Non-Metal Ducts: Materials, Applications & Standards
Overview
Non-metal ducts provide alternatives to traditional galvanized steel ductwork, offering advantages in specific applications including thermal performance, weight reduction, acoustical control, and installation flexibility. These systems encompass fiberglass duct board, fabric air dispersion systems, fiber-reinforced plastic (FRP), flexible ducts, and specialized polymer materials.
Selection criteria depend on application requirements including temperature range, pressure class, environmental conditions, acoustical performance, and installation constraints.
Non-Metal Duct Types
graph TD
A[Non-Metal Ducts] --> B[Fiberglass Duct Board]
A --> C[Fabric Ducts]
A --> D[Fiber-Reinforced Plastic]
A --> E[Flexible Ducts]
A --> F[PVC/CPVC Ducts]
B --> B1[Rigid Board Systems]
B --> B2[Thermal/Acoustical Insulation]
C --> C1[Textile Air Dispersion]
C --> C2[Temporary Applications]
D --> D1[Corrosive Environments]
D --> D2[Chemical Exhaust]
E --> E1[Insulated Flex Duct]
E --> E2[Non-Insulated Flex]
F --> F1[Laboratory Exhaust]
F --> F2[Chemical Fume Systems]
Material Properties Comparison
Performance Characteristics
| Material | Max Temp (°F) | Pressure Class | Thermal R-Value | Weight (lb/ft²) | Fire Rating |
|---|---|---|---|---|---|
| Fiberglass Board 1.5" | 250 | 2" w.g. | 6.0 | 0.38 | Class 1 |
| Fabric (Polyester) | 160 | 4" w.g. | N/A (uninsulated) | 0.15 | NFPA 701 |
| FRP (Polyester) | 200 | 10" w.g. | Varies | 1.2 | Class 1 |
| Flexible (Insulated) | 250 | 1" w.g. | 4.2-8.0 | 0.60 | UL 181 Class 1 |
| PVC Schedule 40 | 140 | 15" w.g. | None | 2.1 | Limited |
Application Matrix
| Material | Supply Air | Return Air | Exhaust | High Humidity | Corrosive |
|---|---|---|---|---|---|
| Fiberglass Board | Excellent | Excellent | Limited | Fair | Poor |
| Fabric Ducts | Excellent | Fair | No | Good | Fair |
| FRP | Good | Good | Excellent | Excellent | Excellent |
| Flexible Ducts | Good | Fair | Limited | Good | Fair |
| PVC/CPVC | Poor | Poor | Excellent | Excellent | Excellent |
Fiberglass Duct Board Systems
Fiberglass duct board consists of rigid, resin-bonded glass fibers with a reinforced foil-scrim-kraft (FSK) or aluminum foil vapor barrier facing. The material functions as both duct structure and thermal insulation.
Key Properties:
- Density: 3-6 lb/ft³ depending on pressure class
- Thermal conductivity: 0.23-0.26 BTU·in/(hr·ft²·°F)
- Acoustical absorption: NRC 0.70-0.90
- Compressive strength: 5-15 psi minimum
Fabrication Requirements (SMACNA HVAC Duct Construction Standards):
- V-groove cutting depth: leave 1/4" minimum material thickness
- Closure methods: staples and pressure-sensitive tape for low pressure; mechanical fasteners for 2" w.g.
- Maximum aspect ratio: 4:1 for rectangular ducts
- Support spacing: 10 ft maximum for horizontal runs
Advantages:
- Integral thermal insulation (eliminates external wrap)
- Superior acoustical attenuation (reduces fan noise transmission)
- Lightweight (reduces structural loading)
- No condensation on exterior surfaces in cooling applications
Limitations:
- Cannot be used outdoors or in high-humidity spaces without protection
- Not suitable for exhaust systems with potential chemical exposure
- Requires careful handling during installation
- Maximum velocity: 2,500 fpm for supply air
Standards Compliance:
- UL 181: Factory-made air ducts and connectors
- ASTM C1338: Standard test method for pressure rating of duct board
- NFPA 90A: Standard for installation of air-conditioning and ventilating systems
Fabric Duct Systems
Fabric ducts, also called textile air dispersion systems, distribute conditioned air through engineered porous or perforated fabric materials. The fabric acts as both duct and air diffuser.
Material Options:
- Polyester (most common): washable, durable, wide temperature range
- Nylon: higher strength, chemical resistance
- Polypropylene: moisture resistance, lower cost
Dispersion Methods:
- Porous fabric: air diffuses through material weave (low velocity)
- Laser-cut orifices: directional airflow patterns
- Combination systems: mix of porous and orifice dispersion
Design Considerations:
- Static pressure at fabric: 0.08-0.20" w.g. typical
- Supply air velocity in fabric: 400-2,500 fpm
- Throw distance: 3-20 ft depending on orifice design
- Support cable sizing: per manufacturer specifications
Advantages:
- Uniform air distribution over entire duct length
- Eliminates traditional diffusers and registers
- Washable and cleanable (critical for food processing)
- Lightweight and aesthetic appearance
- Rapid installation
Typical Applications:
- Food processing and preparation facilities
- Sports arenas and gymnasiums
- Temporary cooling for events
- Clean rooms (special antistatic materials)
- Warehouses and distribution centers
Standards:
- NFPA 701: Standard methods of fire tests for flame propagation
- ASHRAE 70: Method of testing diffusion effectiveness
- Factory Mutual approval for specific applications
Fiber-Reinforced Plastic (FRP) Ducts
FRP ductwork consists of fiberglass reinforcement embedded in thermosetting resin (polyester, vinyl ester, or epoxy). These systems excel in corrosive environments where metal ducts fail rapidly.
Resin Selection:
- Polyester: general chemical resistance, lowest cost
- Vinyl ester: superior corrosion resistance, higher temperature
- Epoxy: maximum chemical resistance, highest cost
Construction Methods:
- Hand lay-up: custom shapes, field fabrication possible
- Filament winding: cylindrical ducts, high strength
- Pultrusion: constant cross-section profiles
Mechanical Properties:
- Tensile strength: 10,000-25,000 psi
- Flexural strength: 15,000-40,000 psi
- Maximum continuous temperature: 180-250°F depending on resin
Applications:
- Chemical process exhaust systems
- Laboratory fume hood exhaust
- Plating and metal finishing operations
- Wastewater treatment facilities
- Marine environments
Installation Requirements:
- Support spacing: calculate based on span loading (typically 8-10 ft)
- Joining methods: flanged connections with gasketing, adhesive bonds
- Expansion compensation: 0.5-1.0 in per 100 ft per 100°F temperature change
- Grounding: non-conductive; requires bonding jumpers for static dissipation
Standards:
- SMACNA FRP Duct Construction Manual
- ASTM D2996: Standard specification for filament-wound fiberglass pipe
- Factory Mutual 4910: Approval standard for ducts
Installation Best Practices
Fiberglass Duct Board:
- Store flat in dry location, off ground
- Cut using sharp knives; seal all joints with UL 181-rated tapes
- Install hangers at 10 ft spacing maximum
- Protect exposed ends during construction
Fabric Ducts:
- Install support cables with proper tensioning (per manufacturer)
- Ensure minimum clearance to combustibles (36" typical)
- Provide access for periodic removal and cleaning
- Verify air balance matches design dispersion pattern
FRP Systems:
- Follow manufacturer torque specifications for flange bolts
- Use compatible gasket materials (EPDM, Viton, PTFE)
- Provide adequate structural support (FRP has lower stiffness than metal)
- Ground system if handling flammable vapors
Selection Criteria
Choose non-metal ductwork when:
- Fiberglass Board: Low-pressure HVAC systems requiring thermal and acoustical performance
- Fabric Ducts: Uniform air distribution required over large spaces or cleanability is critical
- FRP: Corrosive chemical exposure makes metal ducts unsuitable
- Flexible Ducts: Short connection runs from rigid ductwork to terminals
- PVC/CPVC: Chemical exhaust at moderate temperatures with acid/alkali exposure
Consider metal ductwork when higher pressures, temperatures above material limits, outdoor exposure, or structural rigidity requirements exist.
Sections
Fiberglass Duct Board
Components
- Rigid Fiberglass Duct Board
- Thermal Insulation R Value
- Acoustical Properties Fiberglass
- Facing Reinforcement Foil Scrim
- Maximum Velocity 2500 To 4000 Fpm
- Maximum Pressure 2 To 4 Iwc
- Rectangular Construction Only
- Closure Systems Staples Tape
- Outward Clinch Stapling
Flexible Duct
Components
- Insulated Flexible Duct
- Non Insulated Flexible Duct
- Inner Core Wire Helix
- Polymer Film Vapor Barrier
- Fiberglass Insulation R42 R60 R80
- Outer Jacket Protection
- Maximum Length Limitations
- Support Spacing Requirements
- Stretched Tight Installation
- Avoid Compression Kinking
- Maximum Pressure 1 To 2 Iwc
Fabric Ducts
Components
- Porous Textile Ducts
- Non Porous Textile Ducts
- Permeable Fabric Air Dispersion
- Orifice Pattern Diffusion
- Modular Sections Zipper
- Cleanable Washable Fabric
- Antimicrobial Treatment
- Custom Engineered Perforations