HVAC Systems Encyclopedia

A comprehensive encyclopedia of heating, ventilation, and air conditioning systems

AHRI Standards Ratings

Overview

The Air-Conditioning, Heating, and Refrigeration Institute (AHRI) establishes performance and rating standards for HVAC and refrigeration equipment. AHRI standards define test conditions, measurement procedures, and rating methodologies that ensure consistent equipment evaluation across manufacturers.

AHRI Certification Programs

AHRI operates voluntary certification programs that verify manufacturer claims through independent testing.

Certification Process

  1. Manufacturer Participation: Manufacturers submit equipment for certification
  2. Sample Selection: Random samples selected from production units
  3. Third-Party Testing: Independent laboratories conduct tests per AHRI standards
  4. Data Verification: Test results compared against published ratings
  5. Directory Publication: Certified equipment listed in AHRI directories
  6. Ongoing Surveillance: Periodic retesting maintains certification validity

Certified Product Directories

AHRI publishes directories of certified equipment accessible online. Each listing includes:

  • Model numbers and variations
  • Capacity ratings at specified conditions
  • Efficiency metrics (SEER, EER, IPLV, COP)
  • Operating voltage and phase
  • Refrigerant type and charge
  • Sound ratings
  • Certification date and status

Equipment Rating Standards

AHRI 210/240 Unitary Air-Conditioners and Heat Pumps

Covers residential and light commercial equipment up to 65,000 Btu/h cooling capacity.

Key Rating Metrics:

MetricTest ConditionApplication
SEER (Seasonal Energy Efficiency Ratio)Weighted seasonal averagePrimary efficiency metric for cooling
EER (Energy Efficiency Ratio)95°F outdoor dry bulbPeak load performance
HSPF (Heating Seasonal Performance Factor)Seasonal heating averageHeat pump heating efficiency
COP (Coefficient of Performance)47°F outdoor for heatingInstantaneous heating efficiency

SEER Calculation: Based on total seasonal cooling output divided by total electrical energy input during a typical cooling season. Test conditions range from 65°F to 104°F outdoor temperature.

Current Minimum Standards:

  • Split systems: SEER 14.0 (southern regions), SEER 13.0 (northern regions)
  • Package units: SEER 14.0
  • Heat pumps: SEER 14.0, HSPF 8.2

AHRI 310/380 Packaged Terminal Equipment

Applies to through-the-wall air conditioners and heat pumps (PTACs and PTHPs).

Rating Conditions:

  • Cooling: 95°F outdoor dry bulb, 80°F/67°F indoor dry bulb/wet bulb
  • Heating: 47°F outdoor, 70°F indoor
  • Standard wall sleeve installation

Performance Requirements:

  • EER varies by capacity: EER = 12.0 - (0.3 × capacity in 1000 Btu/h)
  • Minimum COP for heat pumps: 3.0 at 47°F outdoor

AHRI 340/360 Commercial and Industrial Unitary Equipment

Covers commercial unitary air conditioners and heat pumps exceeding 65,000 Btu/h.

Rating Points:

Equipment TypeCooling CapacityPrimary Metric
Air-cooled <135,000 Btu/h65,000-135,000 Btu/hEER and IEER
Air-cooled ≥135,000 Btu/h≥135,000 Btu/hEER and IEER
Water-cooledAll capacitiesEER and IPLV

IEER (Integrated Energy Efficiency Ratio): Part-load efficiency metric calculated from performance at four operating points:

  1. 100% capacity at 95°F outdoor
  2. 75% capacity at 81°F outdoor
  3. 50% capacity at 68°F outdoor
  4. 25% capacity at 65°F outdoor

IEER Formula: IEER = 0.020A + 0.617B + 0.238C + 0.125D

Where A, B, C, D are EER values at 100%, 75%, 50%, and 25% load respectively.

AHRI 365 Commercial and Industrial Air-Source Heat Pumps

Establishes ratings for large commercial heat pumps.

Test Conditions:

  • Cooling: 95°F outdoor, 80°F/67°F indoor
  • Heating standard: 47°F outdoor, 70°F indoor
  • Heating low temperature: 17°F outdoor, 70°F indoor

Performance Metrics:

  • EER for cooling at full load
  • COP for heating at 47°F and 17°F
  • IPLV for part-load cooling efficiency

AHRI 400 Liquid-to-Liquid Heat Exchangers

Covers shell-and-tube, brazed plate, and other liquid heat exchangers.

Rating Requirements:

  • Fouling factors specified for both fluid sides
  • Pressure drop at rated flow
  • Heat transfer capacity at specified inlet temperatures and flow rates
  • Materials of construction

Standard Test Conditions: Varies by application (water-to-water, glycol solutions, refrigerant-to-water).

AHRI 410 Forced-Circulation Air-Cooling and Air-Heating Coils

Defines rating for chilled water and hot water coils.

Coil Performance Data:

ParameterCooling CoilsHeating Coils
CapacitySensible and totalTotal heat output
Air pressure dropAt rated CFMAt rated CFM
Water pressure dropAt rated GPMAt rated GPM
Entering air conditions80°F DB/67°F WB70°F DB
Water temperature45°F entering180°F entering

Fouling Factors: 0.0005 hr·ft²·°F/Btu for water side.

AHRI 430 Central Station Air-Handling Units

Establishes performance and construction standards for custom and semi-custom air handlers.

Certification Criteria:

  • Casing thermal performance (R-value and thermal bridging)
  • Air leakage at specified pressures
  • Casing deflection under pressure
  • Structural integrity
  • Access and serviceability

Air Leakage Classes:

ClassMaximum Leakage (CFM/ft² at 4" w.g.)
112
28
34
62
121

AHRI 440 Room Fan-Coils

Covers ratings for room-level terminal units.

Rating Conditions:

  • Cooling: 80°F/67°F entering air, 45°F entering water
  • Heating: 70°F entering air, 200°F entering water
  • Three fan speeds: high, medium, low

Published Data:

  • Capacity at each fan speed
  • Water flow rate
  • Air flow rate (CFM)
  • Sound power levels

AHRI 550/590 Water-Chilling and Heat Pump Water-Heating Packages

Comprehensive standard for chillers using mechanical compression cycle.

Primary Rating Conditions:

Chiller TypeEvaporatorCondenserApplication
Air-cooled44°F leaving water95°F entering airStandard rating
Water-cooled44°F leaving water85°F entering waterStandard rating
Evaporatively-cooled44°F leaving water75°F entering WBStandard rating

IPLV (Integrated Part Load Value): Critical metric for annual energy consumption estimation.

IPLV Calculation: IPLV = 0.010A + 0.42B + 0.45C + 0.12D

Where:

  • A = EER at 100% load, standard conditions
  • B = EER at 75% load, reduced condenser temperature
  • C = EER at 50% load, reduced condenser temperature
  • D = EER at 25% load, reduced condenser temperature

Part-Load Test Conditions:

LoadAir-Cooled Condenser TempWater-Cooled Condenser Temp
100%95°F DB85°F entering
75%75°F DB75°F entering
50%65°F DB65°F entering
25%55°F DB55°F entering

Non-Standard Rating Points: AHRI 550/590 also defines rating at:

  • Low ambient cooling conditions
  • High ambient conditions (115°F for air-cooled)
  • Ice storage charging conditions

AHRI 560 Absorption Water Chilling and Water Heating Equipment

Establishes performance criteria for absorption chillers.

Rating Conditions:

  • Single-effect: 44°F chilled water, 95°F cooling water, hot water or steam heat source
  • Double-effect: Same water temperatures, higher temperature heat source
  • COP based on heating energy input plus parasitic power

Heat Source Specifications:

  • Low-pressure steam: 12-15 psig
  • Hot water: 230-270°F
  • Direct-fired: natural gas or fuel oil

AHRI 700 Refrigerant Specifications

Defines purity requirements and testing methods for refrigerants.

Specifications Include:

  • Chemical composition limits
  • Moisture content (typically <10 ppm)
  • Non-condensable gas content
  • High boiling residue
  • Acidity
  • Particulate matter

Common Refrigerants Covered:

  • R-410A (HFC blend for residential equipment)
  • R-134a (HFC for chillers)
  • R-32 (Lower GWP alternative)
  • R-1234yf and R-1234ze (HFO low-GWP refrigerants)
  • R-717 (ammonia for industrial applications)
  • R-744 (CO₂ for transcritical systems)

AHRI 740 Performance of Refrigerant Recovery, Recycling, and Reclaim Equipment

Establishes requirements for refrigerant handling equipment.

Recovery Equipment Requirements:

  • Recovery rate (lbs/min) at specified conditions
  • Final vacuum level achievable (typically 0" Hg for vapor recovery, 4" Hg for liquid recovery on small equipment)
  • Purity of recovered refrigerant
  • Non-condensable gas separation

Recycling Equipment Standards:

  • Moisture reduction to <50 ppm
  • Acid removal
  • Particulate filtration to 10 microns
  • Oil separation efficiency

Application of AHRI Ratings

Equipment Selection

When selecting equipment, AHRI ratings provide standardized comparison:

  1. Verify Certification: Check equipment appears in AHRI directory
  2. Compare at Same Conditions: Ratings at standard conditions enable direct comparison
  3. Consider Part-Load Performance: IPLV or IEER often more important than full-load EER for annual energy use
  4. Account for Operating Conditions: Adjust for site-specific conditions when actual operating temperatures differ from rating conditions

Energy Code Compliance

ASHRAE 90.1 and IECC reference AHRI minimum efficiency requirements:

  • Equipment must meet or exceed minimum EER, SEER, IPLV values
  • Testing and rating per AHRI standards demonstrates compliance
  • Submittals include AHRI directory listing page or certification letter

Performance Verification

AHRI certification provides assurance:

  • Independent third-party testing validates manufacturer claims
  • Ratings accuracy within specified tolerances (typically ±5% for capacity, efficiency)
  • Challenge testing process addresses non-compliant equipment

Limitations and Considerations

Rating Conditions vs. Actual Operation:

  • AHRI standard conditions may not match site-specific installations
  • Actual performance varies with:
    • Outdoor ambient temperature
    • Indoor load conditions
    • Duct or piping system effects
    • Refrigerant line lengths (split systems)
    • Altitude corrections

Installation Effects:

  • Field installation quality impacts actual performance
  • Improper refrigerant charge reduces efficiency
  • Airflow restrictions lower capacity and efficiency
  • Non-standard configurations void ratings

Application Range:

  • Ratings apply to specific capacity ranges and equipment types
  • Operating outside rated range affects performance
  • Multiple rating standards may apply to single equipment category