4% total system leakage)
    • Minimize duct length and fittings
  2. Air Handlers:

    • Sealed combustion if gas-fired
    • Condensate drainage with traps and overflow protection
    • Vibration isolation to prevent noise transmission
    • Access platform for service
  3. Consider Alternatives:

    • Locate equipment within conditioned space
    • Create insulated, sealed closet within attic (unvented attic approach)
    • Bury ducts in attic insulation with additional insulation above

Attic Access Requirements

Code Requirements (IRC R807.1):

  • Minimum opening: 22 inches × 30 inches
  • Minimum headroom: 30 inches at access opening
  • Minimum clearance: 30 inches between framing and top of ceiling joists at access location
  • Attic access must be insulated and weatherstripped to same R-value as surrounding ceiling

Enhanced Access Details:

  • Rigid insulation adhered to back of hatch
  • Compression weatherstrip on all four sides
  • Latching mechanism to maintain compression
  • Pull-down attic stairs: insulated cover box above stairs when closed

Hybrid Approaches and Variations

Raised Heel Truss Design

Standard truss designs create minimal space for insulation at the eave, forcing compression of insulation or inadequate R-value at perimeter.

Raised Heel Truss Benefits:

  • Provides full insulation depth over exterior wall top plate
  • Eliminates thermal bridging at eave
  • Allows proper ventilation airflow from soffit without insulation obstruction
  • Increases effective R-value by 15-25% for ceiling assembly

Heel Height Calculation:

H_heel = d_insulation + d_baffle + d_clearance + d_framing

For R-49 blown insulation: H_heel = 14" + 2" + 2" + 1.5" = 19.5" minimum

Conditioned Attic (Unvented) Alternative

Modern building science increasingly favors unvented attic approaches (insulation at roof deck, no ventilation) for many applications. This moves the thermal and air control boundary to the roof deck rather than attic floor.

Advantages of Unvented Attic:

  • HVAC equipment and ductwork in semi-conditioned space
  • Eliminates ice dam risk (no heat loss to roof surface)
  • Simplifies air sealing (fewer penetrations through roof deck than ceiling)
  • Better moisture control in many climates

Requirements for Unvented Attic:

  • Air-impermeable insulation at roof deck (spray foam, rigid foam)
  • Vapor control integrated with insulation strategy
  • No ventilation openings
  • Code compliance (IRC Section R806.5, requires specific conditions)

This represents a fundamentally different assembly type, beyond the scope of vented attic design.

Verification and Commissioning

Installation Verification Checklist

Ventilation System:

  • Calculate required net free vent area for attic floor area
  • Verify intake vent net free area (50-60% of total)
  • Verify exhaust vent net free area (40-50% of total)
  • Confirm soffit vents not blocked by insulation
  • Verify insulation baffles installed at all soffit vent locations
  • Confirm no conflicting exhaust vent types (e.g., ridge + gable)

Air Sealing:

  • All penetrations sealed before insulation (visual inspection)
  • Recessed lights: IC-rated airtight or sealed covers
  • Attic access: weatherstripped and insulated
  • Plumbing and electrical penetrations sealed
  • Top plates of partition walls sealed
  • Chimney chase sealed with fire-rated materials
  • Blower door test confirms air sealing effectiveness (< 3 ACH50 target)

Insulation:

  • Verify R-value meets or exceeds code for climate zone
  • Confirm uniform coverage with no gaps or voids
  • Measure settled depth at multiple locations
  • Verify insulation does not block ventilation pathways
  • Confirm manufacturer installation instructions followed

Equipment (if present):

  • Ductwork sealed and insulated to specifications
  • Duct leakage testing completed and passed
  • Combustion air provided if required
  • Condensate drainage installed and tested
  • Equipment access maintained

Performance Testing

Blower Door Testing: Quantifies total building air leakage. Attic air sealing significantly impacts whole-building results.

Target: ACH50 < 3.0 for new construction (varies by climate and program requirements)

Infrared Thermography: Identifies thermal bypasses, insulation voids, and air leakage locations. Most effective with temperature difference across building envelope (≥ 10°C preferred).

Duct Leakage Testing: Quantifies duct system airtightness. Critical when ducts located in unconditioned attic.

Target: Total leakage < 4 CFM25 per 100 ft² conditioned floor area

Common Problems and Remediation

Problem: Condensation/Frost on Roof Sheathing

Symptoms:

  • Frost accumulation on underside of roof deck (winter)
  • Water staining on sheathing and framing
  • Mold growth on wood surfaces
  • Dripping when frost melts

Causes:

  • Excessive air leakage from conditioned space
  • Insufficient ventilation
  • Vapor-impermeable roof deck (can trap moisture)
  • Humidifier operating at excessive level

Solutions:

  1. Identify and seal major air leakage sites (thermal imaging helpful)
  2. Reduce indoor humidity if excessive (> 40% RH in cold climates)
  3. Verify adequate ventilation and clear airflow pathways
  4. In severe cases: increase ventilation, add vapor retarder at ceiling

Problem: Ice Dams

Symptoms:

  • Ice buildup at eaves
  • Icicles along eave
  • Water leakage into building at eave/soffit
  • Interior staining on exterior walls near ceiling

Causes:

  • Insufficient ceiling insulation
  • Air leakage warming attic
  • Blocked soffit ventilation
  • Complex roof geometry creating warm pockets

Solutions:

  1. Increase ceiling insulation to maximum practical level
  2. Comprehensive air sealing (prioritize)
  3. Ensure soffit ventilation clear and functional
  4. Install ice and water shield at eaves (if not present)
  5. Consider heat cable as temporary measure (does not address root cause)

Problem: Excessive Attic Temperature (Summer)

Symptoms:

  • Attic temperatures > 150°F
  • High cooling costs
  • Premature shingle failure
  • HVAC equipment overheating/short-cycling

Causes:

  • Dark roof absorbing solar radiation
  • Insufficient ventilation
  • Inadequate ceiling insulation
  • Ductwork/equipment in attic uninsulated

Solutions:

  1. Verify adequate ventilation per code (minimum 1:150)
  2. Ensure balanced intake/exhaust and clear airflow
  3. Increase ceiling insulation to reduce heat gain to space below
  4. Consider radiant barrier (hot climates)
  5. Consider light-colored/reflective roofing at replacement
  6. Relocate ductwork to conditioned space (if feasible)

Problem: Insulation Blocked Soffit Vents

Symptoms:

  • Visible insulation blocking soffit vent openings
  • Poor air circulation in attic
  • Moisture/temperature problems concentrated at eaves

Causes:

  • Insulation installed without baffles/chutes
  • Insufficient baffle length
  • Wind washing insulation into vent area

Solutions:

  1. Install proper ventilation baffles/chutes from soffit to attic space
  2. Pull back insulation from vent area
  3. Verify adequate baffle length (extend above insulation surface)
  4. Secure insulation to prevent wind displacement

References and Standards

International Residential Code (IRC):

  • Section R806: Roof Ventilation
  • Section R807: Attic Access
  • Section R402: Building Thermal Envelope

International Building Code (IBC):

  • Section 1203: Ventilation

ASHRAE Standards:

  • ASHRAE 90.1: Energy Standard for Buildings Except Low-Rise Residential
  • ASHRAE 62.1/62.2: Ventilation for Acceptable Indoor Air Quality

Building Science References:

  • Building Science Corporation: “Moisture Control in Buildings”
  • ASHRAE Handbook of Fundamentals: Chapter 27, Climatic Design Information
  • “Residential Energy: Cost Savings and Comfort for Existing Buildings” (Krigger & Dorsi)

Industry Resources:

  • Air Barrier Association of America (ABAA)
  • Insulation Contractors Association of America (ICAA)
  • National Roofing Contractors Association (NRCA)

Engineering Note: Vented attic assemblies represent proven, code-compliant construction for most residential and light commercial applications. Success requires three critical elements executed properly: adequate balanced ventilation, comprehensive air sealing at the ceiling plane, and sufficient insulation. Of these three, air sealing provides the greatest moisture control benefit and is most frequently inadequate in existing construction. When troubleshooting attic moisture or temperature problems, prioritize identification and remediation of air leakage before addressing ventilation or insulation deficiencies.