HVAC Systems Encyclopedia

A comprehensive encyclopedia of heating, ventilation, and air conditioning systems

NFPA 90B Warm Air Heating & Residential HVAC Systems

NFPA 90B establishes installation standards for warm air heating and air conditioning systems serving residential and small commercial occupancies. This standard addresses one- and two-family dwellings, manufactured homes, recreational vehicles, and other low-rise residential buildings with individual heating and cooling systems.

Scope and Application

NFPA 90B applies to warm air heating systems where the air circulation capacity does not exceed 2,000 cfm (cubic feet per minute) and the heat input does not exceed 400,000 BTU/hr for gas-fired appliances or 250,000 BTU/hr for oil-fired appliances. The standard coordinates closely with International Residential Code (IRC) Chapter 16 for duct systems and Chapter 24 for fuel gas installations.

The standard covers:

  • Factory-built fireplaces and fireplace stoves
  • Residential forced air furnaces (gas, oil, electric)
  • Heat pumps and air conditioning systems
  • Duct systems (supply, return, and exhaust)
  • Air distribution components and accessories

Duct Material Requirements

Duct materials must meet specific performance criteria for fire resistance, structural integrity, and air leakage prevention. The following table outlines approved materials and their applications:

Material TypeApplicationMax TemperatureThickness Requirements
Galvanized steelSupply/return ducts250°F continuous28 gauge min for ≤14" dia
Aluminum sheetSupply/return ducts250°F continuous0.019" min for ≤14" dia
Stainless steelHigh-temp applications1,000°F continuous28 gauge min
Fiberglass duct boardLow-velocity systems250°F continuousListed and labeled
Flexible duct (metalized)Short runs, connections250°F intermittentUL 181 listed
PVC/CPVCCombustion air intakePer listingListed for application
Concrete/masonryUnderground/embeddedVariesLined or coated

All duct materials must bear appropriate listings from recognized testing laboratories (UL 181 for flexible ducts, UL 181A for rigid fiberglass, UL 181B for closure systems).

Furnace and Equipment Clearances

Clearance requirements prevent fire hazards and ensure proper operation. These dimensions represent minimum distances from combustible materials unless equipment is specifically listed for reduced clearances:

Equipment TypeFrontSidesRearTopFlue Pipe
Gas furnace (standard)24"6"6"6"6" radial
Oil furnace (standard)24"12"12"18"18" radial
Electric furnace24"3"3"3"N/A
Listed low-clearancePer labelPer labelPer labelPer labelPer label
Heat pump (indoor)24"6"6"6"N/A

Equipment installed in alcoves or closets requires additional clearances to ensure adequate combustion air supply (for fuel-burning appliances) and service access. The front clearance must allow full access to the burner compartment and controls.

Residential HVAC Installation Configuration

graph TD
    A[Return Air Grille<br/>Filter Location] -->|Return Duct| B[Furnace/Air Handler<br/>in Utility Room]
    B -->|Supply Plenum| C[Main Trunk Duct]
    B -->|Flue Pipe 6 clearance| D[Chimney/Vent Terminal]
    C -->|Branch Duct| E[Supply Register<br/>Bedroom 1]
    C -->|Branch Duct| F[Supply Register<br/>Bedroom 2]
    C -->|Branch Duct| G[Supply Register<br/>Living Room]
    C -->|Branch Duct| H[Supply Register<br/>Kitchen]

    style B fill:#ff9999
    style A fill:#99ccff
    style E fill:#99ff99
    style F fill:#99ff99
    style G fill:#99ff99
    style H fill:#99ff99
    style D fill:#ffcc99

    subgraph Clearances
    I[6 minimum from<br/>combustible walls]
    J[24 front access<br/>clearance required]
    end

Duct Installation Requirements

Supply Duct Construction: Supply ducts must maintain structural integrity under positive pressure (typically 0.5 to 2.0 inches w.c.) and resist air leakage. Joints and seams require mechanical fastening plus mastic sealant or pressure-sensitive tape meeting UL 181A-P (rigid) or UL 181B-FX (flexible) standards. Longitudinal seams must be on upper surfaces where accessible.

Return Duct Construction: Return air systems operate under negative pressure and require careful sealing to prevent infiltration of unconditioned air or contaminants. Building cavities (joist spaces, stud bays) are prohibited as return air plenums unless they are sealed and constructed of continuous combustible materials or lined with approved duct material.

Support and Bracing: Metal ducts require support at maximum 10-foot intervals using metal straps, hangers, or brackets. Flexible duct must be supported every 4 feet maximum and stretched to minimize pressure drop (sag not exceeding 1/2 inch per foot of length).

Penetrations: Where ducts pass through fire-rated assemblies (walls, floors, ceilings), fire dampers or other fire-stopping methods are required to maintain the assembly’s fire rating. Combustible ducts must be replaced with metal for 18 inches on both sides of the penetration.

Combustion Air and Ventilation

Fuel-burning appliances require adequate combustion air to ensure complete combustion and prevent spillage of combustion products. Two methods are recognized:

Indoor Combustion Air: Requires two permanent openings (one within 12 inches of ceiling, one within 12 inches of floor), each with minimum free area of 100 square inches per 1,000 BTU/hr input for confined spaces. Buildings with tight construction (infiltration-resistant) require dedicated outdoor air supply.

Outdoor Combustion Air: Direct connection to outdoors via two openings or single opening with motorized dampers. Minimum free area is 1 square inch per 4,000 BTU/hr input when both openings connect directly to outdoors.

Special Installation Considerations

Attic Installations: Ducts in unconditioned attics require insulation meeting or exceeding R-8 thermal resistance to prevent condensation and heat loss. Support must account for additional weight of insulation. Access for service must be provided per IRC requirements (minimum 22 x 30 inch opening, unobstructed path).

Crawlspace Installations: Ducts in vented crawlspaces require insulation and vapor barrier protection. Support must prevent contact with ground. Flexible duct is permitted but must be installed on solid surfaces or suspended to prevent damage from foot traffic during service.

Garage Installations: Equipment and ductwork installed in garages must be protected from physical damage and installed with base elevation minimum 18 inches above floor for fuel-burning appliances (to prevent ignition of gasoline vapors, which are heavier than air).

Manufactured Housing: Additional requirements apply per HUD standards, including duct system tightness testing and specific support methods to prevent damage during transportation and setup.

Inspection and Testing

Duct systems must be inspected for proper materials, support, and sealing before concealment. Visual inspection verifies clearances, proper slope for condensate drainage (if applicable), and absence of damage. Some jurisdictions require duct leakage testing, with maximum permitted leakage of 6 to 8 cfm per 100 square feet of conditioned floor area at 25 Pa test pressure.

The authority having jurisdiction may require demonstration of adequate combustion air supply, proper venting of combustion products, and verification that automatic safety controls function correctly before final approval.

Coordination with Other Standards

NFPA 90B coordinates with multiple standards to provide comprehensive installation guidance:

  • NFPA 54 (National Fuel Gas Code) for gas piping and appliance connections
  • NFPA 31 for oil-burning equipment installation
  • NFPA 211 for chimneys, fireplaces, vents, and solid fuel systems
  • IRC Chapters 12-24 for residential mechanical systems
  • ASHRAE 62.2 for residential ventilation requirements

Equipment manufacturers’ installation instructions take precedence when they specify more restrictive requirements than NFPA 90B, as equipment listings are based on specific installation parameters verified through testing.