HVAC Systems Encyclopedia

A comprehensive encyclopedia of heating, ventilation, and air conditioning systems

ASHRAE 170: Ventilation of Healthcare Facilities

ASHRAE Standard 170, Ventilation of Health Care Facilities, establishes minimum ventilation requirements for healthcare spaces to minimize infection transmission, control odors, and maintain appropriate environmental conditions. This standard works in conjunction with the Facility Guidelines Institute (FGI) Guidelines for Design and Construction of Hospitals and Outpatient Facilities.

Fundamental Design Principles

Healthcare facility HVAC systems differ fundamentally from commercial buildings due to critical requirements for infection control, patient safety, and regulatory compliance. The standard addresses three primary infection control strategies:

Dilution Ventilation reduces airborne contaminant concentrations through continuous air change. The total air changes per hour (ACH) required depends on space function, with critical areas demanding higher rates.

Directional Airflow controls contaminant migration through pressure relationships. Positive pressure protects immunocompromised patients by preventing infiltration of corridor air, while negative pressure contains infectious aerosols in isolation rooms.

Filtration removes particulates and microorganisms. The standard specifies minimum efficiency reporting value (MERV) ratings and, for critical spaces, high-efficiency particulate air (HEPA) filtration.

Pressure Relationship Requirements

Pressure differentials prevent cross-contamination between spaces. The standard requires minimum pressure differences of 2.5 Pa (0.01 in. w.g.) between adjacent spaces, though design values of 5-10 Pa provide operational margin.

graph LR
    A[Corridor<br/>Neutral Reference] -->|Negative| B[Isolation Room<br/>-2.5 Pa min]
    A -->|Positive| C[Operating Room<br/>+2.5 Pa min]
    A -->|Positive| D[Protective Environment<br/>+2.5 Pa min]
    B -->|Negative| E[Anteroom<br/>-1.25 Pa]
    D -->|Positive| F[Anteroom<br/>+1.25 Pa]
    C -->|Recirculation| G[HEPA Filter<br/>99.97% @ 0.3μm]

    style B fill:#ffcccc
    style C fill:#ccffcc
    style D fill:#ccccff
    style E fill:#ffe6cc
    style F fill:#e6ccff

Room-by-Room Design Parameters

Critical Care and Surgical Spaces

Space TypePressureACH TotalACH Outside AirRecirculationAir FiltrationTemperature (°F)RH (%)
Operating Room (Class B/C)Positive20 min4 minPermittedMERV 14 + HEPA68-7320-60
Protective Environment (PE)Positive12 min2 minNot permittedMERV 14 + HEPA68-7540 max
Airborne Infection Isolation (AII)Negative12 min2 minNot permittedMERV 1468-7530-60
Intensive Care Unit (ICU)Positive/Equal6 min2 minPermittedMERV 1470-7530-60
Cardiac CatheterizationPositive15 min3 minPermittedMERV 14 + HEPA68-7320-60

Diagnostic and Treatment Areas

Space TypePressureACH TotalACH Outside AirAir FiltrationTemperature (°F)RH (%)
Emergency DepartmentEqual/Negative12 min2 minMERV 1470-7530-60
Bronchoscopy RoomNegative12 min2 minMERV 1468-7530-60
Autopsy RoomNegative12 min2 minMERV 868-7530-60
Radiology (X-ray)Equal6 min2 minMERV 872-7830-60
MRI SuiteEqual6 min2 minMERV 870-7530-60
Pharmacy (Sterile Compounding)Positive30 min4 minMERV 14 + HEPA68-7330-60

Support and Ancillary Spaces

Space TypePressureACH TotalACH Outside AirAir Filtration
Soiled WorkroomNegative10 min2 minMERV 8
Sterilizer Equipment RoomNegative10 min2 minMERV 8
Housekeeping RoomNegative10 min2 minMERV 8
Food PreparationNegative10 min2 minMERV 8
Patient Toilet RoomNegative10 min1 minMERV 8

Air Change Calculations

The total air changes per hour is calculated from the required airflow rate and room volume:

$$\text{ACH} = \frac{Q \times 60}{V}$$

Where:

  • $\text{ACH}$ = Air changes per hour
  • $Q$ = Airflow rate (CFM)
  • $V$ = Room volume (ft³)

For rooms with minimum ACH requirements, the required airflow becomes:

$$Q = \frac{\text{ACH} \times V}{60}$$

Outside air ventilation must meet the greater of the ACH requirement or the ventilation needed for thermal load control:

$$Q_{oa} = \max\left(\frac{\text{ACH}{oa} \times V}{60}, \frac{Q{sensible}}{1.08 \times \Delta T}\right)$$

Where:

  • $Q_{oa}$ = Outside air flow rate (CFM)
  • $Q_{sensible}$ = Sensible cooling load (BTU/hr)
  • $\Delta T$ = Supply-to-room temperature difference (°F)

Filtration Requirements

Healthcare facilities require progressive filtration to protect both patients and HVAC equipment:

MERV 8 Prefilter: Protects downstream equipment and maintains system cleanliness. Minimum for all healthcare supply systems.

MERV 14 Secondary Filter: Required for patient care areas. Captures 75-85% of 0.3-1.0 μm particles, including most bacterial carriers and large viral aerosols.

HEPA Final Filter: Required for protective environments, operating rooms, and pharmaceutical compounding. Removes ≥99.97% of 0.3 μm particles. Filter efficiency testing:

$$E = \left(1 - \frac{C_{downstream}}{C_{upstream}}\right) \times 100%$$

Where efficiency $E$ must be ≥99.97% at the most penetrating particle size (MPPS) of 0.3 μm.

Special Ventilation Considerations

Anteroom Design: Anterooms buffer pressure transitions between isolation rooms and corridors. They may operate in positive, negative, or neutral mode depending on whether they serve protective environments or airborne infection isolation rooms.

Demand-Based Control: Some non-critical spaces permit airflow reduction during unoccupied periods, but critical areas require continuous operation at full ACH rates regardless of occupancy.

Redundancy Requirements: Life safety systems serving operating rooms and critical care areas should incorporate redundant equipment, emergency power connections, and fail-safe controls to maintain pressure relationships during equipment failure.

Humidity Control: Relative humidity control prevents bacterial growth (>60% RH) and static electricity issues (<30% RH). Operating rooms and protective environments have the tightest tolerances.

Integration with FGI Guidelines

The FGI Guidelines reference ASHRAE 170 as the authoritative ventilation standard but add space types and requirements not covered in ASHRAE 170. Designers must comply with both documents, applying the more stringent requirement when conflicts arise. Recent editions have improved alignment between the two standards, particularly regarding anteroom configurations and Class B versus Class C operating rooms.

Components

  • Ventilation Healthcare Ashrae 170
  • Pressure Relationships Healthcare
  • Air Change Rates Healthcare
  • Filtration Healthcare
  • Temperature Humidity Healthcare
  • Design Parameters Space Type