Destratification Fans
Destratification fans reduce thermal stratification in high-bay facilities by circulating warm ceiling air downward to occupied zones. The slow-speed, large-diameter fans create gentle vertical air movement that mixes temperature layers without creating uncomfortable drafts. Properly designed systems reduce heating energy consumption by 20-35% in spaces with ceiling heights exceeding 20 feet by recovering otherwise wasted heat accumulating at ceiling level.
Thermal Stratification Fundamentals
Heated air rises through buoyancy forces until reaching physical barriers (ceiling) or temperature equilibrium. The temperature gradient in high-bay spaces follows:
$$\frac{dT}{dh} = \frac{\Delta T_{total}}{h_{ceiling}}$$
where $\frac{dT}{dh}$ represents temperature change per foot of height. For a warehouse with:
- Floor temperature: 60°F
- Ceiling temperature: 85°F at 30 feet
- Total stratification: 25°F
Average temperature gradient:
$$\frac{dT}{dh} = \frac{25}{30} = 0.83°F\text{ per foot}$$
At the 6-foot occupied zone height:
$$T_{occupied} = 60 + (0.83 \times 6) = 65°F$$
Without destratification, maintaining 65°F at floor level requires ceiling temperatures approaching 90-100°F in severely stratified spaces. The heating system wastes energy conditioning air above the occupied zone that provides no comfort benefit.
Energy Savings Mechanisms
Destratification fans reduce heating loads through two mechanisms:
Stratification Reduction
Mixing warm ceiling air with cooler floor air elevates occupied zone temperature without additional heating input. The mixed temperature depends on fan effectiveness:
$$T_{mixed} = T_{floor} + \epsilon_{fan} \times (T_{ceiling} - T_{floor})$$
where $\epsilon_{fan}$ represents mixing effectiveness (typically 0.4-0.7 for well-designed systems). For the previous example with 60% effectiveness:
$$T_{mixed} = 60 + 0.60 \times (85 - 60) = 75°F$$
This 10°F increase (from 65°F to 75°F) in occupied zone temperature reduces heating demand:
$$\text{Heating reduction} = \frac{\Delta T_{improvement}}{\Delta T_{design}} = \frac{10}{65-(-10)} = 13%$$
Assuming -10°F outdoor design temperature and 65°F original floor temperature.
Reduced Envelope Losses
Lowering ceiling temperature reduces heat transfer through roofs and high walls. The envelope heat loss:
$$Q_{envelope} = U \times A \times (T_{inside} - T_{outside})$$
Reducing ceiling temperature from 85°F to 78°F (after destratification) cuts roof heat loss:
$$\text{Loss reduction} = \frac{(85-20) - (78-20)}{85-20} = \frac{7}{65} = 11%$$
Assuming 20°F outdoor temperature and well-insulated roof.
Combined savings from improved occupied zone comfort and reduced envelope losses typically reach 20-30% in facilities with ceiling heights of 24-35 feet.
Fan Operating Principles
Destratification fans employ large-diameter, slow-speed propellers creating high volumetric airflow at low velocities. The design prevents uncomfortable drafts while effectively mixing space air.
Airflow Characteristics
Fan diameter ranges from 4-24 feet for industrial applications. Rotational speeds operate at 20-100 RPM, producing tip speeds of 200-600 FPM. This contrasts sharply with comfort ceiling fans (200-300 RPM, 1000-2000 FPM tip speed) designed for occupant cooling rather than space mixing.
Volumetric flow rate approximation:
$$Q = K \times D^2 \times \text{RPM}$$
where $K$ depends on blade pitch and design (typically 0.1-0.2 for destratification fans). For a 20-foot diameter fan at 50 RPM:
$$Q = 0.15 \times 20^2 \times 50 = 3,000 \text{ CFM}$$
This represents the direct discharge from the fan. The induced flow from air entrainment multiplies total circulation by 3-5 times, resulting in 9,000-15,000 CFM total circulation per fan.
Circulation Pattern
Destratification fans operate in “reverse” mode during heating seasons, pulling air upward through the fan center and discharging radially outward along the ceiling. The air travels horizontally across the ceiling, descends along walls, returns across the floor, and rises back to the fan, creating a toroidal circulation pattern.
Coverage diameter depends on fan size and ceiling height:
$$D_{coverage} = K_c \times D_{fan} \times \left(\frac{h_{ceiling}}{10}\right)^{0.5}$$
where $K_c$ ranges from 8-12 depending on blade design. For a 10-foot fan at 30-foot ceiling height:
$$D_{coverage} = 10 \times 10 \times \left(\frac{30}{10}\right)^{0.5} = 173 \text{ feet}$$
This coverage diameter provides approximately 23,500 ft² coverage area per fan, suitable for a 150 × 150 foot warehouse zone.
Sizing Methodology
Proper sizing balances coverage area, mixing effectiveness, and energy efficiency:
Coverage-Based Sizing
Divide facility floor area by individual fan coverage to determine quantity:
$$N_{fans} = \frac{A_{floor}}{A_{coverage,fan}}$$
For a 300 × 400 foot warehouse (120,000 ft²) with fans covering 20,000 ft² each:
$$N_{fans} = \frac{120,000}{20,000} = 6 \text{ fans}$$
Layout fans in grid pattern with spacing equal to coverage diameter. Stagger rows to prevent dead zones between units.
Air Change Rate Method
Alternative sizing targets air change rates ensuring adequate mixing. Recommended rates for destratification:
- Light stratification (20-25 ft ceilings): 2-4 air changes per hour
- Moderate stratification (25-35 ft ceilings): 4-6 air changes per hour
- Severe stratification (35+ ft ceilings): 6-10 air changes per hour
Total required airflow:
$$\text{CFM}_{total} = \frac{\text{Volume} \times \text{ACH}}{60}$$
For the 300 × 400 × 30 ft warehouse targeting 5 ACH:
$$\text{CFM}_{total} = \frac{120,000 \times 30 \times 5}{60} = 300,000 \text{ CFM}$$
Number of fans if each delivers 10,000 CFM effective circulation:
$$N_{fans} = \frac{300,000}{10,000} = 30 \text{ fans}$$
This exceeds the coverage-based calculation, indicating coverage method may underestimate requirements for severely stratified spaces. Use the larger value for conservative design.
Motor Selection and Controls
Motor Power Requirements
Fan motor horsepower depends on airflow and blade efficiency:
$$\text{HP} = \frac{\text{CFM} \times \text{SP}}{6356 \times \eta}$$
Destratification fans operate at minimal static pressure (0.01-0.05 in. wg) with efficiencies of 30-50%. For 10,000 CFM at 0.02 in. wg and 40% efficiency:
$$\text{HP} = \frac{10,000 \times 0.02}{6356 \times 0.40} = 0.08 \text{ HP}$$
Manufacturers typically use fractional horsepower motors (1/10 to 1/2 HP) for fans up to 20 feet diameter. Larger fans require 1-3 HP motors.
Variable Speed Control
Variable-frequency drives modulate fan speed based on:
- Temperature differential: Increase speed when ceiling-floor temperature spread exceeds setpoint
- Outdoor temperature: Higher speeds during cold weather when stratification risk increases
- Occupancy schedule: Reduced speed or off during unoccupied periods
- Space temperature: Ramp speed if space temperature drops below setpoint
VFD cost ($200-600 per fan) pays back through reduced energy consumption (fans operate at lower speeds during mild weather, saving 30-50% of fan energy).
Seasonal Reversing
Summer operation reverses fan direction, pulling air downward through the center and discharging upward around the perimeter. This creates gentle downward air movement providing evaporative cooling without mechanical refrigeration.
Reversing switches or VFD direction control enables seasonal mode changes. Some systems automatically reverse based on outdoor temperature thresholds (heating mode below 65°F, cooling mode above 65°F).
Installation Considerations
Structural Support
Large destratification fans create substantial loads from:
- Equipment weight: 50-500 lbs depending on size
- Dynamic forces: Rotating mass and vibration
- Seismic loads: Lateral restraint per code requirements
Mounting to bar joists requires supplemental bracing. Attachment to structural steel beams provides adequate support for fans up to 14 feet diameter. Larger fans may require dedicated support structures engineered for specific installations.
Clearances
Maintain minimum clearances:
- Above fan: 2-3 feet to ceiling for airflow development
- Below fan: 10-12 feet to floor or highest obstruction (safety and airflow)
- Horizontal: Fan radius + 2 feet to walls, columns, or adjacent fans
Inadequate clearances reduce effectiveness and create noise from turbulence.
Electrical
Each fan requires:
- Power supply: 120VAC or 277VAC depending on motor
- Circuit protection: 15-20A breaker for fractional HP motors
- Control wiring: 24VAC or 0-10VDC for VFD speed control
- Disconnect: Within sight of fan for service safety
Multiple fans connect to centralized control panels coordinating operation across zones.
Energy Savings Analysis
Calculate annual savings from reduced heating load:
Baseline heating energy (no destratification):
$$E_{baseline} = \frac{Q_{design} \times \text{HDD} \times 24}{\Delta T_{design} \times \eta}$$
For a facility with 800 MBH design load, 6,000 HDD climate, 75°F indoor / -10°F outdoor design, and 85% heating efficiency:
$$E_{baseline} = \frac{800,000 \times 6000 \times 24}{85 \times 0.85} = 1,601 \text{ MMBtu/year}$$
With 25% heating reduction from destratification:
$$E_{savings} = 1,601 \times 0.25 = 400 \text{ MMBtu/year}$$
At $10 per MMBtu gas cost:
$$\text{Annual savings} = 400 \times 10 = $4,000$$
Fan operating cost (6 fans at 0.25 HP each, operating 4,000 hrs/year at $0.10/kWh):
$$\text{Fan cost} = 6 \times 0.25 \times 0.746 \times 4000 \times 0.10 = $447\text{/year}$$
Net savings:
$$\text{Net savings} = 4,000 - 447 = $3,553\text{/year}$$
For installed cost of $12,000 (6 fans at $2,000 each), simple payback:
$$\text{Payback} = \frac{12,000}{3,553} = 3.4 \text{ years}$$
This favorable payback drives adoption in facilities with high heating costs, cold climates, and ceiling heights exceeding 24 feet.
Performance Optimization
Maximize destratification effectiveness through:
- Thermostat placement: Mount at occupied zone height (4-6 feet), not at ceiling
- Staging: Operate fans continuously during heating season, not cycling with heating equipment
- Speed modulation: Vary speed based on stratification level (ceiling-floor temperature differential)
- Distribution coordination: Ensure heated air discharge patterns complement fan circulation
- Envelope improvements: Seal roof and wall penetrations reducing infiltration that disrupts circulation patterns
Regular commissioning verifies performance through temperature mapping at multiple heights across the facility, confirming reduced stratification and occupied zone comfort improvements.
Destratification fans provide cost-effective heating energy reduction in high-bay facilities through passive circulation eliminating temperature stratification. The combination of favorable economics, simple installation, and minimal maintenance makes these systems attractive retrofits for warehouses, manufacturing plants, and other facilities with substantial ceiling heights and heating loads.