Ductwork Design and Sizing for HVAC Systems
Introduction
Duct design represents the systematic application of fluid mechanics principles to air distribution systems. The objective is to deliver specified airflow rates to each terminal device while minimizing energy consumption, construction cost, and acoustic emissions. This requires balancing competing constraints: smaller ducts reduce material cost but increase pressure loss and fan energy; larger ducts reduce friction but consume building space and increase initial cost.
The design process involves three fundamental steps: selecting a sizing method, calculating pressure losses through all system components, and verifying that velocities remain within acceptable limits for noise control. Modern duct design integrates thermodynamics (heat transfer through duct walls), fluid mechanics (pressure loss and flow distribution), and acoustics (noise generation and attenuation).
Fundamental Flow Equations
Air distribution systems operate in the turbulent flow regime (Reynolds number > 4000) under standard conditions. The governing equations derive from conservation principles and empirical correlations for friction factors.
Continuity Equation
Mass conservation requires:
For constant density (incompressible flow assumption valid for duct systems):
where:
- $Q$ = volumetric flow rate (cfm or m³/s)
- $A$ = cross-sectional area (ft² or m²)
- $V$ = average velocity (fpm or m/s)
- $\rho$ = air density (lb/ft³ or kg/m³)
- $\dot{m}$ = mass flow rate (lb/s or kg/s)
Bernoulli Equation with Losses
Energy conservation along a streamline, accounting for friction and minor losses:
For horizontal ducts with negligible elevation change, expressed in pressure units:
where:
- $P_s$ = static pressure (in. wg or Pa)
- $P_v = \rho V^2/2$ = velocity pressure (in. wg or Pa)
- $\Delta P_L$ = total pressure loss (in. wg or Pa)
Velocity Pressure
The dynamic pressure component resulting from fluid motion:
For standard air at 70°F and sea level ($\rho$ = 0.075 lb/ft³):
where $V$ is in fpm.
In SI units (air at 20°C, 101.325 kPa, $\rho$ = 1.204 kg/m³):
where $V$ is in m/s.
Duct Sizing Methods
Three primary methods exist for sizing duct systems, each with distinct advantages and applications.
Equal Friction Method
The equal friction method maintains constant pressure loss per unit length throughout the system. This approach provides balanced design with predictable pressure losses and simplifies manual calculations.
Design Procedure:
- Select friction rate based on system type and noise constraints
- Size main trunk at selected friction rate
- Size all branches at the same friction rate
- Calculate dynamic losses for all fittings
- Balance system using dampers or resize sections
Friction Rate Selection:
Typical friction rates for different applications:
- Low velocity systems: 0.08-0.10 in. wg/100 ft
- Medium velocity residential: 0.10-0.15 in. wg/100 ft
- Commercial systems: 0.15-0.25 in. wg/100 ft
- Industrial systems: 0.25-0.40 in. wg/100 ft
Lower friction rates reduce fan energy but increase duct size and cost. The optimal friction rate minimizes total lifecycle cost (first cost + present value of operating cost).
Sizing from Friction Chart:
Given airflow $Q$ (cfm) and friction rate $\Delta P_f$ (in. wg/100 ft):
- Locate intersection of $Q$ and $\Delta P_f$ on friction chart
- Read duct diameter or rectangular dimensions
- Read velocity $V$ (fpm) from chart
Advantages:
- Simple to apply manually
- Balanced pressure distribution
- Minimal calculation required
- Good for preliminary sizing
Disadvantages:
- Does not minimize first cost or operating cost
- Requires dampers for final balancing
- Static pressure varies through system
- Not optimal for complex systems
Velocity Method
The velocity method selects duct sizes based on maximum allowable velocities for noise control and energy conservation. This approach directly addresses acoustic constraints.
Maximum Velocity Recommendations:
Design Procedure:
- Select maximum velocities based on application and location
- Calculate required area: $A = Q/V$
- Select standard duct size meeting area requirement
- Reduce velocity progressively downstream
- Calculate actual pressure losses
- Size fan for total system resistance
Velocity Reduction:
Progressive velocity reduction through the system maintains acceptable noise levels while optimizing duct size. A typical reduction strategy:
- Main trunk at maximum velocity
- Reduce 100-200 fpm at each major branch
- Terminal branches at minimum recommended velocity
Advantages:
- Direct noise control
- Simple conceptual approach
- Suitable for noise-sensitive applications
- No complex calculations required
Disadvantages:
- Does not optimize energy or cost
- May result in oversized ducts
- Ignores static pressure recovery
- Conservative approach increases first cost
Static Regain Method
The static regain method exploits velocity pressure conversion to static pressure as velocity decreases. This approach maintains approximately constant static pressure at each branch takeoff, achieving self-balancing without dampers.
Physical Principle:
As air velocity decreases in a reducing trunk, kinetic energy converts to static pressure. The duct section is sized such that the static pressure increase from velocity reduction equals the friction loss in that section:
Static Regain Calculation:
The change in velocity pressure between sections:
For standard air:
Regain Factor:
Not all velocity pressure converts to static pressure due to turbulence and losses. The regain factor $R$ accounts for this inefficiency:
Typical regain factors:
- Straight duct, gradual reduction: $R$ = 0.75-0.90
- Duct with elbow: $R$ = 0.60-0.75
- Abrupt reduction: $R$ = 0.50-0.60
Design Procedure:
- Calculate airflow at each section (cumulative from terminals)
- Select velocity at fan discharge (typically 1500-2500 fpm)
- Size first section for selected velocity
- Calculate friction loss in first section
- Determine velocity reduction to achieve static regain equal to friction loss
- Size next section for reduced velocity
- Repeat for all sections
- Calculate dynamic losses and verify static pressure at branches
Section Sizing Algorithm:
For section $i$ with length $L_i$:
- Known: $Q_i$, $V_{i-1}$, $P_{s,i-1}$
- Estimate $V_i$ (typically 0.8-0.9 × $V_{i-1}$)
- Calculate $P_{v,i}$ and regain: $\Delta P_{v,\text{regain}} = R(P_{v,i-1} - P_{v,i})$
- Size duct such that $\Delta P_f \times L_i/100 = \Delta P_{v,\text{regain}}$
- Verify: $P_{s,i} = P_{s,i-1} + \Delta P_{v,\text{regain}} - \Delta P_f - \Delta P_{\text{fittings}}$
Advantages:
- Balanced static pressure at branches
- Minimal damper requirements
- Optimized for low operating cost
- Self-balancing design
Disadvantages:
- Complex manual calculations
- Requires iterative sizing
- Sensitive to regain factor accuracy
- Difficult to apply without software
Method Comparison
Pressure Loss Calculations
Total pressure loss consists of friction losses in straight duct sections and dynamic losses in fittings, transitions, and equipment.
Friction Loss in Straight Ducts
Friction loss results from viscous shear stress at the duct wall and turbulent momentum exchange. The Darcy-Weisbach equation governs friction loss:
where:
- $f$ = Darcy friction factor (dimensionless)
- $L$ = duct length (ft or m)
- $D_h$ = hydraulic diameter (ft or m)
- $P_v$ = velocity pressure (in. wg or Pa)
Hydraulic Diameter:
For non-circular ducts, the hydraulic diameter represents the equivalent circular diameter for friction calculations:
where:
- $A$ = cross-sectional area
- $P_w$ = wetted perimeter
For rectangular ducts:
where $a$ and $b$ are duct dimensions.
Friction Factor:
The Colebrook equation relates friction factor to Reynolds number and relative roughness:
where:
- $\epsilon$ = absolute roughness (ft or m)
- $Re = \rho V D_h / \mu$ = Reynolds number
- $\mu$ = dynamic viscosity
This implicit equation requires iterative solution. For practical duct design, the Altshul-Tsal equation provides explicit approximation:
Surface Roughness:
Absolute roughness values for common duct materials:
Friction Chart Method:
ASHRAE friction charts incorporate the Darcy-Weisbach equation with standard air properties and assumed roughness ($\epsilon$ = 0.0005 ft for galvanized steel). The charts plot:
- Airflow rate $Q$ (cfm or L/s)
- Duct diameter or dimensions (in. or mm)
- Friction loss (in. wg/100 ft or Pa/m)
- Velocity $V$ (fpm or m/s)
Usage:
- Connect known airflow and duct size
- Read friction loss and velocity
- Scale for actual duct length
Correction for Altitude and Temperature:
Friction loss varies with air density. For non-standard conditions:
Density ratio:
where pressures are absolute and temperatures are absolute (Rankine or Kelvin).
Dynamic Losses in Fittings
Fittings, transitions, and equipment create turbulence and flow separation, resulting in dynamic pressure losses. These losses are quantified by loss coefficients.
Loss Coefficient Method:
where:
- $C$ = loss coefficient (dimensionless)
- $P_v$ = velocity pressure at reference location
The reference velocity depends on fitting type:
- Elbows, entries: velocity in duct section
- Transitions: velocity at smaller cross-section
- Branch takeoffs: velocity in branch or main (specified with $C$ value)
Elbow Loss Coefficients:
Round elbows:
where $R$ = centerline radius, $D$ = duct diameter.
Rectangular elbows without vanes:
where $H$ = height, $W$ = width.
Rectangular elbows with turning vanes reduce losses significantly:
Transition Loss Coefficients:
Gradual transitions (expansion or contraction):
For expansions (increasing area):
based on upstream velocity $V_1$.
For contractions (decreasing area):
based on downstream velocity $V_2$.
where $\theta$ = included angle of transition.
Recommended transition angles:
- Expansions: $\theta$ ≤ 20° (preferred ≤ 15°)
- Contractions: $\theta$ ≤ 30° (preferred ≤ 20°)
Abrupt transitions (no transition section):
Entry and Exit Losses:
Inlet conditions:
Exit losses:
All duct exits discharge to static pressure environment:
Complete velocity pressure is lost (100% loss coefficient). This applies to supply grilles, diffusers, and exhaust hoods.
Damper Losses:
Volume dampers:
Fire/smoke dampers (fully open):
Comprehensive Fitting Loss Table
Total System Pressure Loss
The total pressure loss from fan discharge to terminal equals the sum of all friction and dynamic losses:
For design, calculate the critical path (longest run with highest resistance):
- Identify path from fan to most remote terminal
- Calculate friction loss in each duct section
- Sum all fitting losses along path
- Add terminal device pressure drop
- Include filter and coil pressure drops
- Add safety factor (10-15%) for uncertainty
Fan total pressure requirement:
Aspect Ratio Effects
Rectangular ducts deviate from circular cross-sections, affecting pressure loss and construction cost. The aspect ratio $AR = a/b$ (longer side / shorter side) quantifies this deviation.
Hydraulic Diameter vs. Equivalent Diameter
Two diameter definitions exist for rectangular ducts:
Hydraulic Diameter (for friction calculations):
Equivalent Diameter (circular duct with same friction and flow):
For aspect ratios 1-4, $D_e$ provides accurate friction loss when used with circular duct friction charts.
Pressure Loss vs. Aspect Ratio
For constant cross-sectional area, increasing aspect ratio increases pressure loss:
graph LR
A[12" x 12" Square
AR = 1.0
Baseline Loss] --> B[8" x 18" Rectangle
AR = 2.25
Loss = 1.10x]
B --> C[6" x 24" Rectangle
AR = 4.0
Loss = 1.25x]
C --> D[4" x 36" Rectangle
AR = 9.0
Loss = 1.50x]
style A fill:#90EE90
style B fill:#FFD700
style C fill:#FFA500
style D fill:#FF6347
Aspect ratio correction factor for pressure loss:
Optimal Aspect Ratio
Balancing construction cost, pressure loss, and space constraints:
Construction Cost:
- Square ducts minimize material (lowest perimeter for given area)
- Moderate aspect ratios (2-3) balance material and fabrication costs
- High aspect ratios increase fabrication complexity
Pressure Loss:
- Square ducts minimize friction loss
- Each doubling of aspect ratio increases loss 10-15%
Space Utilization:
- Flat ducts (high AR) fit above ceilings or in wall cavities
- Architectural constraints often drive aspect ratio selection
Recommended Practice:
Structural Considerations
Rectangular ducts require structural reinforcement based on aspect ratio, pressure class, and dimensions. Per SMACNA standards:
Reinforcement Spacing:
For ducts operating at pressure class 2 in. wg:
Velocity Limits for Noise Control
Air velocity generates noise through turbulence and vibration. Excessive velocity produces objectionable acoustic emissions.
Noise Generation Mechanisms
Turbulence Noise:
Velocity fluctuations in turbulent flow create pressure waves:
where:
- $L_W$ = sound power level (dB)
- $V$ = air velocity (fpm)
- $A$ = duct area (ft²)
Doubling velocity increases noise approximately 18 dB.
Fitting Noise:
Elbows, dampers, and branches create vortex shedding and flow separation, generating discrete frequency noise (typically 500-2000 Hz).
Terminal Device Noise:
Grilles and diffusers generate noise as air expands into occupied space. Noise correlates with discharge velocity and pressure drop.
Velocity Recommendations by Application
Maximum velocities to achieve NC (Noise Criteria) levels:
Residential (NC 25-35):
Commercial Office (NC 30-40):
Public Spaces (NC 35-45):
Special Applications:
Grille and Diffuser Selection
Terminal device noise depends on discharge velocity (neck velocity):
Recommended maximum neck velocities:
Actual noise rating depends on manufacturer data. Consult product catalogs for specific NC values at operating conditions.
Duct Materials and Construction Standards
Material selection affects cost, pressure loss (surface roughness), and system longevity.
Galvanized Steel Duct
Material Specifications:
ASTM A653 galvanized steel, coating designation G60 (0.60 oz/ft² per side) minimum.
Gauge Selection (SMACNA):
Round duct:
Rectangular duct (longest side):
Construction Types:
- Spiral wound: Helical seam, efficient fabrication, limited sizes
- Longitudinal seam: Straight seam, any length, standard construction
- Snap-lock: Low-pressure applications (≤ 2 in. wg), residential
- Standing seam: Exposed architectural ductwork
Joint Types:
Sealing Requirements:
SMACNA Seal Class:
- Class A: Sealed transverse joints only (≤ 2 in. wg)
- Class B: Sealed transverse joints and longitudinal seams (2-4 in. wg)
- Class C: All joints sealed, gasketed flanges (> 4 in. wg)
Fiberglass Duct Board
Rigid fiberglass board fabricated into rectangular ducts.
Material Properties:
- Thermal resistance: R-4 to R-8 per inch thickness
- Density: 3-6 lb/ft³
- Fire rating: ASTM E84 Class 1 (flame spread ≤ 25)
Advantages:
- Integrated thermal insulation
- Acoustic attenuation (1-2 dB/ft typical)
- Lower installed cost for certain applications
- No external insulation required
Disadvantages:
- Lower pressure rating (2-4 in. wg maximum)
- Higher surface roughness (increased friction)
- Potential fiber shedding (requires sealed liner in critical applications)
- Moisture sensitivity
Sizing Considerations:
Friction loss 30-50% higher than galvanized steel due to roughness:
Use fiberglass-specific friction charts or apply correction factor.
Flexible Duct
Flexible duct consists of wire helix supporting polymer film with external insulation.
Material Construction:
- Inner core: Polymer film (polyester, metallized polyester)
- Support: Spring steel wire helix
- Insulation: Fiberglass batting (R-4.2 to R-8)
- Vapor barrier: Polymer film jacket
Pressure Loss:
Flexible duct exhibits significantly higher friction than rigid duct:
Installation Requirements:
ASHRAE/SMACNA standards for flexible duct:
- Maximum length: 5 ft per run (minimize use)
- Full extension: No compression allowed
- Support spacing: 4 ft maximum
- Turns: Minimize bends, radius ≥ 1.5 × diameter
- Connections: Secured with draw bands over beads
Applications:
Flexible duct serves as terminal connections between rigid duct and diffusers:
- VAV box to diffuser connections
- Duct system adjustments during installation
- Temporary installations
- Vibration isolation connections
Do not use flexible duct as primary distribution due to high friction loss.
Insulation Requirements
External Insulation Applications:
Supply air ducts require insulation to:
- Prevent condensation (cooling applications)
- Reduce heat gain/loss (energy efficiency)
- Reduce noise transmission (acoustic barrier)
Thickness Selection:
Vapor Barrier:
Cooling applications require vapor barrier on outer surface to prevent moisture infiltration. Vapor retarder permeability ≤ 0.02 perms.
Return Air Ducts:
Return ducts typically do not require insulation when located in conditioned space. Insulate return ducts in unconditioned spaces to prevent condensation and heat gain.
Branch Takeoff Design
Branch takeoffs significantly affect pressure distribution and system balance.
Takeoff Configurations
graph TD
A[Main Duct Flow] --> B{Takeoff Type}
B --> C[45° Wye
C = 0.30-0.50]
B --> D[90° Conical Tee
C = 0.15-0.30]
B --> E[90° Tee
C = 0.90-1.50]
B --> F[Bullhead Tee
C = 1.50-3.00]
style C fill:#90EE90
style D fill:#90EE90
style E fill:#FFD700
style F fill:#FF6347
45° Wye (Preferred):
Low loss coefficient, smooth flow division:
where:
- $V_b$ = branch velocity
- $V_m$ = main duct velocity upstream
Conical Tee (Preferred for 90°):
Tapered entry reduces separation:
90° Tee (Avoid):
Abrupt flow direction change creates high loss:
Bullhead Tee (Avoid):
Flow splits into two opposing branches, maximum loss:
Main Duct Loss at Takeoffs
The main duct experiences loss as flow divides at branches:
Straight-Through Loss:
where:
- $Q_b$ = branch flow
- $Q_m$ = main duct flow upstream
- $C_0$ = base coefficient (0.10-0.30 depending on configuration)
Takeoff Sizing Strategy
Equal Velocity Method:
Maintain approximately equal velocities in main and branch:
This minimizes loss coefficient and balances static pressure.
Progressive Reduction:
Reduce main duct velocity downstream of each takeoff:
- Calculate airflow remaining after branch
- Resize main duct for 80-90% of upstream velocity
- Takeoff sees balanced static pressure
Damper Placement:
Locate balancing dampers 3-5 duct diameters downstream of takeoff to allow flow reattachment. Dampers immediately at takeoff increase turbulence and noise.
Return Air and Exhaust Duct Sizing
Return air systems operate at lower pressure and velocity than supply systems.
Return Air Velocity Limits
Lower velocities permitted due to:
- Less critical noise propagation (grilles in low-sensitivity areas)
- Lower static pressure availability
- Larger duct cross-sections economically feasible
Recommended maximum velocities:
Return Air Pathways
Ducted Return:
Fully ducted return systems provide:
- Controlled airflow paths
- Minimal leakage
- Acoustic isolation between spaces
- Higher first cost
Size using equal friction method at 0.05-0.08 in. wg/100 ft (lower than supply).
Plenum Return:
Use of ceiling plenum, wall cavities, or raised floors as return air path:
Advantages:
- Lower first cost (no duct material)
- Easier installation
- Flexible for future modifications
Disadvantages:
- Potential odor and contaminant transfer
- Code restrictions in rated construction
- Leakage to outdoors (increased load)
- Sound transmission between spaces
Code Requirements:
Plenum spaces must:
- Use plenum-rated cables (CMP, FEP)
- Maintain fire rating with proper penetrations
- Provide access for cleaning
- Meet IMC Section 602 requirements
Sizing:
Plenum velocity should not exceed 1.5× ducted return velocity limits to prevent excessive noise from grilles and registers.
Exhaust System Sizing
Kitchen, bathroom, and laboratory exhaust systems:
Velocity Recommendations:
Grease Exhaust:
Kitchen exhaust ducts require special considerations:
- Minimum velocity 1500 fpm (prevent grease deposition)
- Carbon steel (not galvanized, coating degrades)
- Welded construction, grease-tight
- Slope 2% toward hood for drainage
- Access panels for cleaning
Dust and Fume:
Material transport velocity depends on particle size and density. Consult ACGIH Industrial Ventilation Manual for specific materials.
Practical Design Examples
Example 1: Residential Forced Air System
System Description:
Single-story residence, 2400 ft², cooling load 36,000 Btu/h (3 tons).
Design Parameters:
- Supply airflow: $Q = 400$ cfm/ton × 3 ton = 1200 cfm
- Supply air temperature: 55°F
- Return air temperature: 75°F
- Duct location: Unconditioned attic
- Design method: Equal friction
Step 1: Select Friction Rate
For residential system in attic: 0.10 in. wg/100 ft
Step 2: Main Trunk Sizing
At furnace discharge: $Q$ = 1200 cfm
From friction chart at 0.10 in. wg/100 ft and 1200 cfm:
- Round duct diameter: 14 in.
- Velocity: 940 fpm
- Actual friction: 0.10 in. wg/100 ft
Alternatively, rectangular duct:
- Using $D_e = 1.30(ab)^{0.625}/(a+b)^{0.25} = 14$ in.
- Try 10 × 20 in.: $D_e = 1.30(200)^{0.625}/30^{0.25} = 14.0$ in. ✓
- Aspect ratio: 2.0 (acceptable)
Step 3: Branch Sizing
All sized at 0.10 in. wg/100 ft friction rate.
Step 4: Pressure Loss Calculation (Critical Path)
Longest run: Furnace → Master bedroom (80 ft total)
Friction losses:
Fitting losses:
Step 5: Total System Resistance
Add safety factor (15%):
Step 6: Return System
Return airflow: 1200 cfm (same as supply)
Size at lower friction rate (0.08 in. wg/100 ft):
- Return trunk: 16 in. diameter (or 12 × 20 rectangular)
- Branch returns: Typically use ceiling grilles with short plenum connection
Return system pressure drop: ~0.10 in. wg (including filter)
Step 7: Fan Selection
External static pressure requirement:
Select furnace/air handler with fan rated for 1200 cfm at 0.35 in. wg ESP minimum.
Example 2: Commercial VAV System
System Description:
Office building floor, 12,000 ft², 120 tons cooling capacity.
Design Parameters:
- Peak supply airflow: 48,000 cfm (400 cfm/ton)
- Supply air temperature: 55°F
- Distribution: 24 VAV boxes, 2000 cfm each
- Duct location: Ceiling plenum
- Design method: Static regain
Step 1: Main Duct Initial Sizing
Select discharge velocity: 2000 fpm
Required area:
Circular diameter:
Use 66 in. diameter round or 36 × 60 in. rectangular duct ($D_e$ = 66 in., AR = 1.67).
Step 2: Section-by-Section Sizing (Static Regain)
First section (fan to first VAV box):
- Length: 40 ft
- Flow: 48,000 cfm
- Velocity: 2000 fpm
- $P_v = (2000/4005)^2 = 0.25$ in. wg
Friction loss at 66 in. diameter:
- From friction chart: 0.14 in. wg/100 ft
- Section loss: 0.14 × 40/100 = 0.056 in. wg
After first takeoff (2000 cfm removed):
- Remaining flow: 46,000 cfm
- Target velocity for static regain: Solve for velocity where friction equals regain
Regain available:
With regain factor $R$ = 0.75:
Target friction for next section: 0.056 in. wg / 35 ft × 100 = 0.16 in. wg/100 ft
From friction chart at 46,000 cfm and 0.16 in. wg/100 ft:
- Diameter: 62 in.
- Velocity: 1900 fpm
- Verify regain: $\Delta P_v = 0.25 - (1900/4005)^2 = 0.25 - 0.23 = 0.02$ in. wg
- Regained: 0.75 × 0.02 = 0.015 in. wg ≈ 0.016 in. wg (close enough)
Continue this process for each section, progressively reducing diameter and velocity.
Step 3: Fitting Losses
Major fittings in critical path:
Step 4: Total Pressure
With proper static regain design, friction losses approximately balance velocity pressure recovery. Total system pressure dominated by:
- Fitting losses: 0.40 in. wg
- Residual friction (imperfect regain): 0.10 in. wg
- Safety factor: 0.10 in. wg
Total system pressure: ~0.60 in. wg
Add filter (0.50 in. wg) and coil (0.80 in. wg):
At discharge velocity 2000 fpm:
Fan total pressure:
Step 5: VAV System Considerations
At minimum flow (30% of design):
- Main duct flow: 14,400 cfm
- Velocity: 600 fpm (1/3 of design)
- Pressure loss: $(600/2000)^2 = 0.09×$ design ≈ 0.05 in. wg
- Fan rides back on curve, pressure increases
- VAV boxes throttle to maintain setpoint
- Fan control (VFD) reduces speed to maintain duct static pressure
Design static pressure sensor location: 2/3 distance into duct system to maintain adequate pressure at all terminals.
Example 3: Flex Duct Runout Analysis
Configuration:
VAV box to ceiling diffuser connection using flexible duct.
Parameters:
- Airflow: 500 cfm
- Flex duct diameter: 10 in.
- Length: 6 ft (exceeds 5 ft recommendation, but common in practice)
- Diffuser pressure drop: 0.04 in. wg
Rigid Duct Alternative:
10 in. rigid round duct:
- Velocity: $V = 500/(π × (10/12)^2 / 4) = 917$ fpm
- Friction: 0.08 in. wg/100 ft (from chart)
- Loss: 0.08 × 6/100 = 0.0048 in. wg
Flex Duct (Fully Extended):
Friction multiplier: 2.0× rigid duct
- Friction: 0.16 in. wg/100 ft
- Loss: 0.16 × 6/100 = 0.0096 in. wg
Flex Duct (10% Compressed to 5.4 ft):
Friction multiplier: 3.0× rigid duct
- Effective friction: 0.24 in. wg/100 ft
- Loss: 0.24 × 5.4/100 = 0.013 in. wg
Impact Analysis:
For 24 diffusers in building:
*Assumes 3000 operating hours/year, $0.12/kWh, fan efficiency 60%, motor efficiency 92%.
Energy Cost Calculation:
Pressure increase from flex duct: $\Delta P$ = 0.24 - 0.12 = 0.12 in. wg
Fan power increase:
Annual cost:
Conclusion:
Minimize flex duct use. Each 6 ft flex connection costs $110-285/year additional energy compared to rigid duct. Over 20-year lifecycle, this represents $2200-5700 per connection at 3% discount rate.
Advanced Design Considerations
Duct Heat Gain and Loss
Air temperature changes as heat transfers through duct walls. This affects delivered capacity and humidity control.
Heat Transfer Rate:
where:
- $U$ = overall heat transfer coefficient (Btu/h·ft²·°F)
- $A_s$ = duct surface area (ft²)
- $T_{\text{ambient}}$ = surrounding air temperature (°F)
- $T_{\text{air}}$ = duct air temperature (°F)
Overall Heat Transfer Coefficient:
For typical insulated duct in attic:
- Interior film coefficient $h_i$ = 1.5 Btu/h·ft²·°F
- Insulation conductivity $k_{\text{ins}}$ = 0.25 Btu/h·ft·°F (fiberglass)
- Insulation thickness $t_{\text{ins}}$ = 2 in. = 0.167 ft
- Exterior film coefficient $h_o$ = 2.0 Btu/h·ft²·°F
Temperature Change:
where:
- $Q$ = airflow (cfm)
- 1.08 = specific heat factor for air (Btu/h per cfm·°F)
Example:
20 in. diameter duct, 50 ft length in 130°F attic, 55°F supply air, 1200 cfm flow:
Surface area: $A_s = π × (20/12) × 50 = 261$ ft²
Heat gain:
Temperature rise:
Delivered air temperature: 55 + 8.2 = 63.2°F (significantly degraded cooling capacity).
Mitigation:
- Locate ducts in conditioned space
- Increase insulation thickness (R-8 minimum in unconditioned spaces)
- Minimize duct length in extreme environments
- Consider buried duct in attic insulation
Duct Leakage
Real duct systems leak air through joints, penetrations, and damaged sections. Leakage reduces delivered airflow and increases energy consumption.
Leakage Classes:
ASHRAE 90.1 and IECC define duct leakage classes:
Leakage Rate:
where:
- $C_L$ = leakage class (cfm/100 ft² @ 1 in. wg)
- $A_s$ = duct surface area (ft²)
- $\Delta P$ = duct pressure (in. wg)
Example:
1000 ft² duct surface area, Seal Class 12, operating at 2 in. wg:
For 10,000 cfm system, this represents 1.88% leakage.
Impact:
- Reduced delivered airflow to terminals
- Increased fan energy (higher flow at fan)
- Increased heating/cooling energy (conditioned air lost to unconditioned space)
- Pressure imbalance (negative pressure sucks in unconditioned air)
Testing:
Duct leakage testing per ANSI/RESNET/ICC 380:
- Pressurize system to 25 Pa (0.1 in. wg)
- Measure airflow required to maintain pressure
- Calculate leakage as cfm per 100 ft² of duct surface area
Target: ≤ 6 cfm/100 ft² @ 25 Pa for tight construction.
Summary and Design Process
Comprehensive Design Workflow
Load Calculation and Airflow Requirements
- Calculate heating and cooling loads per ACCA Manual J or ASHRAE methods
- Determine supply airflow: $Q = \text{Load} / (1.08 \times \Delta T)$
- Establish terminal airflow requirements
Preliminary Layout
- Sketch duct routing on building plans
- Identify available space for duct installation
- Locate supply and return terminals
- Determine critical path (longest, highest resistance run)
Sizing Method Selection
- Equal friction: Simple systems, manual design
- Velocity method: Noise-critical applications
- Static regain: Large systems, energy efficiency priority
Main Duct Sizing
- Select initial velocity or friction rate
- Size main trunk duct
- Verify aspect ratio ≤ 4:1 preferred, ≤ 8:1 maximum
Branch and Runout Sizing
- Size branches using selected method
- Progressively reduce velocity downstream
- Maintain velocity limits for noise control
Pressure Loss Calculation
- Calculate friction loss for all sections
- Determine fitting loss coefficients
- Sum losses along critical path
- Add equipment pressure drops (filter, coil, terminal devices)
Return System Design
- Size return ducts at lower friction rate
- Consider plenum return where applicable
- Calculate return system pressure loss
Fan Selection
- Sum supply and return pressure losses
- Add safety factor (10-15%)
- Select fan for required CFM at total ESP
- Verify fan operating point on performance curve
Detail Design
- Specify duct materials and gauges
- Detail transitions and fittings
- Locate balancing dampers
- Specify insulation and sealing requirements
Verification
- Check all velocities against limits
- Verify aspect ratios
- Confirm available static pressure at all terminals
- Review for constructability and access
Key Design Principles
Minimize Pressure Loss:
- Use gradual transitions (15-20° expansion, 20-30° contraction)
- Prefer 45° wye takeoffs over 90° tees
- Specify turning vanes in rectangular elbows
- Minimize flex duct use (≤ 5 ft, fully extended)
Maintain Velocity Limits:
- Select velocities based on application noise criteria
- Reduce velocity progressively downstream
- Keep terminal runout velocities low (500-800 fpm)
- Consider acoustic lining for high-velocity ducts
Optimize Aspect Ratio:
- Prefer square or near-square cross-sections (AR ≤ 2)
- Use flat ducts only where space requires (AR ≤ 8 maximum)
- Remember: each doubling of AR increases loss 10-15%
Ensure Proper Sealing:
- Specify seal class per ASHRAE 90.1
- Seal all transverse joints and longitudinal seams
- Use mastic or approved tapes (no cloth-backed duct tape)
- Test duct leakage on critical projects
Account for Real-World Conditions:
- Include safety factors (10-15%) for uncertainty
- Consider duct heat gain/loss in unconditioned spaces
- Specify adequate insulation (R-6 to R-8 minimum)
- Design for future modifications and access
This comprehensive approach to duct design integrates fluid mechanics fundamentals with practical construction constraints, delivering efficient, quiet, and reliable air distribution systems. The physics-based methods presented enable engineers to understand system behavior, optimize designs, and troubleshoot performance issues throughout the system lifecycle.
References and Standards
- ASHRAE Handbook—Fundamentals, Chapter 21: Duct Design
- ASHRAE Standard 90.1: Energy Standard for Buildings Except Low-Rise Residential Buildings
- SMACNA HVAC Duct Construction Standards—Metal and Flexible
- ACCA Manual D: Residential Duct Systems
- ASHRAE Duct Fitting Database (DFDB)
- ANSI/RESNET/ICC 380: Standard for Testing Airtightness of Building Enclosures, Airtightness of Heating and Cooling Air Distribution Systems
- International Mechanical Code (IMC)
- TABB Procedural Standards for Testing, Adjusting, Balancing of Environmental Systems