ASHRAE 90.1-2022: Energy Standard Updates and Compliance Guide

ASHRAE 90.1-2022 Overview

ASHRAE Standard 90.1-2022 represents a significant advancement in building energy efficiency requirements, introducing new compliance pathways and updated efficiency metrics. The standard achieves approximately 15% energy cost reduction compared to the 2019 edition.

Major Changes from 2019

New Mechanical System Performance Path (MSPR)

The 2022 edition introduces Section 6.6, the Mechanical System Performance Path, as an alternative to prescriptive compliance. This path uses the Total System Performance Ratio (TSPR) to evaluate complete HVAC system efficiency.

TSPR Calculation:

TSPR = Annual Cooling Output + Annual Heating Output
       ─────────────────────────────────────────────
       Annual Energy Input (electricity + fuel)

Minimum TSPR Requirements by Climate Zone:

Climate ZoneMinimum TSPRBaseline System
1A, 2A3.8Packaged rooftop, VAV
3A, 4A3.5Packaged rooftop, VAV
5A, 6A3.2Boiler + chiller, VAV
7, 82.8Boiler + chiller, VAV

Heat Recovery Chiller Credit (COPHR)

New metric for evaluating heat recovery during chiller operation:

COPHR = Useful Heating Output / Compressor Energy Input

Systems with COPHR ≥3.0 receive prescriptive trade-off credits.

Updated Equipment Efficiency Requirements

Air-Cooled Chillers (≥150 tons):

Metric2019 Requirement2022 RequirementImprovement
Full Load EER9.710.1+4.1%
IPLV12.513.2+5.6%

Water-Cooled Chillers (300-600 tons, positive displacement):

Metric2019 Requirement2022 RequirementImprovement
Full Load kW/ton0.560.52+7.1%
IPLV0.380.35+7.9%

Boilers (≥1,000,000 Btu/h):

Type2019 Efficiency2022 Efficiency
Gas-fired, hot water82% Et90% Et (condensing)
Gas-fired, steam80% Et82% Et

Energy Recovery Ventilation

Minimum Enthalpy Recovery Ratio (ERR):

Exhaust AirflowClimate Zones 3B, 3C, 4B, 4C, 5BAll Other Zones
≥1,500 cfm50%55%
≥5,000 cfm55%60%
≥10,000 cfm60%65%

VRF and DOAS Requirements

Variable Refrigerant Flow (VRF) Systems:

Cooling CapacityMinimum IEER
<65,000 Btu/h16.0
65,000-135,000 Btu/h15.5
>135,000 Btu/h14.5

Dedicated Outdoor Air Systems (DOAS):

  • Mandatory energy recovery for systems >1,000 cfm outdoor air
  • Demand control ventilation required for spaces >500 sq ft with design occupancy >25 people

Compliance Pathways

Path Comparison

PathwayDescriptionBest For
Prescriptive (6.5)Meet all individual equipment requirementsSimple systems, standard buildings
MSPR (6.6)Meet TSPR for complete mechanical systemComplex systems, integrated design
Performance (11)Whole-building energy modelingHigh-performance, innovative designs

MSPR Advantages

  1. System Integration Credit: Accounts for heat recovery, economizers, and controls synergies
  2. Equipment Trade-offs: Higher efficiency equipment can offset lower efficiency elsewhere
  3. Innovation Allowance: Enables emerging technologies not covered by prescriptive requirements

Prescriptive Changes Summary

Fan System Power

Maximum Fan System Power (W/cfm):

System Type2019 Limit2022 Limit
CV systems, no heating/cooling0.300.28
CV systems with heating/cooling0.600.55
VAV systemsVariableVariable (-5%)

Piping Insulation

Increased Pipe Insulation Requirements:

Fluid Temp RangePipe Size2022 Insulation (inches)
40-60°F<1"1.0
40-60°F1"-4"1.5
40-60°F>4"2.0

Economizer Requirements

Integrated Economizer Requirements:

Climate ZoneCooling Capacity Threshold
1A, 1BNot required
2A, 2B, 3A≥54,000 Btu/h
All others≥33,000 Btu/h

Controls Requirements

Demand Control Ventilation (DCV)

Required for spaces meeting ALL criteria:

  • Design occupancy ≥25 people
  • Floor area ≥500 sq ft
  • Design outdoor airflow >0.3 cfm/sq ft

Setpoint Reset

Supply Air Temperature Reset:

  • Required for all VAV systems >10,000 cfm
  • Minimum reset range: 5°F from design
  • Based on zone demand or outdoor air temperature

Chilled Water Reset:

  • Required for chilled water systems >300,000 Btu/h
  • Reset based on valve position or outdoor air

Documentation Requirements

Compliance Documentation Package

  1. Mechanical schedules with efficiency ratings
  2. TSPR calculations (if using MSPR path)
  3. Controls sequences demonstrating required strategies
  4. Commissioning plan per Section 8

Testing and Balancing

  • Air system balancing within ±10% of design
  • Hydronic balancing within ±5% of design
  • Economizer functional testing required

Adoption Status

US Adoption Timeline

JurisdictionAdoption DateNotes
California (Title 24)2026Based on 90.1-2022
Washington2025State amendments
Massachusetts2025Stretch code option
Federal buildings2024GSA requirement

International Adoption

  • IECC 2024 references 90.1-2022
  • ASHRAE 189.1-2023 builds upon 90.1-2022

References

  • ASHRAE Standard 90.1-2022: Energy Standard for Sites and Buildings Except Low-Rise Residential Buildings
  • ASHRAE 90.1-2022 User’s Manual
  • PNNL Technical Support Documents for ASHRAE 90.1-2022