HVAC Systems Encyclopedia

A comprehensive encyclopedia of heating, ventilation, and air conditioning systems

Air Terminals: Diffusers, Grilles & Registers

Air Terminals: Diffusers, Grilles & Registers

Air terminals are the final components in an air distribution system, delivering conditioned air from ductwork into occupied spaces. Proper terminal selection directly impacts occupant comfort, energy efficiency, and acoustic performance. This guide covers terminal types, selection methodology, and the physics governing air jet behavior.

Terminal Unit Classification

Air terminals fall into four primary categories based on function and airflow control:

graph TB
    A[Air Terminals] --> B[Diffusers]
    A --> C[Grilles]
    A --> D[Registers]
    A --> E[VAV Terminals]

    B --> B1[Ceiling: Slot, Round, Square]
    B --> B2[Linear: Perimeter, High-Side Wall]
    B --> B3[Displacement: Low-Velocity Floor]

    C --> C1[Supply: Fixed Deflection]
    C --> C2[Return/Exhaust: No Deflection]

    D --> D1[Supply with Damper Control]
    D --> D2[Adjustable Deflection Vanes]

    E --> E1[Pressure Independent]
    E --> E2[Pressure Dependent]
    E --> E3[Fan-Powered: Series/Parallel]

    style A fill:#2c3e50,stroke:#ecf0f1,stroke-width:3px,color:#ecf0f1
    style B fill:#3498db,stroke:#ecf0f1,stroke-width:2px,color:#ecf0f1
    style C fill:#3498db,stroke:#ecf0f1,stroke-width:2px,color:#ecf0f1
    style D fill:#3498db,stroke:#ecf0f1,stroke-width:2px,color:#ecf0f1
    style E fill:#e74c3c,stroke:#ecf0f1,stroke-width:2px,color:#ecf0f1

Throw and Drop Physics

Air jet throw represents the horizontal distance air travels from the terminal to a point where velocity decreases to a specified terminal velocity (typically 50 fpm for cooling, 100 fpm for heating). Drop quantifies the vertical deflection caused by buoyancy and gravitational effects.

Throw Calculation

Throw distance follows empirical relationships derived from Albertson’s jet equation for turbulent free jets:

T₅₀ = K × √(Q / V₀)

Where:

  • T₅₀ = throw to 50 fpm terminal velocity (ft)
  • K = throw coefficient (dimensionless, manufacturer-specific)
  • Q = airflow rate (cfm)
  • V₀ = initial outlet velocity (fpm)

For rectangular diffusers, the relationship simplifies to:

T₅₀ = K × (Q / L)

Where L = active length (ft) of the diffuser.

Drop Calculation

Drop results from density differences between supply air and room air. For isothermal jets, drop is negligible. For non-isothermal conditions:

D = 0.00027 × ΔT × T₅₀

Where:

  • D = drop distance (ft)
  • ΔT = temperature difference, supply minus room (°F)
  • T₅₀ = throw distance (ft)

Critical consideration: Cooling jets drop due to negative buoyancy (ρ_supply > ρ_room). Heating jets rise. Maximum acceptable drop is 2-3 ft for ceiling diffusers to prevent drafts in the occupied zone.

Diffuser Selection Criteria

Selection requires balancing airflow delivery, acoustic performance, and architectural constraints. Reference ASHRAE Standard 70 (Method of Testing for Rating the Performance of Air Outlets and Inlets) for performance data standardization.

ParameterCeiling DiffusersLinear SlotDisplacementHigh Sidewall
Typical Throw (ft)8-2010-303-615-40
Supply Velocity (fpm)400-800500-100050-100600-1200
NC Level @ 10 ft25-3530-40<2035-45
Throw/Drop Ratio4:1 typical6:1 typicalN/A10:1 typical
ApplicationGeneral officePerimeter zonesLabs, clean roomsGymnasiums, lobbies
Spread Pattern2-4 wayLinear360° radial1-way horizontal

Acoustic Performance

Sound generation at terminals stems from turbulence at vanes and pressure drop across the device. ADC (Air Diffusion Council) standards provide NC (Noise Criteria) ratings:

NC ≈ 10 × log₁₀(Δp) + C

Where Δp = pressure drop (in. w.g.) and C = constant based on terminal geometry.

Design target: NC 25-35 for offices, NC 30-40 for retail, NC 20-25 for conference rooms.

VAV Terminal Units

VAV terminals modulate airflow while maintaining space temperature setpoints. Two fundamental types exist:

Pressure Independent (PI) vs. Pressure Dependent (PD)

FeaturePressure IndependentPressure Dependent
Flow ControlIntegral flow sensor + controllerDamper position only
Duct Pressure SensitivityCompensates for pressure variationFlow varies with pressure
Cost30-50% higherBase cost
ApplicationSystems >10 terminalsSmall systems, budget constraints
Accuracy±10% of setpoint±20-30% of setpoint

Fan-Powered VAV Terminals

Fan-powered units blend primary (cooled) air with plenum air, maintaining constant volume delivery during low-load conditions:

Series Fan: Fan operates continuously, mixing primary and induced air before discharge.

Parallel Fan: Fan operates only when primary airflow drops below minimum, operating in parallel with primary air.

Heating capacity (series):

Q_heat = 1.08 × (CFM_total) × (T_discharge - T_primary)

Where CFM_total includes both primary and induced airflow.

Selection Methodology

  1. Determine zone load: Calculate sensible cooling load (Btu/hr).
  2. Calculate required airflow: CFM = Q_sensible / (1.08 × ΔT).
  3. Establish throw requirement: T₅₀ = 0.75 × (room length or width, whichever is critical).
  4. Select terminal type: Based on architectural constraints and application.
  5. Verify performance: Check manufacturer data for throw at calculated CFM.
  6. Confirm pressure drop: Ensure Δp < system available static pressure, typically 0.05-0.15 in. w.g.
  7. Validate acoustics: Verify NC rating meets space requirements.

Standards and References

  • ASHRAE Standard 70: Method of Testing for Rating the Performance of Air Outlets and Inlets
  • ASHRAE Fundamentals Handbook: Chapter 20, Space Air Diffusion
  • ADC (Air Diffusion Council): Diffuser performance testing standards
  • SMACNA: HVAC Systems Duct Design, Section 6, Terminal Devices

Installation Considerations

Ceiling diffusers: Install minimum 6 in. from walls to prevent staining. Maintain 4× neck diameter upstream straight duct length.

Linear diffusers: Align slots perpendicular to window wall for perimeter heating. Seal plenum boxes to prevent bypass leakage.

Displacement terminals: Locate in occupied zone (floor or low wall). Requires stratified temperature profile; not suitable for spaces <9 ft ceiling height.

VAV terminals: Mount with service clearance for damper and controller access. Install minimum 3× diameter upstream straight duct for accurate flow measurement.

Proper terminal selection and installation ensures effective air distribution, minimizes energy consumption, and maintains occupant comfort throughout the conditioned space.

Sections

Supply Outlets & Diffuser Selection

Comprehensive guide to HVAC supply outlets including ceiling, sidewall, floor, and slot diffusers with throw calculations, performance ratings, and selection criteria.

Return Air Inlets

Return air grilles, filter grilles, door grilles, and transfer grilles for HVAC systems including low pressure drop design considerations and sizing criteria.

Performance Parameters

Components

  • Throw Definition
  • Throw Distance To Terminal Velocity
  • Drop Definition Vertical Displacement
  • Spread Definition Horizontal Coverage
  • Terminal Velocity 50 Fpm Typical
  • Terminal Velocity 100 Fpm Industrial
  • Terminal Velocity 150 Fpm High Throw
  • Nc Noise Criteria Diffuser
  • Nc 25 30 35 40 Ratings
  • Pressure Drop Terminal Device
  • Effective Area Calculation
  • Neck Velocity Limitations
  • Face Velocity Limitations
  • Aspiration Ratio
  • Entrainment Ratio
  • Coanda Effect Ceiling Attachment
  • Isothermal Throw
  • Non Isothermal Throw
  • Cooling Mode Drop
  • Heating Mode Rise

Diffuser Selection Methodology

Components

  • Room Load Cfm Calculation
  • Supply Air Temperature Differential
  • Air Change Rate Verification
  • Throw To Room Dimension Ratio
  • Throw Distance Criteria
  • Characteristic Length Room
  • Adpi Air Diffusion Performance Index
  • Effective Draft Temperature Edt
  • Local Air Velocity Comfort
  • Diffuser Spacing Guidelines
  • Maximum Spacing Limits
  • Manufacturer Performance Data
  • Application Selection Charts
  • Correction Factors Temperature
  • Correction Factors Mounting

Specialty Diffusers

Components

  • Displacement Ventilation Diffusers Low Velocity
  • Underfloor Air Distribution Outlets Swirl
  • Ufad Floor Diffusers
  • Ufad Floor Grilles
  • Variable Air Volume Diffusers
  • Pattern Controllers Directional
  • High Aspiration Diffusers
  • Low Aspiration Diffusers
  • Architectural Linear Slot Diffusers
  • Continuous Slot Diffusers
  • Perforated Panel Systems
  • Plenum Diffusers
  • Sound Attenuating Diffusers
  • Light Fixture Integrated Diffusers
  • Active Chilled Beam Diffusers